37
Identification
Setting
Main menu tree
...
By press >1s
By press <1s
By press or <1s
Output voltage
<230V>
Output frequency
<autosensing>
Power strategy
<normal>
Start on battery
<enabled>
Site wiring fault alarm
<disabled>
Audio Alarm Enable
<enabled>
Automatic battery test
period
<7>
Auto Restart
<enabled>
AutoBypass
<enabled>
Inv short clearance
<enabled>
LCD contrast
<+0>
Clear event log
Total events: 50
Control commands
from serial port
<enabled>
Battery quantity
<20>
EPO input polarity
<open>
HE voltage high limit
<+10%>
HE voltage low limit
<-10%>
HE frequency high limit
<+10%>
HE frequency low limit
<-10%>
Bypass frequency low
limit
<-10%>
Bypass frequency high
limit
<+10%>
Bypass voltage low
limit
<176V>
Bypass voltage high
limit
<264V>
User password
<disabled>
Password: AAAA
Setting menu tree
Fig. 5-21 Setting menu tree