ENG
37
Note:
• The through-wal height of drain hose
shouldn’t be higher than the outlet pipe
hole of indoor unit.
• Slant the drain hose slightly downwards.
The drain hose can’t be curved, raised and
fluctuant, etc.
Step 6: neaten the pipes
1
. The pipes should be placed along the wall,
bent reasonably and hidden possibly. Min.
semidiameter of bending the pipe is 10 cm.
2
. If the outdoor unit is higher than the wall hole,
you must set a U-shaped curve in the pipe
before pipe goes into the room, in order to
prevent rain from getting into the room.
wall
U-shaped curve
drain hose
the drain hose
can’t raise
upwards
the drain
hose can’t
be fluctuant
the water
outlet can’t
be fluctuant
the water outlet can’t
be placed in water
the drain hose can’t be fluctuant
Installation of outdoor unit
2
. Fix the power connection wire and signal control wire with wire clip
(only for cooling and heating unit).
Note:
• After tighten the screw, pull the power cord slightly to check if it is firm.
• Never cut the power connection wire to prolong or shorten the distance.
• The water outlet can’t be placed in
water in order to drain smoothly.