background image

© MASS ELECTRONICS Pty Ltd  2005

Page 2

DS 2.75 - MS5-01 - Microcontroller

August 2013

Installation

1. Mount in a dry and reasonable clean location free of excessive 

vibration.

2. Wire in accordance with INNOTECH connection diagrams and 

local bylaws or refer to your local distributor.

Wiring

1. Connect 240VAC supply to the correct terminals on the 

controller, observing the correct polarity of the connections.

2. Connect the EARTH to the correct terminals on all units.

3. DO NOT connect 240VAC to the control terminals.

4. Ensure that the wiring between the control station and the 

controller is correctly connected. Failure to do so will result in 

malfunctioning and may damage either or both units.

5. The maximum wire length between the control station and 

controller should not exceed 50 metres. The wiring between 

these devices should not be run in parallel with conductors 

carrying high current.

Digital Inputs

DI1 Timeclock

The Microcontroller is equipped with a remote timeclock enable 

function.

When the time clock input (DI1) is "ON", the Microcontroller will run 

in A/C mode.

DI2 

After Hours

The Microcontroller is equipped with an After Hours timer.

When a pulse is received on the After Hours input (DI2), the unit will 

run in A/C mode for the period set in Program Parameter 6.

If a pulse is received while the Microcontroller is in After Hours mode, 

it will toggle off.

DI3 

Unit Disable

The Microcontroller is equipped with an AC unit disable function.

If the disable input (DI3) is "ON" for the period set in Program 

Parameter 7, the Microcontroller will shut down the Air Conditioning 

unit. When the Microcontroller is disabled, the ON/OFF LED will flash 

to indicate that the Microcontroller is being overridden.

When the remove disable input is opened, the unit can be restarted 

by pressing the A/C button.

DI4 

Device Disable

The Microcontroller is equipped with a Heat/Cool disable.

If the remote disable input (DI4) is "ON" for the period set in 

Parameter 9, the Microcontroller will shut down the specified A/C 

devices (Heat only, Cool only or Heat and Cool) as indicated in 

Parameter 8. If an A/C device is being overridden, the corresponding 

Mode LED (Heat/Cool) will flash. When the input is turned off, the 

unit will restart the A/C devices as required.

When the input is turned off, the unit will restart the A/C devices as 

required.

Analogue Outputs

AO1 

Chilled Water Valve

The Microcontroller is equipped with an output for a chilled water 

valve. When the Microcontroller is in cooling mode, the analogue 

output will vary linearly from 0-10V over the range of the PB 

(Parameter 4).

Digital Display

The digital display will show the following error codes to assist with 

fault finding.

•  Display Reads "99.9"

 

This indicates either a faulty sensor or faulty sensor    

 cabling.

•  Display Reads "HLP"

 

This indicates that communication between the Control  

 

Station and Controller is not operating.

First check the interconnecting cabling and if this is OK, contact your 

local Innotech Distributor.

Adjustable Parameters

Jumper Settings on the Control Station

Jumper #1 (JP1 Rev)

Not Used.

Jumper #2 (JP2 H/C)

Not Used.

Jumper #3 (JP3 Fan)

This jumper is used to select continuous fan operation or fan cycles 

with heating.

When the link is closed, the fan runs continuously on cooling and 

cycles with heating.

Jumper settings will not take effect until supply power is reset to 

the controller.

Program Functions on the Control Station

All variable settings for the Microcontroller are adjusted at the 

Control Station.

Programming Mode

To enter Programming Mode, depress and hold the 

 and 

         

buttons for 5 seconds. The display will become blank indicating that 
you are in the Programming Mode. Release both keys and the display 
will show parameter 0.

While in the programming mode, the following buttons are active:

Change to the next parameter

Increase the current parameter value

Decrease the current parameter value

To Exit the Programming Mode, depress the 

 and 

 buttons 

and the new setting will be saved.

This product should only be installed by qualified personnel.

Отзывы: