DS 2.75 - MS5-01 - Microcontroller

August 2013

STANDARD CONNECTION

240VAC Supply

Neutral

Earth

TIMECLOCK

AFTER HOURS

UNIT DISABLE

DEVICE DISABLE

Screen  MUST  be

connected  at  both

the Control Station

and  the  Controller

P+
P-
C+

C-

SHLD

SENSOR

(Voltage Free Contacts by other)

TYPICAL DIGITAL INPUTS

To CHW

Valve

(Voltage Free Contacts by other)

ALTERNATIVE DIGITAL INPUTS

+24V

0V

DI#+

DI#-

NOTE:

ALL DIGITAL INPUTS:-
Rated at: 
24V (AC or DC)

Com

0-10V DC

D

I  4

D

I  1

D

I  2

D

I  3

Po

w

er

Po

w

er

Fan Lo

Heat

Fan Med

Fan Hi

0V

NOTE:

ALL OUTPUT RELAYS:-
Rated at: 
24V   16Amp Resistive
24VAC 6Amp Inductive
Com = Common Contact
NO    = Normally Open Contact
ANALOGUE OUTPUT:-
Rated at: 
0-10VDC into >2k  Load
                   

24V

* MAXIMUM CABLE LENGTH BETWEEN THE CONTROL STATION & CONTROLLER IS 50 METRES.