ModbusData
Index
Bit
Variable Description
DataType
Default
Min
Max
Direction
HoldingRegister
1
32
Command Output Universal Channel 1
Float
0
0.0
100.0
ReadWrite
HoldingRegister
3
32
Command Output Universal Channel 2
Float
0
0.0
100.0
ReadWrite
HoldingRegister
5
32
Command Output Universal Channel 3
Float
0
0.0
100.0
ReadWrite
HoldingRegister
7
32
Command Output Universal Channel 4
Float
0
0.0
100.0
ReadWrite
HoldingRegister
9
32
Command Output Universal Channel 5
Float
0
0.0
100.0
ReadWrite
HoldingRegister
11
32
Command Output Universal Channel 6
Float
0
0.0
100.0
ReadWrite
HoldingRegister
13
32
Command Output Universal Channel 7
Float
0
0.0
100.0
ReadWrite
HoldingRegister
15
32
Command Output Universal Channel 8
Float
0
0.0
100.0
ReadWrite
HoldingRegister
17
32
Command Output Universal Channel 9
Float
0
0.0
100.0
ReadWrite
HoldingRegister
19
32
Command Output Universal Channel 10
Float
0
0.0
100.0
ReadWrite
HoldingRegister
21
32
Command Output Y1
Float
0
0.0
100.0
ReadWrite
HoldingRegister
23
32
Command Output Y2
Float
0
0.0
100.0
ReadWrite
HoldingRegister
31
32
Preset Value Counter 1
Float
0
0.0
999999
ReadWrite
HoldingRegister
33
32
Preset Value Counter 2
Float
0
0.0
999999
ReadWrite
HoldingRegister
35
32
Scaling Counter 1
Float
1.0
-999.9
999.9
ReadWrite
HoldingRegister
37
32
Scaling Counter 2
Float
1.0
-999.9
999.9
ReadWrite
HoldingRegister
39
32
Setpoint Thermostat 1
Float
25.0
-999.9
999.9
ReadWrite
HoldingRegister
41
32
Hysteresis Thermostat 1
Float
2.0
-999.9
999.9
ReadWrite
HoldingRegister
43
32
Setpoint Thermostat 2
Float
25.0
-999.9
999.9
ReadWrite
HoldingRegister
45
32
Hysteresis Thermostat 2
Float
2.0
-999.9
999.9
ReadWrite
ModbusData
Index
Bit
Variable Description
DataType
Default
Min
Max
Direction
InputRegister
1
32
Current Value Universal Channel 1
Float
Read
InputRegister
3
32
Current Value Universal Channel 2
Float
Read
InputRegister
5
32
Current Value Universal Channel 3
Float
Read
InputRegister
7
32
Current Value Universal Channel 4
Float
Read
InputRegister
9
32
Current Value Universal Channel 5
Float
Read
InputRegister
11
32
Current Value Universal Channel 6
Float
Read
InputRegister
13
32
Current Value Universal Channel 7
Float
Read
InputRegister
15
32
Current Value Universal Channel 8
Float
Read
InputRegister
17
32
Current Value Universal Channel 9
Float
Read
InputRegister
19
32
Current Value Universal Channel 10
Float
Read
InputRegister
21
32
Current Value Output Y1
Float
Read
InputRegister
23
32
Current Value Output Y2
Float
Read
InputRegister
25
16
Auto/Manual status Universal Ch Outputs
Bit-Field
Read
InputRegister
26
16
Function status Universal Ch Outputs
Bit-Field
Read
InputRegister
27
16
Auto/Manual status Digital Outputs
Bit-Field
Read
InputRegister
28
16
Function status Digital Outputs
Bit-Field
Read
InputRegister
29
16
Auto/Manual status Analog Outputs
Bit-Field
Read
InputRegister
30
16
Function status Analog Outputs
Bit-Field
Read
InputRegister
31
32
Current Value of Counter 1
Float
Read
InputRegister
33
32
Current Value of Counter 2
Float
Read