The setting in this menu takes care of the periodic saving of the pulse counters in case of a power failure. So
if for example the counter was saved every 10 minutes, the memory cell would be guaranteed for the next
20 years. Saving less frequently will extend the time proportionally (15 minutes = 30 years, 20 minutes = 40
years and so on).
As for the thermostat functions, set point could be changed from the BMS. Changing it regularly will be fine
(as per pulse counter). The issue would come if you were to do ambient tracking on the BMS or similar
functions, where the set-point would constantly change damaging the flash memory in the long run. If you
plan on using ambient tracking, a solution would be to filter the required set-point changes within the BMS
and send them to Link IO only every 15 minutes for example.
Buzzer “beeping” mode
By default, the on-board buz
zer gives a feedback “beeping” on every key pressed.
This can be disabled here selecting “NO” and effectively muting the buzzer.
(the buzzer will still beep only once when the cursor is on top or a parameter and cycling from the maximum
value to its minimum or viceversa)
Setting log in password
I
t is possible to customise the settings password. Default is “1234”, but you can use any number between
0000 and 9999.
Please save and remember your password.