Auto/Manual
The “Auto/Manual” section allows to configure outp
uts to a fixed status or value.
When an output is configured in “Manual”, any demand from the BMS,
the BMS watchdog active or any
function applied to the output will be bypassed and the output maintained at the desired Manual
configuration.
For the expansion, the status of the expansion outputs is dictated by the main unit. So, if the expansion is
disconnected from the main unit and the expansion watchdog is enabled, the expansions output will be
driven safely to their watchdog position, even if the output was in Manual mode. If the watchdog is not
enabled, the expansion will maintain the outputs to their last demand status until the expansion is restarted.
Universal Channels
Any Universal Channel configured as Output (0-10V or PWM) will be available here to be configured in either
AUTO (controlled by BMS, watchdog or functions) or in MANUAL mode, where a fixed value is set.
In the example below, Universal Channels 1, 2 and 4 are configured as Outputs and Universal Channel 2 is
fixed to a manual position of 5V (50%)
Digital Outputs
All Digital Outputs are available to be configured in either AUTO (controlled by BMS, watchdog or functions)
or in MANUAL mode, where a fixed position is set.
In the example below, Digital Outputs 2 and 3 are fixed to a manual state, with Digital Output 2 being OFF
and Digital Output 3 being ON
Analog Outputs (main unit only)
On the main unit 2 extra Analog Outputs are available to be configured in either AUTO (controlled by BMS,
watchdog or functions) or in MANUAL mode, where a fixed value is set.
In the example below, Analog Output 2 is fixed to a manual position of 7.5V (75%)