Document name: Link IO - Manual
Document date: 1.2 10/02/2020
34
Here is a quick overview of the default configuration
Parameter main group
Parameter group
Parameter
Factory default setting
Configure I/O
Universal Channels (all)
Direction
INPUT
Type
10K3A1
Filter
5
Analog outputs (main unit, Y1 and
Y2)
Type
0-10V
Output when offline (watchdog) for
Universal Channels (visible when
configured as output)
Value
0%
Output when offline (watchdog) for
Digital Outputs
Value
OFF (relay disengaged)
Output when offline (watchdog) for
Analog Outputs (main unit)
Value
0%
Auto/Manual
Auto/Manual for Universal Channels
(visible when configured as output)
Auto/Manual
AUTO
Manual value
0%
Auto/Manual for Digital Outputs
Auto/Manual
AUTO
Manual value
OFF
Auto/Manual for Analog Outputs
(main unit)
Auto/Manual
AUTO
Manual value
0%
Functions
Functions (in general)
All inputs
NOT SELECTED (disabled)
All outputs
NOT SELECTED (disabled)
Network settings
Watchdog BMS
Enable
DISABLED
Timeout
30s
Watchdog expansions
Enable
DISABLED
RS485 device only
Protocol
MODBUS
RS485 device, Modbus
Modbus ID
1
Baudrate
19200
Parity
NONE
Stop bits
1
RS485 device, BACnet
BACnet ID
1
BACnet MAC address
1
Baudrate
19200
COV setting
0.1
IP device, Modbus
Modbus ID
1
Modbus port
502
IP device, BACnet
BACnet ID
1
BACnet port
47808
COV setting
0.1
IP device, IP port settings
IP address
192.168.80.91
Subnet
255.255.255.0
Gateway
192.168.80.1
DNS
0.0.0.0
General settings
Expansions
Number of expansions
0
Temperature readings
Celsius of Fahrenheit
CELSIUS
Pulse counter function
Flash saving frequency
Every 15min
Display user access password change
Password
1234