52
SSA-SVX06B-EN
Maintenance
Monthly
Conduct the following maintenance inspections once per month.
The following warning complies with State of California law, Proposition 65.
1.
Inspect air filters and clean (or replace) if necessary.
2. Check unit wiring to ensure all connections are tight and that the wiring insulation is intact.
3. Check drain pans and condensate piping to insure they are free of obstacles.
4. Manually rotate the indoor fan to ensure proper operation.
5. Inspect the evaporator coils for dirt and debris. If the coils appear dirty, clean them.
Table 21. Belt Tension Measurement and Deflection
Belts Cross
Section
Small Pitch
Diameter
Range
Deflection Force (Lbs.)
Standard V-Belt
V-Belt with Molded Notches
Min.
Max.
Min.
Max.
A
3.0 - 3.6
3
4 1/2
3 7/8
5 1/2
3.8 - 4.8
3 1/2
5
4 1/2
6 1/4
5.0 - 7.0
4
5 1/2
5
6 7/8
B
3.4 - 4.2
4
5 1/2
5 3/4
8
4.4 - 5.6
5 1/8
7 1/8
6 1/2
9 1/8
5.8 - 8.8
6 3/8
8 3/4
7 3/8
10 1/8
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this product during installation,
maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic
fibers known to the state of California to cause cancer through inhalation. You MUST wear all
necessary Personal Protective Equipment (PPE) including gloves, eye protection, mask, long
sleeves and pants when working with products containing fiberglass wool. Exposition to glass
wool fibers without all necessary PPE equipment could result in cancer, respiratory, skin or eye
irritation, which could result in death or serious injury.
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power
cannot be inadvertently energized. For variable frequency drives or other energy storing
components provided by Trane or others, refer to the appropriate manufacturer’s literature for
allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that
all capacitors have discharged. Failure to disconnect power and discharge capacitors before
servicing could result in death or serious injury.
For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN
NOTICE:
Operating Under Vacuum!
Do not operate or apply power to the compressor while under a vacuum. Failure to follow
these instructions will result in compressor failure.