SSA-SVX06B-EN
43
Installation
Note:
The above potentiometer voltage readings can be verified via the provided test points
located next to each potentiometer. Use a DC voltmeter to the Vdc reading between those
points and common.
Table 19.
DA Heat Setpoint
Voltage
(Vdc)
Setpoint
(ºF)
Voltage
(Vdc)
Setpoint
(ºF)
Voltage
(Vdc)
Setpoint
(ºF)
Voltage
(Vdc)
Setpoint
(ºF)
0
50
0.98
75
1.61
100
2.06
125
0.09
51
1
76
1.63
101
2.08
126
0.13
52
1.03
77
1.66
102
2.09
127
0.16
53
1.06
78
1.69
103
2.11
128
0.2
54
1.08
79
1.71
104
2.12
129
0.24
55
1.11
80
1.72
105
2.13
130
0.28
56
1.13
81
1.74
106
2.13
131
0.31
57
1.16
82
1.76
107
2.14
132
0.35
58
1.18
83
1.78
108
2.16
133
0.39
59
1.21
84
1.79
109
2.17
134
0.42
60
1.23
85
1.81
110
2.19
135
0.46
61
1.26
86
1.83
111
2.2
136
0.5
62
1.28
87
1.84
112
2.21
137
0.53
63
1.31
88
1.86
113
2.23
138
0.57
64
1.33
89
1.88
114
2.24
139
0.61
65
1.36
90
1.89
115
2.25
140
0.65
66
1.38
91
1.91
116
2.26
141
0.68
67
1.41
92
1.93
117
2.28
142
0.72
68
1.43
93
1.95
118
2.29
143
0.76
69
1.46
94
1.96
119
2.3
144
0.79
70
1.48
95
1.98
120
2.32
145
0.83
71
1.51
96
2
121
2.33
146
0.87
72
1.53
97
2.01
122
2.34
147
0.9
73
1.56
98
2.03
123
2.36
148
0.94
74
1.58
99
2.05
124
2.37
149
—
—
—
—
—
—
2.4
150
Table 20. DA Cool Setpoint (Mounted Above Keyboard)
Setpoint (°F)
Voltage (Vdc)
Setpoint (°F)
Voltage (Vdc)
Setpoint (°F)
Voltage (Vdc)
40
<0.1
51
1.3
61
2
41
0.2
52
1.35
62
2.05
42
0.3
53
1.45
63
2.1
43
0.45
54
1.55
64
2.13
44
0.55
55
1.65
65
2.17
45
0.7
56
1.7
66
2.21
46
0.8
57
1.75
67
2.27
47
0.95
58
1.83
68
2.3
48
1.05
59
1.9
69
2.35
49
1.15
60
1.95
70
>2.4
50
1.25