26
SSA-SVX06B-EN
Electrical Data - Standard, SZVAV and 2-Speed VFD
Table 7.
Unit Wiring with Electric Heat (Single Point Connection) — 5-10 Ton Standard Air Handlers — 60 Hz
Tons Used
With
Heater Model
No.
Heater KW
Rating
(a)
Unit Power
Supply Control
Stages
Minimum
Circuit
Ampacity
(b)
Maximum
Fuse or HACR
Circuit
Breaker
Size
(b)(c)
5
TWE061D1
TWE061E1
BAYHTRL106A 4.33/5.76
208-230/1/60
1
33.5/37.4
35/40
BAYHTRL112A 8.65/11.52
1
59.5/67.4
60/70
BAYHTRL117A 12.98/17.28
1
85.5/97.4
90/100
BAYHTRL123A 17.31/23.04
2
111.5/127.4
(d)
125/150
7½
TWE090D1
TWE090E1
BAYHTRL106A 4.33/5.76
1
34.5/37.8
40/40
BAYHTRL112A 8.65/11.52
1
60.5/67.8
(d)
70/70
BAYHTRL117A 12.98/17.28
1
86.5/97.8
90/100
BAYHTRL123A 17.31/23.04
2
112.5/127.8
(d)
125/150
BAYHTRL129A 21.63/28.80
2
138.6/157.8
(d)
150/175
10
TWE120D1
TWE120E1
BAYHTRL106A 4.33/5.76
1
36.6/39.6
40/45
BAYHTRL112A 8.65/11.52
1
62.6/69.6
(d)
70/70
BAYHTRL117A 12.98/17.28
1
88.6/99.6
90/100
BAYHTRL123A 17.31/23.04
2
114.6/129.6
(d)
125/150
BAYHTRL129A 21.63/28.80
2
140.7/159.6
(d)
150/175
5
TWE061D3
TWE061E3
BAYHTRL305A 3.76/5.00
208-230/3/60
1
16.1/18
20/20
BAYHTRL310A 7.48/9.96
1
29/33
30/35
BAYHTRL315A 11.24/14.96
1
42.2/48
45/50
BAYHTRL325A 18.72/24.92
2
68/77.9
(d)
70/80
7½
TWE090D3
TWE090E3
BAYHTRL305A 3.76/5.00
1
19.6/21.3
25/25
BAYHTRL310A 7.48/9.96
1
32.5/36.2
35/40
BAYHTRL315A 11.24/14.96
1
45.7/51.2
50/60
BAYHTRL325A 18.72/24.92
2
71.5/82
(d)
80/90
BAYHTRL335A 26.20/34.88
2
98.7/112
(e)
100/125
10
TWE120D3
TWE120E3
BAYHTRL305A 3.76/5.00
1
21/23
25/30
BAYHTRL310A 7.48/9.96
1
34/38
35/40
BAYHTRL315A 11.24/14.96
1
47/53
50/60
BAYHTRL325A 18.72/24.92
2
73/83
(d)
80/90
BAYHTRL335A 26.20/34.88
2
98.7/113
(e)
100/125
continued on next page