8
RT-SVB98B-EN
Screen shown only for units with Energy Recovery Installed
Exhaust Air Bypass Damper Control Gain
Rate Time
XXX Sec
└─┬─┘
Range 0.0-100.0
Default 0
One of the following two screens will be shown:
Only if Energy Recovery Installed and value is greater than 0.
Range 1-255 and Disable
Default 3 Min
┌─┴─┐
Energy Wheel Off Delay Time:
XXX Min
Turn Wheel Off When Temp Above Setpoint
“Disable” is displayed when the value is incremented above 255. A selection of “Disable” disables wheel shutoff
changes to screen below and allows continuous wheel operation when conditions permit.
Only if Energy Recovery Installed and value is equal to Disable.
Energy Wheel Off Delay Time: Disable
Wheel Remains On Until Call For Cooling
Screen shown only on units with Rapid Restart or Dehumidification installed
Range 15 - 50
Default 30
┌─┴─┐
Rapid DX Interstage Timing: XXX Sec
Screen shown if in this submenu
End Of Submenu (NEXT) To Enter SETUP