Ingersoll-Rand Trane Intellipak Скачать руководство пользователя страница 8

8

 RT-SVB98B-EN

Screen shown only for units with Energy Recovery Installed 

  Exhaust Air Bypass Damper Control Gain 

 

  Rate Time 

XXX  Sec  

                                └─┬─┘

 

Range 0.0-100.0 

 

Default 0 

 

 

One of the following two screens will be shown: 

    Only if Energy Recovery Installed and value is greater than 0. 

    

Range 1-255 and Disable 

 

Default 3 Min 

 

   ┌─┴─┐

 

  Energy Wheel Off Delay Time:  

XXX Min 

 

  Turn Wheel Off When Temp Above Setpoint   

 
“Disable” is displayed when the value is incremented above 255.  A selection of “Disable”  disables wheel shutoff 
changes to screen below and allows continuous wheel operation when conditions permit. 

Only if Energy Recovery Installed and value is equal to Disable. 

  Energy Wheel Off Delay Time:    Disable   
  Wheel Remains On Until Call For Cooling   

 

Screen shown only on units with Rapid Restart or Dehumidification installed 
 

 

Range 15 - 50 

 

Default 30 

 

                                  ┌─┴─┐

 

 

Rapid DX Interstage Timing:      XXX Sec 

 

 

 

 

Screen shown if in this submenu 

   

 

  End Of Submenu (NEXT) To Enter SETUP 

 

 

Содержание Trane Intellipak

Страница 1: ...and labels that are attached to the equipment Control Algorithm Tuning Parameters Intellipak Rooftop Units General Service Bulletin ATTENTION Warnings Cautions and Notices appear at appropriate sectio...

Страница 2: ...plays showing the correct factory preset values Any particular unit will contain only a portion of this list of displays WARNING Personal Protective Equipment PPE Required Failure to wear proper PPE f...

Страница 3: ...een shown only for units with Dehumidification Installed SA Reheat Control Gains Proportional XX X F Reset Time XXX Sec Range 0 2 20 0 Range 5 600 Default 3 3 Default 50 Note XXX Sec field becomes DIS...

Страница 4: ...Default 1800 Note XXX Sec field becomes DISABLE if 3600 seconds Screen shown only for CV units Zone Control Occupied Cooling Gains Proport Bias XXX Max Cy Rate X X CPH Range 0 400 Range 1 5 6 0 Defaul...

Страница 5: ...for the number of configured heat stages If heat stages are not configured it will place 30 F in the field as a default until heat stages are configured This will happen once at power up if needed an...

Страница 6: ...pply Air Temp High Limit XX X F Range 80 140 Default 120 Screen shown only for VAV units Supply Air Pressure Gain Proportional XX X IWC Reset Time XXX Sec Range 0 2 20 0 Range 1 60 Default 3 3 Default...

Страница 7: ...0 Default 17 s Default 80 Note XXXXs field becomes DISABLE and Prop and Feedforward items are not shown if Reset Time 1000 s on Ipak 1 units only Screen shown only for RT or RT AH units with DX Coolin...

Страница 8: ...hen Temp Above Setpoint Disable is displayed when the value is incremented above 255 A selection of Disable disables wheel shutoff changes to screen below and allows continuous wheel operation when co...

Страница 9: ...et Time w VSC wo VSC 100 Sec 50 Sec ___________ Setup CV Air Economizer Control Gains Proportional 10 0 F ___________ Setup Reset Time DISABLE ___________ Setup Rate Time 0 Sec ___________ Setup Bias...

Страница 10: ...rease industrial productivity and efficiency We are a 13 billion global business committed to a world of sustainable progress and enduring results For more information visit www ingersollrand com Inge...

Отзывы: