Ingersoll-Rand Trane Intellipak Скачать руководство пользователя страница 5

RT-SVB98B-EN

Screen shown only for CV units with Air Economizer, or SZVAV installed 

CV 

CV Air Econ Control   Rate Time 

 

 

SZVAV 

SZVAV Cooling Control Rate Time 

Default 0 

 

           

┌─────────────────┴───────────────────┐┌─┴─┐

 

  XXXXXXXXXXXXXXXXXXXXXX XXXXXXXXX XXX  Sec 

 

  Proport Bias  XX °F 

 

 

 

 

             └─┬─┘

 

 

Range 0-40 

 

 

 

 

Default 5 

 

 

 

 

Screen shown only for units with Staged Gas or Electric Heat installed 

  Zone Control Occupied Heating Gains 

 

  Proportional XX.X %/F  Reset Time  XXX Sec 

 

             └─┬─┘                └─┬─┘

 

 

Range 2.0-200.0 

 

Range 90-3600 

 

 

Default 30.0 

 

Default 1800 

 

Note 1 : “XXX Sec” field becomes “DISABLE” if > 3600 seconds 

 

Note 2: The Proportional Gain parameter depends on the number of configured heat stages for proper algorithm 
performance.  The HI will automatically adjust this parameter to the proper setting defined below if it detects the 
incorrect value for the number of configured heat stages.  If heat stages are not configured it will place 30 %/F in the 
field as a default until heat stages are configured. This will happen once at power up if needed and applies to all units. 
 

Product 

Staged Heat Type 

Number of 

Stages 

Proportional Gain 

IPak I 

Gas  

30.0 %/F 

IPak I 

Electric 

45.0 %/F 

IPak II

 

Gas 2 

30.0 

%/F 

IPak II 

Electric - 90 kw 

45.0 %/F 

IPak II 

Electric – 140 kw 

60.0 %/F 

IPak II 

Electric – 265 kw 

75.0 %/F 

Ipak II 

Electric - 300 kw 

75.0 %/F 

 

 

Screen shown only for units with Staged Gas or Electric Heat installed 

  Zone Control Occupied Heating Gains 

 

  Proport Bias XXX  % 

Max Cy Rate X.X CPH 

 

             └─┬─┘                └─┬─┘

 

 

Range 0-400 

 

Range 1.5-6.0 

 

 

Default 0 

 

Default 5.0 

 

 

 

Zone Control Modulating Heat Gain 

When CV 

SZVAV Heating Control Gains 

When SZVAV 

 ┌──────────────────┴────────────────────┐

 

  XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX  
  Proportional XX.X %/F  Reset Time  XXX Sec 

 

             └─┬─┘                └─┬─┘

 

 

Range 0.2-50.0 

  Range 90-3600 

 

 

Default 8.0 

  Default 1200 

 

Note: “XXX Sec” field becomes “DISABLE” if > 3600 seconds 

Содержание Trane Intellipak

Страница 1: ...and labels that are attached to the equipment Control Algorithm Tuning Parameters Intellipak Rooftop Units General Service Bulletin ATTENTION Warnings Cautions and Notices appear at appropriate sectio...

Страница 2: ...plays showing the correct factory preset values Any particular unit will contain only a portion of this list of displays WARNING Personal Protective Equipment PPE Required Failure to wear proper PPE f...

Страница 3: ...een shown only for units with Dehumidification Installed SA Reheat Control Gains Proportional XX X F Reset Time XXX Sec Range 0 2 20 0 Range 5 600 Default 3 3 Default 50 Note XXX Sec field becomes DIS...

Страница 4: ...Default 1800 Note XXX Sec field becomes DISABLE if 3600 seconds Screen shown only for CV units Zone Control Occupied Cooling Gains Proport Bias XXX Max Cy Rate X X CPH Range 0 400 Range 1 5 6 0 Defaul...

Страница 5: ...for the number of configured heat stages If heat stages are not configured it will place 30 F in the field as a default until heat stages are configured This will happen once at power up if needed an...

Страница 6: ...pply Air Temp High Limit XX X F Range 80 140 Default 120 Screen shown only for VAV units Supply Air Pressure Gain Proportional XX X IWC Reset Time XXX Sec Range 0 2 20 0 Range 1 60 Default 3 3 Default...

Страница 7: ...0 Default 17 s Default 80 Note XXXXs field becomes DISABLE and Prop and Feedforward items are not shown if Reset Time 1000 s on Ipak 1 units only Screen shown only for RT or RT AH units with DX Coolin...

Страница 8: ...hen Temp Above Setpoint Disable is displayed when the value is incremented above 255 A selection of Disable disables wheel shutoff changes to screen below and allows continuous wheel operation when co...

Страница 9: ...et Time w VSC wo VSC 100 Sec 50 Sec ___________ Setup CV Air Economizer Control Gains Proportional 10 0 F ___________ Setup Reset Time DISABLE ___________ Setup Rate Time 0 Sec ___________ Setup Bias...

Страница 10: ...rease industrial productivity and efficiency We are a 13 billion global business committed to a world of sustainable progress and enduring results For more information visit www ingersollrand com Inge...

Отзывы: