RT-SVB98B-EN

Screen shown only for units with Power Exhaust with Statitrac installed and Reset Time set to DISABLE  

  Space Pressure Control 

 

  Integral Gain 

XX.X  %/IWC  

                              └─┬─┘

 

Range 0.5-60.0 

 

Default 6.0 

 

 

or 

Screen shown only on units with Power Exhaust or Return Fan with Statitrac installed 
(with IntelliPak II RTM, ECEM and HI) 

 

Range 0.2-20.0 

 

Default 0.5 

 

                               ┌─┴─┐

 

 

Space Press Control:   Prop: XX.X %/IWC 

 

 

Reset Time XXXXXXX     Feedforward XXX % 

 

           └───┬───┘                └─┬─┘

 

 

Range 1-1000 s 

 

Range 0-100 

 

 

Default 17 s 

 

Default 80 

 

 

Note: “XXXXs” field becomes “DISABLE” and “Prop:” and “Feedforward:” items are not shown if Reset Time > 1000 s 
on Ipak 1 units only

 

 

Screen shown only for RT or RT AH units with DX Cooling 

  Low Ambient Fan Control Gain 

 

  Proportional XX.X %/F 

Reset Time XXX Sec 

 

             └─┬─┘                └─┬─┘

 

 

Range 0.2-20.0 

 

Range 5-600 

 

 

Default 2.0 

 

Default 90 

 

 

Screen shown only for RT or RT AH units with DX Cooling 

  Low Ambient Fan Control Gain 

 

  Rate Time 

XXX  Sec  

                                └─┬─┘

 

Range 0.0-50.0 

 

Default 0 

 

 

Screen shown only for units with Energy Recovery Installed 

  Exhaust Air Bypass Damper Control Gain 

 

  Proportional XX.X %/F 

Reset Time XXX Sec 

 

             └─┬─┘                └─┬─┘

 

 

Range 0.2-20.0 

 

Range 1-200 

 

 

Default 5.0 

 

Default 5 

 

 

Содержание Trane Intellipak

Страница 1: ...and labels that are attached to the equipment Control Algorithm Tuning Parameters Intellipak Rooftop Units General Service Bulletin ATTENTION Warnings Cautions and Notices appear at appropriate sectio...

Страница 2: ...plays showing the correct factory preset values Any particular unit will contain only a portion of this list of displays WARNING Personal Protective Equipment PPE Required Failure to wear proper PPE f...

Страница 3: ...een shown only for units with Dehumidification Installed SA Reheat Control Gains Proportional XX X F Reset Time XXX Sec Range 0 2 20 0 Range 5 600 Default 3 3 Default 50 Note XXX Sec field becomes DIS...

Страница 4: ...Default 1800 Note XXX Sec field becomes DISABLE if 3600 seconds Screen shown only for CV units Zone Control Occupied Cooling Gains Proport Bias XXX Max Cy Rate X X CPH Range 0 400 Range 1 5 6 0 Defaul...

Страница 5: ...for the number of configured heat stages If heat stages are not configured it will place 30 F in the field as a default until heat stages are configured This will happen once at power up if needed an...

Страница 6: ...pply Air Temp High Limit XX X F Range 80 140 Default 120 Screen shown only for VAV units Supply Air Pressure Gain Proportional XX X IWC Reset Time XXX Sec Range 0 2 20 0 Range 1 60 Default 3 3 Default...

Страница 7: ...0 Default 17 s Default 80 Note XXXXs field becomes DISABLE and Prop and Feedforward items are not shown if Reset Time 1000 s on Ipak 1 units only Screen shown only for RT or RT AH units with DX Coolin...

Страница 8: ...hen Temp Above Setpoint Disable is displayed when the value is incremented above 255 A selection of Disable disables wheel shutoff changes to screen below and allows continuous wheel operation when co...

Страница 9: ...et Time w VSC wo VSC 100 Sec 50 Sec ___________ Setup CV Air Economizer Control Gains Proportional 10 0 F ___________ Setup Reset Time DISABLE ___________ Setup Rate Time 0 Sec ___________ Setup Bias...

Страница 10: ...rease industrial productivity and efficiency We are a 13 billion global business committed to a world of sustainable progress and enduring results For more information visit www ingersollrand com Inge...

Отзывы: