![Ingersoll-Rand Trane Intellipak Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/ingersoll-rand/trane-intellipak/trane-intellipak_general-service-bulletin_2059244004.webp)
4
RT-SVB98B-EN
Screen shown only for units with Hydronic Heat or Modulating Gas Heat installed
Range 0.2-20.0
Default 2.0
┌─┴─┐
Mod Heat Gains
Proportional XX.X %/F
Reset Time
XXX Sec
Rate Time XXX Sec
└─┬─┘ └─┬─┘
Range 5-600
Range 0-100
Default 90
Default 0
Screen shown only for CV units
Zone Control Occupied Cooling Gains
Proportional XX.X %/F Reset Time XXX Sec
└─┬─┘ └─┬─┘
Range 2.0-200.0 Range 90-3600
Default 90
Default 1800
Note: “XXX Sec” field becomes “DISABLE” if > 3600 seconds
Screen shown only for CV units
Zone Control Occupied Cooling Gains
Proport Bias XXX %
Max Cy Rate X.X CPH
└─┬─┘ └─┬─┘
Range 0-400
Range 1.5-6.0
Default 0
Default 3.0
Screen shown only for CV units with Air Economizer, or SZVAV installed
CV Air Economizer Control Gains
When CV
SZVAV Cooling Control Gains
When SZVAV
┌──────────────────┴────────────────────┐
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
Proportional XX.X %/F Reset Time XXX Sec
└─┬─┘ └─┬─┘
Range 0.2-50.0
Range 90-3600
Default
CV Air: 10.0
SZVAV: 6
Default
CV Air: Disable
SZVAV: 1200
Note: “XXX Sec” field becomes “DISABLE” if > 3600 seconds