Screen shown only for units with Hydronic Heat or Modulating Gas Heat installed 

Range 0.2-20.0 

 

Default 2.0 

 

                                 ┌─┴─┐

 

  Mod Heat Gains 

Proportional XX.X %/F 

 

  Reset Time 

XXX  Sec 

Rate Time  XXX Sec 

 

             └─┬─┘                └─┬─┘

 

 

Range 5-600 

 

Range 0-100 

 

 

Default 90 

 

Default 0 

 

 

Screen shown only for CV units 

  Zone Control Occupied Cooling Gains 

 

  Proportional XX.X %/F  Reset Time  XXX Sec 

 

             └─┬─┘                └─┬─┘

 

 

Range 2.0-200.0    Range 90-3600 

 

 

Default 90 

  Default 1800 

 

Note: “XXX Sec” field becomes “DISABLE” if > 3600 seconds 

 

Screen shown only for CV units 

  Zone Control Occupied Cooling Gains 

 

  Proport Bias XXX  % 

Max Cy Rate X.X CPH 

 

             └─┬─┘                └─┬─┘

 

 

Range 0-400 

 

Range 1.5-6.0 

 

 

Default 0 

 

Default 3.0 

 

 

Screen shown only for CV units with Air Economizer, or SZVAV installed 
 
 

CV Air Economizer Control Gains 

When CV 

SZVAV Cooling Control Gains 

When SZVAV 

 ┌──────────────────┴────────────────────┐

 

  XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX  
  Proportional XX.X %/F  Reset Time  XXX Sec 

 

             └─┬─┘                └─┬─┘

 

 

Range 0.2-50.0 

  Range 90-3600 

 

 

Default 
CV Air: 10.0 
SZVAV: 6 
 

 Default 

 

CV Air: Disable 
SZVAV: 1200 

 

Note: “XXX Sec” field becomes “DISABLE” if > 3600 seconds 

Содержание Trane Intellipak

Страница 1: ...and labels that are attached to the equipment Control Algorithm Tuning Parameters Intellipak Rooftop Units General Service Bulletin ATTENTION Warnings Cautions and Notices appear at appropriate sectio...

Страница 2: ...plays showing the correct factory preset values Any particular unit will contain only a portion of this list of displays WARNING Personal Protective Equipment PPE Required Failure to wear proper PPE f...

Страница 3: ...een shown only for units with Dehumidification Installed SA Reheat Control Gains Proportional XX X F Reset Time XXX Sec Range 0 2 20 0 Range 5 600 Default 3 3 Default 50 Note XXX Sec field becomes DIS...

Страница 4: ...Default 1800 Note XXX Sec field becomes DISABLE if 3600 seconds Screen shown only for CV units Zone Control Occupied Cooling Gains Proport Bias XXX Max Cy Rate X X CPH Range 0 400 Range 1 5 6 0 Defaul...

Страница 5: ...for the number of configured heat stages If heat stages are not configured it will place 30 F in the field as a default until heat stages are configured This will happen once at power up if needed an...

Страница 6: ...pply Air Temp High Limit XX X F Range 80 140 Default 120 Screen shown only for VAV units Supply Air Pressure Gain Proportional XX X IWC Reset Time XXX Sec Range 0 2 20 0 Range 1 60 Default 3 3 Default...

Страница 7: ...0 Default 17 s Default 80 Note XXXXs field becomes DISABLE and Prop and Feedforward items are not shown if Reset Time 1000 s on Ipak 1 units only Screen shown only for RT or RT AH units with DX Coolin...

Страница 8: ...hen Temp Above Setpoint Disable is displayed when the value is incremented above 255 A selection of Disable disables wheel shutoff changes to screen below and allows continuous wheel operation when co...

Страница 9: ...et Time w VSC wo VSC 100 Sec 50 Sec ___________ Setup CV Air Economizer Control Gains Proportional 10 0 F ___________ Setup Reset Time DISABLE ___________ Setup Rate Time 0 Sec ___________ Setup Bias...

Страница 10: ...rease industrial productivity and efficiency We are a 13 billion global business committed to a world of sustainable progress and enduring results For more information visit www ingersollrand com Inge...

Отзывы: