66
AC-SVX002C-EN
Stopped to Starting
The following diagram shows the timing from a
stopped mode to energizing the first compressor. The
shortest allowable time would be under the following
conditions:
•
No motor restart inhibit time left from subsequent
starts
•
Evaporator Water flow occurs quickly with pump on
command
•
Need to cool (differential to start) already exists
•
The above conditions would allow a compressor to
start in about 20 seconds.
Figure 48.
Sequence of operation: stopped to starting
Stopped
Or
Run
Inhibit
Start
Command to
Lead
Compressor*
Chiller Set to Auto
Auto
(Waiting for Evaporator
Water Flow)
Energize Evaporator
Water Pump Relay
Confirm Evaporator Water
Flow Within 20 minutes
(10 Sec Filter)
Waiting to Start
Confirm Evaporator
Water Flow
(10 Second Filter)
Auto
(Waiting for
a Need to Cool)
*Lead Circuit/Compressor is determined by:
- Circuit Staging Option: Balanced Wear, Circuit 1 Lead, Circuit 2 Lead
- Compressor Staging Option: Balanced Wear, Fixed Sequence (Follows per circuit configuration)
- also influenced by lockouts, restart inhibit and diagnostics present
Pre-Position EXV
of Lead Circuit*
EXV stroke to
Preposition
Waiting to Start
Waiting for
Differential to Start
Fan Pre-Start
of Lead Circuit*
Wait for Pressure
Stabilization
(3 Seconds)
Call for Cooling: Differential to Start is met