20
AC-SVX002C-EN
Level the unit using the base rail as a reference. The
unit must be level within 1/4” (6.4 mm) over the entire
length and width. Use shims as necessary to level the
unit.
Elastomeric Isolators
N
No
otte
e:: See unit submittal, or tables in this section, for
point weights, isolator locations and isolator
selections.
1. Secure the isolators to the mounting surface using
the mounting slots in the isolator base plate. Do not
fully tighten the isolator mounting bolts at this time.
2. Align the mounting holes in the base of the unit
with the threaded positioning pins on the top of the
isolators.
3. Lower the unit onto the isolators and secure the
isolator to the unit with a nut.
4. Level the unit carefully. Fully tighten the isolator
mounting bolts.
Figure 5. Elastomeric isolator
0.50 in
1.60±0.25
Mounting molded in neoprene
3.0
2.75
0.38
1/2 - 13NC - 2B
0.56 in
F
E
G
D
A
B
C
Table 6. Elastomeric isolator specifications
Isolator
Max Load
(lbs)
Max
Deflection
(in)
A
B
C
D
E
F
G
Type
Brown 61
1500
0.5
3.0
2.75
0.38
1.60
6.25
5.00
4.63
RDP4-WR
Red 62
2250
0.5
3.0
2.75
0.38
1.60
6.25
5.00
4.63
RDP4-WR
Green 63
3000
0.5
3.0
2.75
0.38
1.60
6.25
5.00
4.63
RDP4-WR
Mounting Locations, Weights, Isolators
See figure below for mounting point location
designations.
Figure 6. Mounting point locations (top view)
1
3
5
7
C
o
n
t
r
o
l
p
a
n
e
l
2
4
6
8
N
No
otte
e:: Quantity of isolators varies with unit. See
submittal for actual number required for specific
unit.