TK 56218-2-OP-EN
105
Electric Standby Power Fails or is Disconnected
If the electric standby power source fails or is disconnected and manual
switching to Diesel Mode is selected, the unit will prompt for a switch to
Diesel Mode (
Figure 131.
Diesel Mode Prompt
•
Pressing the YES Soft Key will switch unit operation back to Diesel
Mode.
•
Pressing the NO Soft Key will allow the unit to remain in Electric Mode
even though standby power is not available.
The unit will not run and Alarm Code 91 Check Electric Ready Input will be
set as a Prevent Alarm.
Switching from Electric to Diesel
If the unit is running in Electric Mode and the Electric to Diesel Auto-Switch
Enabled feature in Guarded Access is set YES, the unit will automatically
switch to Diesel Mode operation when standby power is no longer available.
The screens shown will not appear.
If the Diesel to Electric Auto-Switch Enabled feature in Guarded Access is set
NO and standby power is disconnected or fails, the unit will not
automatically switch to Diesel mode. This is primarily designed to prevent
unauthorized diesel engine starts when the truck is indoors or on a ferry
where engine operation is strictly prohibited.