18-GJ06D2-2E-EN
39
Dip Switches
S
ca n to s e e a
vid e o o n s e ttin g
th e TAM7 DIP
S w itch e s .
Click or Scan to see a video on setting the
TAM7 DIP Switches
D
Diip
p S
Sw
wiittc
ch
h S
S1
1
•
Set the S1–1 and S1–2 dip switches for the OD
multiplier (tonnage) per the chart.
INDOOR MODEL
S1–1
S1–2
OD MULTIPLIER
TAM7A0A24H21SD
TAM7A0A24H21EA
OFF
OFF
2
OFF
ON
1.5
ON
OFF
2.5
ON
ON
3
TAM7A0B30H21SD
TAM7A0B30H21EA
OFF
OFF
2
OFF
ON
1.5
ON
OFF
2.5
ON
ON
3
TAM7A0C36H31SD
TAM7A0C36H31EA
OFF
OFF
3
OFF
ON
2
ON
OFF
2.5
ON
ON
3.5
TAM7A0C42H31SD
TAM7A0C42H31EA
OFF
OFF
3.5
OFF
ON
2.5
ON
OFF
3
ON
ON
4
TAM7A0C48H41SD
TAM7A0C48H41EA
OFF
OFF
4
OFF
ON
3
ON
OFF
3.5
ON
ON
4.5**
TAM7B0C60H51SC
TAM7B0C60H51EA
OFF
OFF
4.5**
OFF
ON
3.5
ON
OFF
4
ON
ON
5
N
No
otte
e:: The OD multiplier in conjunction with the CFM/
TON can be used to adjust total airflow for your
application.
Example: 4.5T x 370 CFM/TON = 1665 CFM
** Not an actual OD size
•
Set the S1–3 dip switch for AC or HP.
OD TYPE
S1–3
HP
OFF
AC
ON
1
1
1
2
3
4
5
1
2
3
4
5
H
P
2 (Co mp re s s o r)
2 (S ta g e s )
AC (S ys te m)
}
OUTDOOR
Ca p a c ity (To n s )
OUTDOOR
}
To rq u e
CFM/To n
Co o l Off De la y
}
INDOOR
CFM
+12V
R13
R14
R4
U1
R NET 1
S 1
on
o
n
S
2
R NET 2
R
6
C
2
2
C
1
9
C10
D9
1
Airflo w Co n tro l (AFC)
S 1
•
Set the S1–4 dip switch for the number of stages on
the outdoor unit.
OD STAGES
S1–4
1
OFF
2
ON
N
No
otte
e:: Refer to the field wiring diagram of the Outdoor
Unit to determine if the unit is 1 or 2 stage.
N
No
otte
e:: This dip switch should be changed while the
power is off or no demand is present. The power
must be shut off and then re-applied in order for
the AFC to recognize the change.
•
Set the S1–5 dip switch for the number of
compressors.
# COMPRESSORS
S1–5
1
OFF
2
ON