INTELLISYS OPTION

9

SSR UP5 11, UP5 15, UP5 18, UP5 22

27 POWER L.E.D.

This will illuminate when the 8V controller supply is available.

28 AUTOMATIC RESTART L.E.D.

This will illuminate when the machine has shutdown due to low air

demand. The compressor will restart and load automatically as soon
as the demand for air resumes.

DISPLAY MESSAGES

When the compressor is running normally, the display will indicate

the package discharge pressure and illuminate the corresponding
L.E.D. 

[1]

. An arrow will also appear in the far right of the display

indicating pressure band selection. Pressing 

display select [19]

 will

change the display value and the corresponding L.E.D. will illuminate.
The controller monitors all aspects of the compressor whilst running
and will display warnings or in severe conditions execute an
emergency stop and display alarm conditions.

MACHINE CONTROL MODES

CAPACITY CONTROL

The compressor is designed to work with two types of capacity

control, to suit the individual plant requirements. These controls are:–
A. On line – Off line. (Fitted as standard)
B. On line – Off line, with Upper Range Modulation. (Optional extra)
Either is available by selection at the control panel.

ON LINE – OFF LINE CONTROL

For applications that require a widely varying air demand, this

mode of control will deliver air at full capacity or zero capacity with
low receiver pressure.

This mode of operation is controlled by the pressure transducer

responding to changes in plant air pressure. This sensor energises
the load solenoid valve which in turn operates the venting valve
(blowdown) and the closing of the atmospheric vent opening in the
air inlet valve.

The compressor then delivers full capacity air to the plant

system. If the air pressure in this system rises to the upper set point
of the pressure setting, the load solenoid valve is de–energised
allowing the inlet valve to close. At the same time, the venting valve
opens allowing the receiver pressure to drop.

The pressure setting has a range of 0,83 bar (12 psi) between

its upper and lower set points.The upper set point is set at 0,2 bar
(3 psi) above the compessor rated discharge pressure.

UPPER RANGE MODULATION CONTROL (Optional Extra)

For plants having a relatively high and constant air demand,

Upper Range Modulation is the recommended mode of control.

Upper range modulation retains the features of On line – Off line

control but provides the throttling of the inlet air flow as the line
pressure rises to the upper set point of the 

off–line

 pressure setting.

By bleeding off a small amount from the regulator valve, which

energises the Modulate Solenoid Valve, a reduction in the air signal
to the pneunatic cylinder on the inlet valve allows the cylinder to
‘trim’ the inlet valve position as dictated by changing line pressure.
Modulation begins when the compressor reaches about 94% of the
rated line pressure and is factory set to modulate down to
aproximately 70% of rated capacity.

If the air demand decreases to a level below the 70% modulated

output, the line pressure will increase slightly to the upper limit of the
pressure setting, when the compressor then changes to the Off line
control position and operates with the receiver vented.

AUTOMATIC START/STOP

For plants that have a widely varying plant air demand, larger air

storage capacity, and/or want automatically available standby air
capacity, Automatic Start–Stop Control Option is available.

During periods of low demand, if the line pressure rises to the offline

air pressure set point of the lntellisys

®

, a timer is energized and begins

to time out. The automatic restart time is adjustable in a 2–60 minute
range. The timer will continue to operate as long as the plant line
pressure remains above the online set point of the Intellisys

®

. If the

timer continues to operate for as long as its adjusted time setting, a
contact in the lntellisys opens to de–energize the compressor starter
coils. At the same time, a yellow Automatic Restart light on the
lntellisys

®

 panel is lit and the message AUTO RESTART will be

displayed to indicate the compressor has shut down automatically and
will restart automatically.

The automatic restart will take place when the line pressure drops

to the online set point of the Intellisys

®

.

To operate in the automatic start/stop mode, proceed with the
following steps:

1. Press the SET button until the message AUTO S/S OFF is
displayed.

2. Push the up or down arrows to select the auto start/stop function (on
or off). AUTO S/S OFF in the display indicates auto start/stop is
disabled (off). AUTO S/S ON in the display indicates auto start/stop is
enabled (on). Press the SET button to store function. The display will
flash to acknowledge and then display AUTO S/S 10 MIN.

3. Press the up or down arrows to select the desired automatic restart
time (2–60 min. range). The default value is 10 minutes. Press SET
button to store the value.The display will flash to acknowledge. Press
the DISPLAY SELECT button or wait 30 seconds for the controller to
automatically exit the set routine.The display returns to READY TO
START.

4. Start the compressor and adjust the isolation valve to allow the unit
to slowly reach the offline pressure and unload.The compressor should
run for a minimum of 10 min. and unloaded for the pre–set time and then
shut down.

5. The compressor should restart automatically when the system air
pressure drops below the online air pressure setting.

CONTROLLER WARNING MESSAGES

In the event of a warning, the controller will display a message and

the 

alarm L.E.D. [10]

 will flash. The warning message will alternate with

the normal display every 4 seconds, the compressor will continue to run
but the fault should be rectified as soon as possible. The 

arrow keys

[23]

 should be used to index the display for any additional warning

messages. A warning message may be reset by depressing 

set [21]

once.

NOTE:

The warning will recur if the fault has not been rectified. The

following warning messages may be displayed:

COOLANT FILTER (OPTIONAL)

The pressure differential across the coolant filter exceeds 1 bar (15

psi).

AIR FILTER

The air filter is dirty or blocked and should be replaced.

SEPARATOR ELEMENT

The separator element is dirty or blocked and should be replaced.

AIREND TEMPERATURE

The airend temperature reaches 97% of the high airend

temperature set point (i.e. 106

°

C (223

°

F)).

Goodnal STP ST041 Site Services (Ingersoll Rand Air Compressor UP5 11-22 50H Intellisys Option Options Manual) Vendor Manual

Q-Pulse Id VM413

Active 29/10/2013

Page 11 of 47

Содержание SSR UP5 11

Страница 1: ...50Hz UP5 18 50Hz UP5 22 2230000 SERIAL No SERIAL No SERIAL No SERIAL No OPTIONS MANUAL Intellisys Option Dryer Option High Dust Option Outdoor Module Option C C N 22135925 GB REV C DATE JULY 2003 CP...

Страница 2: ...Goodnal STP ST041 Site Services Ingersoll Rand Air Compressor UP5 11 22 50H Intellisys Option Options Manual Vendor Manual Q Pulse Id VM413 Active 29 10 2013 Page 2 of 47...

Страница 3: ...HA High ambient machine WC Watercooled machine AC Aircooled machine ERS Energy recovery system T E F C Totally enclosed fan cooled motor IP54 O D P Open drip proof motor BR Portuguese Brazil CA French...

Страница 4: ...d parts list may create hazardous conditions over which Ingersoll Rand has no control Therefore Ingersoll Rand does not accept any liability for losses caused by equipment in which non approved repair...

Страница 5: ...d air from this machine Use fork lift truck from this side only RESET Do not use fork lift truck from this side Emergency stop On power Off power Read the Operation and Maintenance manual before opera...

Страница 6: ...RS Use ULTRA Plus Coolant only Failure to use the specified coolant may result in damage to the machine POWER INSPECT Every X months if sooner than required by operating hours CHANGE REPLACE CLEAN POW...

Страница 7: ...the compressor will only relieve presure upstream of the minimum pressure valve on top of the separator tank If maintenance work is required downstream of this valve ensure that all pressure is relie...

Страница 8: ...class ABC fires Attempt repairs only in clean dry well lighted and ventilated areas Connect the compressor only to electrical systems that are compatiblewith its electrical characteristics and that ar...

Страница 9: ...onal If this setting is set to ON the compressor will automatically restart when power is returned to the compressor if it was operating when power was removed POWER OUT RESTART TIME If the power out...

Страница 10: ...nutes the display defaults to the package discharge pressure Depressing this button in the set point routine will cause exit to checking machine for 2 seconds then ready to start 20 LOAD UNLOAD BUTTON...

Страница 11: ...l position and operates with the receiver vented AUTOMATIC START STOP For plants that have a widely varying plant air demand larger air storage capacity and or want automatically available standby air...

Страница 12: ...bar 15 psi during normal operation FIELD OPTION S Before installation and operation of this option these instructions should be studied carefully to obtain a clear knowledge of the option and its appl...

Страница 13: ...2 ELECTRICAL SCHEMATIC STAR DELTA WITH INTELLISYS CONTROL INTELLISYS STAR DELTA Goodnal STP ST041 Site Services Ingersoll Rand Air Compressor UP5 11 22 50H Intellisys Option Options Manual Vendor Manu...

Страница 14: ...d fused disconnect or circuit breaker per code requirementsmust be provided by customer 2 Dashed lines represent wiring by customer 3 Sizing of electrical components not supplied by Ingersoll Rand is...

Страница 15: ...5 22 PIPING AND INSTRUMENTATION WITH INTELLISYS CONTROL 85584282 Revision C Goodnal STP ST041 Site Services Ingersoll Rand Air Compressor UP5 11 22 50H Intellisys Option Options Manual Vendor Manual Q...

Страница 16: ...Motor 17 Valve safety 18 Valve drain 19 Screen scavenge 20 Valve solenoid blowdown 21 Orifice 22 Indicator air restriction 32 Valve solenoid line sump Intellisys Option 33 Transducer pressure Intelli...

Страница 17: ...ination block 6 Elbow 7 Tee male run 8 Reducer bushing 9 Valve solenoid blowdown 10 Valve solenoid load 11 Indicator air filter 12 Nipple 13 Adaptor 14 Intake valve assembly NOTES A Tubing 3 8 inch B...

Страница 18: ...84340 4 Latch 18 92829308 1 Key 19 96703756 2 Nut 20 22128763 1 Controller INTELLISYS 21 22091193 2 Hinge 22 96743992 4 Screw 23 39495874 1 Gasket 24 96742754 2 Screw 25 22055909 1 Tee 26 22177190 1 C...

Страница 19: ...250998 1 Contactor 11 39251004 2 Contactor 12 22071831 2 Fuse 1 6A 500V 13 22071815 1 Fuse 2A 500V 14 22052229 1 Interlock 15 22137293 1 Panel 16 39191648 1 Plug 11 position 17 39191655 1 Plug 16 posi...

Страница 20: ...tactor 10 22071831 2 Fuse 1 6A 500V 11 22071815 3 Fuse 2A 500V 12 22052229 1 Interlock 13 22137293 1 Panel 14 39191648 1 Plug 11 position 15 39191655 1 Plug 16 position 16 39186101 1 Plug 4 position 1...

Страница 21: ...51061 1 Contactor 11 39250998 2 Contactor 12 22071831 2 Fuse 1 6A 500V 13 22071815 1 Fuse 2A 500V 14 22052229 1 Interlock 15 22137293 1 Panel 16 39191648 1 Plug 11 position 17 39191655 1 Plug 16 posit...

Страница 22: ...lliary 10 39252036 1 Contactor 11 39251061 2 Contactor 12 22071831 2 Fuse 1 6A 500V 13 22071815 3 Fuse 2A 500V 14 22052229 1 Interlock 15 22137293 1 Panel 16 39191648 1 Plug 11 position 17 39191655 1...

Страница 23: ...ngs Examine all motors for grease fittings Not all motors have bearings that require grease MOTORS WITH GREASE FITTINGS If grease fittings are present remove the drain plug and add grease until it beg...

Страница 24: ...ATE OCTOBER 2008 50Hz UP5 11 UP5 15 UP5 18 UP5 22 Goodnal STP ST041 Site Services Ingersoll Rand Air Compressor UP5 11 22 50H Intellisys Option Options Manual Vendor Manual Q Pulse Id VM413 Active 29...

Страница 25: ...Goodnal STP ST041 Site Services Ingersoll Rand Air Compressor UP5 11 22 50H Intellisys Option Options Manual Vendor Manual Q Pulse Id VM413 Active 29 10 2013 Page 25 of 47...

Страница 26: ...rsoll Rand Company subsidiaries and authorised distributors located in the principle cities throughout the world Description The illustrated parts breakdown identifies the various assemblies sub assem...

Страница 27: ...rner 12 22067052 1 Panel assembly left 13 22092886 1 Channel 14 54747761 1 Channel 15 22099626 1 Guard sheave assembly 16 54747753 1 Corner 17 22053433 25 Plug 18 54754163 1 Base 19 39738490 7 Pin loc...

Страница 28: ...UP5 11kW UP5 15kW 22077267 1 Bush UP5 18 5kW UP5 22kW 4 96703186 1 Screw 5 92751130 1 Plate retaining 6 22107643 1 Pulley UP5 11kW 7 5bar 22107577 1 Pulley UP5 11kW 8 5bar 22107650 1 Pulley UP5 11kW 1...

Страница 29: ...54735972 1 Motor 22kW 18 5kW HA 400V IP55 50Hz Star Delta 54735980 1 Motor 22kW 18 5kW HA 550V IP55 50Hz Star Delta 8 88101209 1 Key 9 54727888 1 Support 180 Frame motors 54727870 1 Support 160 Frame...

Страница 30: ...1 Kit unloader valve 14 92368687 2 Screw 15 22097208 1 Indicator air restriction 16 89265300 1 Filter assembly 17 89295935 1 Hose 18 95340683 2 Clamp 19 22065890 1 Guard 20 22062376 1 Adaptor 21 9595...

Страница 31: ...assembly 11 15kW 11kW HA 4 99295362 1 Blower 18 5 22kW 15 18 5kW HA 99295354 1 Blower 11 15kW 11kW HA 5 22099857 1 Shroud assembly 85584365 1 Foam 6 54754296 1 Cover 7 22099840 1 Cover assembly 8 923...

Страница 32: ...5560597 2 Hose assembly 4 95928230 1 Plug 5 95952867 2 Connector 6 96952122 1 Adaptor 7 95938163 2 Elbow 8 96952379 1 Adaptor 9 96737564 4 Nut 10 96704531 4 Screw 11 95928230 1 Plug http air ingersoll...

Страница 33: ...393 1 Connector 14 22505309 1 Switch pressure 15 96737564 AR Nut 16 96743182 AR Screw 17 39155346 1 Tee 18 22224976 1 Adaptor 19 96703756 AR Nut 20 96738828 2 Screw 21 54472485 2 Elbow 22 95952388 1 C...

Страница 34: ...81874 1 Tube assembly 10 54749221 1 Nipple 11 54672654 1 Filter coolant 12 54749247 1 Cartridge separator 13 95928214 1 Plug For Non Intellisys 14 89209217 2 Elbow 15 54740444 1 Sight glass 16 2205129...

Страница 35: ...7 2 Clip retaining 8 22095913 1 Gland cable 9 92368687 2 Screw 10 32341760 1 Bracket 11 95937520 1 Elbow 12 96728225 1 Adaptor 13 22062301 1 Reducer 14 22062327 1 Adaptor 15 92354513 1 Elbow 16 391563...

Страница 36: ...p 7 32342149 1 Switch Off On 8 32342172 1 Pushbutton reset 9 32342131 1 Hourmeter 9a 39237086 1 Gasket 9b 39127245 2 Screw 9c 22462360 1 Varistor 10 92877018 3 Gland cable 11 39140785 1 Plug 22503411...

Страница 37: ...23 8 22071864 1 Earth bridge 9 22071831 2 Fuse 1 6A 500V 10 22071815 1 Fuse 2A 500V 11 22052229 1 Interlock 12 22076350 1 Panel 13 22056741 1 Rail 14 22072631 1 Rail 15 22072649 1 Rail 16 22294037 1 R...

Страница 38: ...tactor C23 9 22071864 1 Earth bridge 10 22317515 2 Fuse 1 6A 600V 11 22071815 1 Fuse 2A 500V 12 22052229 1 Interlock 13 22076350 1 Panel 14 22056741 1 Rail 15 22072631 1 Rail 16 22072649 1 Rail 17 222...

Страница 39: ...r C37 8 39252036 1 Contactor C23 9 22071864 1 Earth bridge 10 22071831 2 Fuse 1 6A 500V 11 22071815 1 Fuse 2A 500V 12 22052229 1 Interlock 13 22076350 1 Panel 14 22056741 1 Rail 15 22072631 1 Rail 16...

Страница 40: ...ge 10 22071831 2 Fuse 1 6A 500V 11 22071815 1 Fuse 2A 500V 12 22052229 1 Interlock 13 22076350 1 Panel 14 22056741 1 Rail 15 22072631 1 Rail 16 22072649 1 Rail 17 22294037 1 Relay time delay 18 392555...

Страница 41: ...1 Fuse 2A 500V 12 22052229 1 Interlock 13 22076350 1 Panel 14 22056741 1 Rail 15 22072631 1 Rail 16 22072649 1 Rail 17 22294037 1 Relay time delay 18 39255559 1 Relay fault high air temp 19 23053770...

Страница 42: ...actor 19002393 Contactor 19001338 Trunking slotted cable 19011600 Relay control 19001726 Block fuse base 19002013 Fuse 2A 19002021 Block terminal 19001999 Stop Din rail 19001981 Aux Contactor No Shown...

Страница 43: ...1 Block fuse base 19002013 1 Fuse 2A 19002021 1 Rail 22056741 3 Relay control 19001726 1 Timer of delay 19001734 1 Timer 6MIN 19001742 1 Overload 19001585 1 Transformer 19002138 1 Trunking slotted ca...

Страница 44: ...41 Manual Parts catalogue 50Hz 80445182 Manual Options 50Hz http air ingersollrand com UP5 11 UP5 15 UP5 18 UP5 22 Goodnal STP ST041 Site Services Ingersoll Rand Air Compressor UP5 11 22 50H Intellisy...

Страница 45: ...654652 Valve solenoid Blowdown 54749114 Spring gas Belts 50Hz 22108393 Belt drive 11kW 7 5 8 5 bar 18 5kW 14 bar 22108401 Belt drive 11kW 10 bar 22108419 Belt drive 11kW 14 bar 89265060 Belt drive 15k...

Страница 46: ...426580 Valve pressure 10 5 bar 50Hz 750L Tank 22057954 Valve safety 15 bar 50Hz Manifold 32342149 Switch Off On 32342172 Pushbutton re set 22053904 Button emergency stop 32342156 Indicator Green 32342...

Страница 47: ...overload 39251319 2 Coil C23 C37 C43 C37 Star Delta 220V 18 5kW 15kW HA 39250998 2 Contactors C43 39251061 1 Contactor C37 23051079 1 Relay overload 39251319 1 Coil C37 39251327 1 Coil C43 C60 C43 St...

Отзывы: