D-1400-4 Page 8 of 16
4.15.
CONNECT DELAYED EGRESS MODULE (DXM) IN POWER SUPPLY (DEX).
DELAYED EGRESS (DX) DEVICE
4.16.
CONNECT INTERFACE BOARD CABLE WIRES FROM DEVICE TO DELAYED EGRESS MODULE.
{
INTERF
ACE BOARD CABLE FROM DEVICE
DOES NOT
INCLUDE
THESE 3 WIRES
GREEN
RESET SWITCH (N.O.)
1
BLUE
AUTHORIZED EGRESS SWITCH
2
BROWN
TRIGGER SWITCH (N.O.)
3
RED
MAGNET (+24 VDC)
4
BLACK
COMMON (–)
5
YELLOW
GREEN LED (–)
6
ORANGE
RED LED/AUDIBLE (–)
7
N/A
DRY ALARM CONTACT (COM)
8
N/A
DRY ALARM CONTACT (N.O.)
9
N/A
DRY ALARM CONTACT (N.C.)
10
WHITE
LEDS/AUDIBLE (+24 VDC)
11
WIRE COLOR
TERMINAL
FUNCTION
1 2 3 4
5 6 7 8
9 1011
DELAYED EGRESS MODULE (DXM)
BLACK (22 A.W.G.)
RED (22 A.W.G.)
FIRE ALARM JUMPER
24 V JUMPER IN PLACE
RED (18 A.W.G.)
BLACK (HOT)
WHITE (NEUTRAL)
800 mA FUSE
BLACK (22 A.W.G.)
RED (22 A.W.G.)
BLACK (18 A.W.G.)
2.0 A FUSE
INPUT: 115 VAC, 800 mA
GREEN (GROUND)
2.0 A FUSE
DELAYED EGRESS
MODULE (DXM)
INSTALLS IN
EITHER SLOT
DXM