background image

6  

Service Facts

M952-SF-4

PERIODIC SERVICING REQUIREMENTS

WARNING

!

ELECTRIC SHOCK HAZARD

DISCONNECT POWER TO THE UNIT BEFORE REMOVING 

THE BLOWER DOOR.  ALLOW A MINIMUM OF 15 

SECONDS FOR IFC POWER SUPPLY TO DISCHARGE TO 

0 VOLTS.  FAILURE TO FOLLOW THIS WARNING COULD 

RESULT IN PERSONAL INJURY FROM MOVING PARTS.

WARNING

!

CARBON MONOXIDE POISONING HAZARD

FAILURE TO FOLLOW THE SERVICE AND/OR PERIODIC 

MAINTENANCE INSTRUCTIONS FOR THE FURNACE 

AND VENTING SYSTEM, COULD RESULT IN CARBON 

MONOXIDE POISONING OR DEATH.

WARNING

!

FIRE OR EXPLOSION HAZARD

FAILURE TO FOLLOW THE SAFETY WARNINGS EXACTLY 

COULD RESULT IN SERIOUS INJURY, DEATH OR 

PROPERTY DAMAGE.

NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME.  

USE A COMMERCIALLY AVAILABLE SOAP SOLUTION 

MADE SPECIFICALLY FOR THE DETECTION OF LEAKS 

TO CHECK ALL CONNECTIONS.  A FIRE OR EXPLOSION 

MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL 

INJURY, OR LOSS OF LIFE.

CAUTION

!

Label all wires prior to disconnection when servicing 

controls.  Wiring errors can cause improper and 

dangerous operation. Verify proper operation after 

servicing.

1.    GENERAL INSPECTION – 

Examine the furnace 

installation annually for the following items:

 

a.  All flue product carrying areas external to the furnace 

(i.e. chimney, vent connector) are clear and free of 

obstruction.  A vent screen in the end of the vent (flue) 

pipe must be inspected for blockage annually.

 

b.  The vent connector is in place, slopes upward and is 

physically sound without holes or excessive corrosion.

 

c.  The return air duct connection(s) is physically sound, is 

sealed to the furnace and terminates outside the space 

containing the furnace.

 

d.  The physical support of the furnace should be sound 

without sagging, cracks, gaps, etc., around the base so 

as to provide a seal between the support and the base.

 

e.  There are no obvious signs of deterioration of the 

furnace.

2.   FILTERS – Filters should be cleaned or replaced (with 

high velocity filters only), monthly and more frequently 

during high use times of the year such as midsummer or 

midwinter.

3.    BLOWERS – The blower size and speed determine 

the air volume delivered by the furnace. The blower 

motor bearings are factory lubricated and under normal 

operating conditions do not require servicing.  If motor 

lubrication is required it should only be done by a qualified 

servicer.  Annual cleaning of the blower wheel and 

housing is recommended for maximum air output, and this 

must be performed only by a qualified servicer or service 

agency.

CAUTION

!

Do NOT touch igniter. It is extremely hot. 

4.    IGNITER – This unit has a hot surface direct ignition 

device that automatically lights the burners. Please note 

that it is very fragile and should be handled with care.

5.    BURNER – Gas burners do not normally require 

scheduled servicing, however, accumulation of foreign 

material may cause a yellowing flame or delayed ignition. 

Either condition indicates  that a service call is required. 

For best operation, burners must be cleaned annually 

using brushes and vacuum cleaner.

    Turn off gas and electric power supply. To clean burners, 

remove burner box cover (6 to 8 screws) and top burner 

bracket.  Lift burners from orifices.

NOTE: Be careful not to break igniter when removing 

burners.

    Clean burners with brush and/or vacuum cleaner. 

Reassemble parts by reversal of the above procedure.  

The burner box must be resealed when replacing box 

cover.

NOTE: On LP (propane) units, some light yellow 

tipping of the outer mantle is normal. Inner mantle 

should be bright blue. 

Natural gas units should not have any yellow tipped 

flames.  This condition indicates that a service call 

is required.  For best operation, burners must be 

cleaned annually using brushes and vacuum cleaner.
NOTE: On LP (propane) units, due to variations in 

BTU content and altitude, servicing may be required 

at shorter intervals.

6.    HEAT EXCHANGER/FLUE PIPE – These items must be 

inspected for signs of corrosion, and/or deterioration at 

the beginning of each heating season by a qualified  service 

technician and cleaned annually for best  operation.  To 

clean flue gas passages, follow recommendations below:

 

a.  Turn off gas and electric power supply.

 

b.  Inspect flue pipe exterior for cracks, leaks, holes or 

leaky joints.  Some discoloration of PVC pipe is normal.

 

c.  Remove burner compartment door from furnace.

 

d.  Inspect around insulation covering flue collector 

box. Inspect induced draft blower connections from 

recuperative cell and to the flue pipe connection.  

 

e.  Remove burners. (See Item 5.)

 

f.  Use a mirror and flashlight to inspect interior of heat 

exchanger, be careful not to damage the igniter, flame 

sensor or other components.

 

g.  If any corrosion is present the heat exchanger should 

be cleaned by a qualified service technician.

 

h.  After inspection is complete replace burner box cover, 

burners, and furnace door.

 

i.  Restore gas supply. Check for leaks using a soap 

solution.  Restore electrical supply. Check unit for 

normal operation. 

 

7.  COOLING COIL CONDENSATE DRAIN – If a cooling 

coil is installed with the furnace, condensate drains 

should be checked and cleaned periodically to assure 

that condensate can drain freely from coil to drain. If 

condensate cannot drain freely water damage can 

occur.  (See Condensate Drain in Installer’s Guide)

Содержание M952V060BD36AB

Страница 1: ...CT 10 x 8 1 Variable See Fan Performance Table 1 2 Variable 115 1 60 7 7 Centrifugal Direct Variable 1 50 5000 33 110 3 60 180 1 0 Yes High Velocity 1 17x25 1 in 2 Round Aluminized Steel Type I 20 3 4...

Страница 2: ...pe I 20 6 45 6 56 Redundant Two Stage Hot Surface Igniter Multiport Inshot 6 115 1 60 17 2 20 1 2 H x W x D 41 3 4 x 26 1 2 x 30 1 2 206 196 M952V060BD36AB 6 Downflow Horizontal 39 000 38 000 60 000 5...

Страница 3: ...ons of use WARNING SAFETY SECTION WARNING ELECTRIC SHOCK HAZARD THE CABINET MUST HAVE AN UNINTERRUPTED OR UNBROKEN GROUND ACCORDING TO NATIONAL ELEC TRICAL CODE ANSI NFPA 70 LATEST EDITION AND CANADIA...

Страница 4: ...sh eyes with water to remove dust If symptoms persist seek medical attention Skin Contact Wash affected areas gently with soap and warm water after handling SEQUENCE OF OPERATION COMFORT CONTROL CALL...

Страница 5: ...otor is reduced to low speed 1st stage satisfied W1 Comfort Control contacts open signaling that 1st Stage heating requirements are satisfied The Gas Valve will close and the induced draft blower will...

Страница 6: ...remely hot 4 IGNITER This unit has a hot surface direct ignition device that automatically lights the burners Please note that it is very fragile and should be handled with care 5 BURNER Gas burners d...

Страница 7: ...7 Service Facts M952 SF 4 M952 WIRING DIAGRAM From drawing D345191P01...

Страница 8: ...8 Service Facts M952 SF 4 M952 SCHEMATIC DIAGRAM2 From drawing D345191P01...

Страница 9: ...9 Service Facts M952 SF 4 M952 WIRING DIAGRAM From drawing D345192...

Страница 10: ...10 Service Facts M952 SF 4 M952 SCHEMATIC DIAGRAM From drawing D345192...

Страница 11: ...otor Will Not Run ECM 2 TM QUICK CHECK Blower Motor Will Not Run 1 Jumper 24 Volt A C R Terminal to G terminal on the Low Voltage T erminal board Does motor run NO Go to step 2 YES Motor runs check Co...

Страница 12: ...to motor low voltage plug pins 12 and 15 and pins 1 and 3 which are common Does motor run NO Go to step 4 YES Fault is in the 16 wire low voltage harness Repair or replace it 4 Is the line voltage to...

Страница 13: ...D on the board should be on 6 If the troubleshooter R L E D is not on check for 24 volts A C at the motor control board 7 If 24 volts A C is not present troubleshoot and repair as needed 8 If 24 volt...

Страница 14: ...s bad repair or replace Low Voltage Comfort Control Operation 14 Verify thermostat signals by jumping R to each of the low voltage terminal connections as follows BK O YLO G W1 W2 W3 See exceptions be...

Страница 15: ...30 HIGH 450 CFM TON OFF OFF ON OFF CFM WATTS 1325 360 1325 425 1300 460 1175 425 1000 365 1 At continuous fan setting Heating or Cooling airflows are approximately 50 of selected cooling value 2 LOW a...

Страница 16: ...LOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW 1 SW 2 SW 3 SW 4 0 1 0 3 0 5 0 7 0 9 2 0 LOW 350 CFM TON ON ON OFF ON CFM WATTS 750 84 750 122 750 154 720 185 710 221 NORMAL 400 CFM TON ON...

Страница 17: ...7 650 1449 595 HIGH 450 CFM TON OFF OFF ON OFF CFM WATTS 1847 630 1863 735 1816 780 1687 720 1532 665 1 At Continuous fan setting Heating or Cooling airflows are approximately 50 of selected cooling v...

Страница 18: ...eating or Cooling airflows are approximately 50 of selected cooling value 2 LOW airflow 350 cfm ton is COMFORT HUMID CLIMATE setting NORMAL airflow 400 cfm ton is typical setting HIGH airflow 450 cfm...

Страница 19: ...RFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW 1 SW 2 SW 3 SW 4 0 1 0 3 0 5 0 7 0 9 1 5 LOW 350 CFM TON OFF OFF OFF ON CFM WATTS 525 45 525 70 525 100 525 135 525 160 NORMAL 400 CFM TON...

Страница 20: ...1350 455 1350 480 1210 435 1070 390 900 345 1 At continuous fan setting Heating or Cooling airflows are approximately 50 of selected cooling value 2 LOW airflow 350 cfm ton is COMFORT HUMID CLIMATE se...

Страница 21: ...TONS AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW 1 SW 2 SW 3 SW 4 0 1 0 3 0 5 0 7 0 9 2 5 LOW 350 CFM TON ON ON OFF ON CFM WATTS 870 100 885 140 887 185 881 230 876 270 NORMAL 400...

Страница 22: ...M952V120DD60AB FURNACE COOLING AIRFLOW CFM AND POWER WATTS VS EXTERNAL STATIC PRESSURE WITH FILTER OUTDOOR UNIT SIZE TONS AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW 1 SW 2 SW 3 SW...

Страница 23: ...l 3 times within 6 seconds The control will acknowledge the reset by turning on the red LED for 2 seconds FAULT CODE RECOVERY On power up last 4 faults if any will be flashed on the red LED The newest...

Страница 24: ...en applying an airflow command signal to the BK input such as with the variable speed single zone and multi zone system controller On single speed cooling only non heat pump systems jumper Y to O for...

Страница 25: ...l Gas Valve Circuit Fault 37 8 Flash Troubleshooting Low Flame Sense Fault 38 9 Flash Troubleshooting Open Inducer Limit 39 VS No Air Flow Incorrect Air Flow The following pages include troubleshootin...

Страница 26: ...FMR N CNT05160 Line Voltage Connections 24 Volt Furnace Component Connections 5 Amp Control Fuse Low Voltage Terminal Strip 16 pin ECM Connector Indoor airflow configuration dip switches Fault LED Red...

Страница 27: ...R OR PRESSURE SWITCH ERROR 4 Flashes OPEN LIMIT OR ROLLOUT SWITCH 5 Flashes FLAME SENSED WHEN NO FLAME SHOULD BE PRESENT 6 Flashes LINE REVERSE POLARITY 7 Flashes GAS VALVE CIRCUIT ERROR 8 Flashes WEA...

Страница 28: ...present from transformer and fuse good YES NO Repair low voltage wiring replace transformer or fuse as needed Repair high voltage connection to unit What is the fault light flash code See FAULT LED F...

Страница 29: ...eck operation NO Flame sensor is good NO Is minimum outlet gas manifold pressure maintained Does inlet gas pressure drop more than 2 WC NO Correct inlet gas pressure Check operation Replace Gas Valve...

Страница 30: ...30 Service Facts M952 SF 4 Correct positioning of ignitor sensor NOTE the slight over lap of the ignitor and the burner Igniter slightly overlapping OD of burner...

Страница 31: ...ion YES While the furnace is operating on 1st stage heat make a call for 2nd stage heat Allow 30 seconds for the furnace to transition to 2nd stage Is 24 volts present measured across PS2 yellow 7 to...

Страница 32: ...rrect gas pressure Check operation NO Is temperature at high limit above the switch setting YES Replace high limit switch NO YES Is temperature at reverse flow switch above specifications Replace reve...

Страница 33: ...Is flue piping restricted Correct as needed Check operation YES Are flames from burners impinging on sides of heat exchanger NO YES When fan comes on do flames stay consistent Replace heat exchanger...

Страница 34: ...ing per installation instructions Using a back up wrench install new gas valve Check operation Inspect gas supply for leaks and have gas supplier check gas quality Are there signs of moisture or debri...

Страница 35: ...952 SF 4 DEFINITION Polarity Fault Incoming high voltage wiring is reversed Disconnect incoming electrical power to furnace Reverse 120 vac power leads to furnace wiring Reconnect power Check operatio...

Страница 36: ...rcuit Error 24 volts is present when it should not be present Is 24 VAC nominal voltage present between Red lead at gas valve connection to chassis ground Turn Comfort Control to OFF position Correct...

Страница 37: ...37 Service Facts M952 SF 4...

Страница 38: ...en Replace Inducer Limit switch Check operation YES NO Definition This error is normally caused by improper installation or application of the furnace venting system Disconnect electrical power from t...

Страница 39: ...r run YES Replace Wire harness NO Is 24 VAC measured between R transformer hot and B C transformer common at the low voltage field connections NO Replace transformer NO Repair wiring between incoming...

Страница 40: ...licy of continuous product and product data improvement and reserves the right to change design and specifications without notice Ingersoll Rand 6200 Troup Highway Tyler TX 75707 For more information...

Отзывы: