15
Service Facts
M952-SF-4
M952V060BU36AB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOOR
UNIT SIZE
(TONS)
AIRFLOW
SETTING
DIP SWITCH SETTING
EXTERNAL STATIC PRESSURE
SW 1
SW 2
SW 3
SW 4
0.1
0.3
0.5
0.7
0.9
1.5
LOW
(350 CFM/TON)
ON
ON
OFF
ON
CFM
WATTS
575
65
575
90
575
125
550
155
-
NORMAL
(400 CFM/TON)
ON
ON
OFF
OFF
CFM
WATTS
640
70
640
110
640
140
630
175
-
HIGH
(450 CFM/TON)
ON
ON
ON
OFF
CFM
WATTS
700
85
700
125
700
160
700
200
-
2.0
LOW
(350 CFM/TON)
OFF
ON
OFF
ON
CFM
WATTS
700
100
700
130
700
170
700
210
-
NORMAL
(400 CFM/TON)
OFF
ON
OFF
OFF
CFM
WATTS
800
115
800
155
800
200
800
250
-
HIGH
(450 CFM/TON)
OFF
ON
ON
OFF
CFM
WATTS
900
140
900
195
900
240
900
290
-
2.5
LOW
(350 CFM/TON)
ON
OFF
OFF
ON
CFM
WATTS
875
130
875
180
875
230
875
270
-
NORMAL
(400 CFM/TON)
ON
OFF
OFF
OFF
CFM
WATTS
1000
175
1000
235
1000
285
1000
335
900
310
HIGH
(450 CFM/TON)
ON
OFF
ON
OFF
CFM
WATTS
1125
235
1125
295
1125
345
1100
370
925
318
3
LOW
(350 CFM/TON)
OFF
OFF
OFF
ON
CFM
WATTS
1050
195
1050
260
1050
305
1050
350
920
315
NORMAL
(400 CFM/TON)
OFF
OFF
OFF
OFF
CFM
WATTS
1200
275
1200
330
1200
385
1100
385
940
330
HIGH
(450 CFM/TON)
OFF
OFF
ON
OFF
CFM
WATTS
1325
360
1325
425
1300
460
1175
425
1000
365
1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.
2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting;
NORMAL airflow (400 cfm/ton) is typical setting;
HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.
M952V060BU36AB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
1st Stage Capacity =
2nd Stage Capacity =
38,000
58,000
AIRFLOW
SETTING
DIP SWITCH SETTING
EXTERNAL STATIC PRESSURE
SW 7
SW 8
0.1
0.3
0.5
0.7
0.9
HEATING
1ST
STAGE
LOW
ON
ON
CFM
TEMP. RISE
WATTS
600
57
85
600
57
110
600
57
155
600
57
190
-
MEDIUM LOW
OFF
ON
CFM
TEMP. RISE
WATTS
700
49
90
700
49
130
700
49
175
700
49
210
-
NORMAL **
ON
OFF
CFM
TEMP. RISE
WATTS
775
44
105
775
44
155
775
44
195
775
44
240
-
HIGH
OFF
OFF
CFM
TEMP. RISE
WATTS
870
39
135
870
39
185
870
39
235
870
39
290
-
HEATING
2ND
STAGE
LOW
ON
ON
CFM
TEMP. RISE
WATTS
860
61
140
920
57
200
920
57
245
920
57
300
670
79
245
MEDIUM LOW
OFF
ON
CFM
TEMP. RISE
WATTS
1000
53
190
1000
53
255
1000
53
305
1000
53
340
700
75
255
NORMAL **
ON
OFF
CFM
TEMP. RISE
WATTS
1125
47
250
1125
47
315
1125
47
370
1025
51
355
775
68
285
HIGH
OFF
OFF
CFM
TEMP. RISE
WATTS
1250
42
340
1250
42
405
1250
42
445
1100
48
390
1000
53
355
** Factory setting
Содержание M952V060BD36AB
Страница 7: ...7 Service Facts M952 SF 4 M952 WIRING DIAGRAM From drawing D345191P01...
Страница 8: ...8 Service Facts M952 SF 4 M952 SCHEMATIC DIAGRAM2 From drawing D345191P01...
Страница 9: ...9 Service Facts M952 SF 4 M952 WIRING DIAGRAM From drawing D345192...
Страница 10: ...10 Service Facts M952 SF 4 M952 SCHEMATIC DIAGRAM From drawing D345192...
Страница 37: ...37 Service Facts M952 SF 4...