Installation

ACC-SVN136E-EN

7

1.

Remove cap nut from the unit's high pressure service
port on the discharge line that runs from the
compressor, see

Figure 4, p. 7

.

2. Install the transducer onto the Tee port without the

valve core, see

Figure 5, p. 7

.

3. Place theTee flare nut with valve core depressor on the

unit high pressure tap, where the cap nut was located.

Note:

If the high pressure service port is on anotherTee,
refer to

Figure 6, p. 7

for connection.

4. Tighten flare nut securely to the high pressure service

port and check for leaks.

Motor

1.

Remove the fan guard.

2. Measure the position of the fan blade on the current

motor.The fan blade will need to be reinstalled at the
same height on the new motor.

3. Remove the fan blade.

4. Remove and appropriately discard the existing fan

motor.

5. Install the new fan motor.

6. Install slinger, making sure it does not press against the

shaft end bearing.

Note:

Use slinger clamp if applicable.

7.

Reinstall the fan so the fan hub is flush with the end of
the motor shaft and torque the fan hub bolt to 165-175
in-lb.

8. Wire motor following unit wiring diagram (see

Figure 14, p. 11

-

Figure 15, p. 12

)

9. Reinstall the fan guard and ensure there is one inch

between the fan guard and fan prop.

Wiring

ReliaTel™ Evaporator Defrost Control
Function Disable (EDC)

1.

Disable ReliaTel on-board low ambient function.

2. Connect wire 68Z (BL) (supplied in kit) into the J1-7 pin

on jack 1 on the RTRM,

Figure 7, p. 8

below.

Note:

Pay close attention to the orientation of the wire
terminal on wire 68Z when inserting it into J1-7
position on the existing wire harness. Verify the
wire snaps into place.

3. Route wire 68Z (BL) to the low voltage terminal board

(LTB1).

4. Connect wire 68Z (BL) to low voltage terminal board

(LTB1) terminal “B”.

5. Using wire ties (provided), bundle and dress this wire

away from sharp edges.

Figure 4.

High pressure service port

Figure 5.

Transducer to tee

Figure 6.

Tee and transducer installed on high
pressure service port

High Pressure 

Service Port

NOTICE:

Equipment Damage!

Do not bend fan blades when removing and installing
fan motor assembly. Bent blades could cause excessive
load on the motor bearings.

NOTICE:

Equipment Damage!

Must route all wires away from hot tubes and/or sharp
edges.

Содержание BAYLOAM335

Страница 1: ...tion Instructions Model Numbers Used With BAYLOAM335 TTA073D3 TTA090D3 TTA073G3 TTA090G3 TTA180J3 TWA073D3 E3 TWA090D3 E3 BAYLOAM336 TTA120D3 E3 F3 TTA120G3 H3 J3 TTA150E3 H3 TTA180E3 F3 H3 TTA240E3 F...

Страница 2: ...cates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could re...

Страница 3: ...tten permission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All tra...

Страница 4: ...4 ACC SVN136E EN Table of Contents Copyright 3 Installation 5 General 5 Controller 6 Transducer and Tee 6 Motor 7 Wiring 7 Operation Troubleshooting 13 Checkout Procedure 13...

Страница 5: ...0EW FW TWA073D3 E3 TTA180H3 TTA076GD TTA126HD TTA180HW JW TWA090D3 E3 TTA240E3 F3 TTA090D4 TTA150E4 TTA240EW FW TTA240H3 F3 TTA090G4 TTA150H4 TTA240HW JW TTA300F3 TTA180J4 TTA156ED FD TTA300FW TTA300J...

Страница 6: ...ath or serious injury WARNING Ground Wire All field installed wiring must be completed by qualified personnel All field installed wiring must comply with NEC and applicable local codes Failure to foll...

Страница 7: ...orque the fan hub bolt to 165 175 in lb 8 Wire motor following unit wiring diagram see Figure 14 p 11 Figure 15 p 12 9 Reinstall the fan guard and ensure there is one inch between the fan guard and fa...

Страница 8: ...th one controller in which case the controller will respond to the transducer that senses the highest pressure see Figure 8 p 8 below for wiring Cut wire ties if necessary to properly route wires 3 Fi...

Страница 9: ...yellow light will turn off and the green light will remain off Setting the Pressure Setpoint When using pressure transducers the control will maintain condenser pressure between 20psig above and 20psi...

Страница 10: ...ll bearing motor set the hard start dial to the MIN position Begin at the recommended setting the hard start time can be fine tuned within the recommended motor range Use the minimum possible hard sta...

Страница 11: ...Installation ACC SVN136E EN 11 Figure 14 Wiring diagram TWA heat pump with ReliaTel...

Страница 12: ...Installation 12 ACC SVN136E EN Figure 15 Wiring diagram TTA cooling with ReliaTel ElectroMechanical...

Страница 13: ...procedures When possible disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing Follow proper lockout tagout procedure...

Страница 14: ...s removed Check that the 24VAC signal and the transducer are wired up correctly into the controller Erratic fan operation Control is not wired correctly See wiring diagrams Pressure transducer problem...

Страница 15: ...Operation Troubleshooting ACC SVN136E EN 15...

Страница 16: ...ced controls and HVAC systems comprehensive building services and parts For more information visit www IRCO com The manufacturer has a policy of continuous product and product data improvement and res...

Отзывы: