Ingersoll-Rand BAYLOAM335 Скачать руководство пользователя страница 14

Operation & Troubleshooting

14

ACC-SVN136E-EN

Table 4.

Troubleshooting guide

Problem

Possible Cause

Possible Solution

No fan operation

No 24 volt control voltage

Check for 24 VAC at control and verify correct wiring. 

If wired correctly, check voltage across the 
transformer.

No line voltage 

Check voltage across the FTB pins D and C. If no line 

voltage is present, verify all wiring is correct.

Bad fan motor or controller

Disconnect power. Place the jumper removed during 
installation back onto FTB-1/FTB-2 across terminals 

(C) and (D). Restore power to the unit and check for 
fan operation. If fan does not start, motor is bad and 

should be replaced. If motor does start, check 
controller settings. If motor still fails to start, replace 

controller.

Improper fan operation

Heat pump jumper not configured correctly

Refer to the IOM or correct hook-up diagram and verify 
the heat pump jumper is configured correctly.

Control is not wired correctly

See wiring diagrams. Ensure that the 24 VAC power 

supply is connected in-phase with the motor power 
supply.

No fan modulation

No need to modulate the fan

If pressure is equal to or greater than the head 

pressure control setpoint, the fan will be operating at 
full speed.

No input pressure to control

Check for proper transducer and Tee installation. 

Schrader valve depressor must depress Schrader valve 
enough to allow refrigerant into pressure transducer.

Heat pump inputs wired incorrectly into the controller

Check hook-up diagram and verify heat pump inputs 
are properly wired into the controller.

Miswired

Verify jumper on FTB is removed

Check that the 24VAC signal and the transducer are 
wired up correctly into the controller.

Erratic fan operation

Control is not wired correctly

See wiring diagrams. 

Pressure transducer problem

Check for proper transducer and Tee installation. 
Schrader valve depressor must depress Schrader valve 
enough to allow refrigerant into pressure transducer.

Dirty or blocked condenser coil

Clean condenser coil.

Fan motor is cycling on thermal 
overload

Dirty or blocked condenser coil

Clean condenser coil.

Wrong motor for fan speed control application

Verify new motor was installed. Replace with motor 
approved for fan speed control application.

Unit fails to start

Incorrect/No voltage present

Using an AC voltmeter, measure the voltage between 
the 24VAC terminals. It should read approximately 24 
volts. Measure the line voltage between LINE1 and 
LINE2 to confirm that line voltage is present. 

Transducer malfunction or not installed

If lights are flashing alternatively, then no probe is 
connected or the probe is malfunctioning. When using 
a pressure transducer, with power applied to the 
control, use a voltmeter to measure volts DC between 
COMM and P1 or P2, where the wire is connected. The 
reading should be according to 

Table 3, p. 13

.

The fuse is blown and/or signs of 
damage on the unit

Miswired

The unit has been mis-wired and may be permanently 
damaged

The fan cycles from ON to OFF with 
little or no speed modulation

Improper hard start setting

Reduce hard start setting to minimum needed to 
accelerate the fan. Excessive hard start causes large 
pressure drops by running too much cold air over the 
condenser.

The high pressure switch trips off Improper head pressure setpoint setting

See unit fails to start above.

Check the setpoint and reduce it if needed.

Содержание BAYLOAM335

Страница 1: ...tion Instructions Model Numbers Used With BAYLOAM335 TTA073D3 TTA090D3 TTA073G3 TTA090G3 TTA180J3 TWA073D3 E3 TWA090D3 E3 BAYLOAM336 TTA120D3 E3 F3 TTA120G3 H3 J3 TTA150E3 H3 TTA180E3 F3 H3 TTA240E3 F...

Страница 2: ...cates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could re...

Страница 3: ...tten permission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All tra...

Страница 4: ...4 ACC SVN136E EN Table of Contents Copyright 3 Installation 5 General 5 Controller 6 Transducer and Tee 6 Motor 7 Wiring 7 Operation Troubleshooting 13 Checkout Procedure 13...

Страница 5: ...0EW FW TWA073D3 E3 TTA180H3 TTA076GD TTA126HD TTA180HW JW TWA090D3 E3 TTA240E3 F3 TTA090D4 TTA150E4 TTA240EW FW TTA240H3 F3 TTA090G4 TTA150H4 TTA240HW JW TTA300F3 TTA180J4 TTA156ED FD TTA300FW TTA300J...

Страница 6: ...ath or serious injury WARNING Ground Wire All field installed wiring must be completed by qualified personnel All field installed wiring must comply with NEC and applicable local codes Failure to foll...

Страница 7: ...orque the fan hub bolt to 165 175 in lb 8 Wire motor following unit wiring diagram see Figure 14 p 11 Figure 15 p 12 9 Reinstall the fan guard and ensure there is one inch between the fan guard and fa...

Страница 8: ...th one controller in which case the controller will respond to the transducer that senses the highest pressure see Figure 8 p 8 below for wiring Cut wire ties if necessary to properly route wires 3 Fi...

Страница 9: ...yellow light will turn off and the green light will remain off Setting the Pressure Setpoint When using pressure transducers the control will maintain condenser pressure between 20psig above and 20psi...

Страница 10: ...ll bearing motor set the hard start dial to the MIN position Begin at the recommended setting the hard start time can be fine tuned within the recommended motor range Use the minimum possible hard sta...

Страница 11: ...Installation ACC SVN136E EN 11 Figure 14 Wiring diagram TWA heat pump with ReliaTel...

Страница 12: ...Installation 12 ACC SVN136E EN Figure 15 Wiring diagram TTA cooling with ReliaTel ElectroMechanical...

Страница 13: ...procedures When possible disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing Follow proper lockout tagout procedure...

Страница 14: ...s removed Check that the 24VAC signal and the transducer are wired up correctly into the controller Erratic fan operation Control is not wired correctly See wiring diagrams Pressure transducer problem...

Страница 15: ...Operation Troubleshooting ACC SVN136E EN 15...

Страница 16: ...ced controls and HVAC systems comprehensive building services and parts For more information visit www IRCO com The manufacturer has a policy of continuous product and product data improvement and res...

Отзывы: