![Ingersoll-Rand BAYLOAM335 Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/ingersoll-rand/bayloam335/bayloam335_installation-instructions-manual_2059342013.webp)
ACC-SVN136E-EN
13
Operation & Troubleshooting
Checkout Procedure
Before leaving the installation, observe for correct
operation through the desired pressure range. See the
Operational Sequence in
Table 3
.
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures
recommended in this section of the manual could result
in exposure to electrical, mechanical or other potential
safety hazards. Always refer to the safety warnings
provided throughout this manual concerning these
procedures. When possible, disconnect all electrical
power including remote disconnect and discharge all
energy storing devices such as capacitors before
servicing. Follow proper lockout/tagout procedures to
ensure the power can not be inadvertently energized.
When necessary to work with live electrical
components, have a qualified licensed electrician or
other individual who has been trained in handling live
electrical components perform these tasks. Failure to
follow all of the recommended safety warnings
provided, could result in death or serious injury.
Table 3.
Pressure vs. voltage
Pressure (psig)
Voltage (Vdc)
0
0.5
50
0.9
100
1.3
150
1.7
200
2.1
250
2.5
300
2.9
350
3.3
400
3.7
450
4.1
500
4.5