Piping requirements
If the outdoor unit is installed below the indoor unit:
1. A drain pipe must be placed above the floor; the end of the drain pipe must not be placed in water.
2. The wrapping of the pipe must be applied from the bottom part towards the top; it should not be very
tight to avoid compression of insulating material and to prevent a loss of efficiency.
3. All pipes are joined together to form a tube bundle which is then installed onto the wall using saddle
brackets.
4. NOTE: Oil traps are required when the outdoor unit is installed below the indoor unit. An oil trap is
required at each 33 ft. (10m) of vertical gas pipe length.
Sellado
Abrazaderas
Tubo
drenado
Trampa
Outdoor unit installed below the
indoor unit
Outdoor unit installed above the
indoor unit
If the outdoor unit is installed above the
indoor unit:
1. Tape wrapping must be applied from the
bottom part towards the top; it should not be
very tight to avoid compression of insulating
material and to prevent a loss of efficiency.
2. All pipes are to be joined together to form a
tube bundle which must then be trapped to
prevent backup water into the room.
3. Install the pipes onto the wall using saddle
brackets.
4. NOTE: Oil traps are required when the
outdoor unit is installed above the indoor unit.
An oil trap is required at each 20 ft. (6m) of
gas pipe vertical rise.
22