background image

16

HB Series Desiccant Dryer Models 150-8000

ingersollrandproducts.com

A

CAUTION

Dryer should not be shut down during the heating cycle.  Doing so may
cause the Heater High Temperature alarm to activate, which will
require the user to manually reset the Heater High Temperature safety
in the control enclosure.  If the dryer must be shut down during the
heating cycle, advance the program via the Program Jog function (see
Section 9.10) to the end of the heating cycle prior to initiating the
Shutdown Sequence.  

For all Blower Purge Dryers that will be routinely shut down and
restarted, Ingersoll Rand recommends that an isolation valve be
installed at the dryer outlet.  Upon restarting the dryer, it is likely that the
pressure downstream of the dryer will have decayed.  When starting the
dryer without the valve (or with the valve in the fully open position), the
high velocities of the air through the towers could damage the desiccant,
as well as provide unprocessed air down stream.  

A

NOTICE

Prior to removing power or compressed air from the dryer, depress the
OFF button on the Microprocessor Control.  This initiates the
Shutdown Sequence, which closes the purge valves, repressurizes the
off-line tower and opens the flow valves.  

DO NOT REMOVE POWER

OR COMPRESSED AIR FROM THE DRYER DURING THE
SHUTDOWN SEQUENCE.

Shut Down Procedure: 

•     Maintain a compressed air source to the dryer and a

supply of power to the Microprocessor Controller.

10.0 INSTALLATION AND INITIAL START-UP

•     De-energize the dryer

•     Shut down air compressor or bypass dryer

•     Close Isolation Valves (if equipped)

Note: On the subsequent Start-up, the outlet isolation valve should be
in the closed position.  Slowly open the valve to build pressure
downstream.

• Verify all actuated valves are in their failsafe position.

• Using a voltmeter, check the power connections for the correct voltage

shown on the dryer serial nameplate 

• Verify blower rotation is per arrow.

• Close and secure all electrical panel covers.

• Ensure that the purge adjustment valve is in the open position.

Once power is applied to the dryer and after a brief initialization
sequence, the PRESS ON prompt will be displayed.

PRESS ON

Depress the ON button to initiate the dryer program.  The
Microprocessor Controller will display the first CUSTOMER
MODE screen

LT DRY   RT REGEN

ON

• The sequence will initiate proper Inlet and Purge Valve positioning and

tower depressurization.  

• If the dryer has been in storage or off for an extended period of time,

the Blue Moisture Indicator may be gray, the High Dew Point Alarm (if
equipped) may be activated and the Dew Point Display (if equipped)
may indicate a high dew point.  Depending upon the duration of idle
time, it may take anywhere from one to twelve hours for the alarm to
deactivate, the BMI to return to its normal blue state and dew point to
drop.

• For dryers equipped with EMS, refer to Section 9.5 regarding the use

of this option.

10.8 SHUT DOWN PROCEDURES

The following procedures must be followed to properly shut down the
dryer to avoid damage to the unit and preserve dryer performance.  The
dryer requires compressed air to actuate the valves.  Removing the
compressed air supply prior to shutting down the dryer will result in
improper valve positioning.  In addition, the dryer must complete a
specific Shutdown Sequence prior to being turned off.  Should power be
removed from the dryer or air pressure removed from the dryer prior to
the completion of the Shutdown Sequence, damage to the dryer may
occur.  Lastly, the inlet valves are configured to open on a loss of power
and the purge valves configured to close (fail safe).  Should a valve
open to a depressurized tower, as would be the case if the dryer were
stopped in mid-cycle, a rapid pressurization will occur.  

A

NOTICE

The force of repeated rapid pressurizations will damage the dryer.  

A

NOTICE

On dryers equipped with EMS, merely leaving the unit in EMS without
a compressed air supply is not advised, as it is likely that the system
pressure will decay over time.  Should this occur, the unit will go into a
FTS alarm as well as risk misalignment of valves should switchover
occur prior to reinstating the air compressor.    

Depress the OFF button to initiate the SHUTDOWN SEQUENCE.

SHUTDOWN
SEQUENCE

OFF

•     Permit the dryer to complete the full SHUTDOWN

SEQUENCE (30 seconds)

Once the PRESS ON Prompt is displayed, the dryer has
completed the SHUTDOWN SEQUENCE.  Power and air may be
safely removed from the dryer.

PRESS ON

120.26 Dryer - Operation, Installation, Maintenance Manual, and Parts 

Содержание 150-8000

Страница 1: ... Manual Del Operador ES Manual do Operador PT Manuel De L opérateur FR Operator s Manual EN I R ORDER NUMBER 81696181 CUSTOMER NAME Woodward RCC c o ALL Equipment CUSTOMER CONTACT Kerry Fang 704 655 5364 CUSTOMER P O NUMBER 78608 DRYER MODEL HB3000 EMS 120 26 Dryer Operation Installation Maintenance Manual and Parts ...

Страница 2: ...MBER 81696181 CUSTOMER NAME Woodward RCC c o ALL Equipment CUSTOMER CONTACT Kerry Fang 704 655 5364 CUSTOMER P O NUMBER 78608 DRYER MODEL HB3000 EMS 120 26 Dryer Operation Installation Maintenance Manual and Parts ...

Страница 3: ... 1 FAILURE TO REPRESSURIZE 8 4 2 FAILURE TO DEPRESSURIZE CONTENTS PAGE 8 5 HIGH DEW POINT ALARM INCLUDED WITH EMS 8 6 ENERGY MANAGEMENT SYSTEM EMS OPTIONAL 8 7 ALARM LIST 8 8 HIGH OUTLET TEMPERATURE OPTIONAL 9 0 TECHNICIAN MODE 10 9 1 ENTERING TECHNICIAN MODE 9 2 OPERATING MODE 9 3 COOL SWEEP 9 4 HEATER TEMPERATURE SETPOINT BLOWER PURGE MODE ONLY 9 5 ENERGY MANAGEMENT SYSTEM OPTIONAL 9 5 1 ENABLIN...

Страница 4: ...omplied with specific recommendations of the Company Accessories or equipment furnished by the Company but manufactured by others shall carry whatever warranty the manufacturers have conveyed to the Company and which can be passed on to the Purchaser The Company shall not be liable for any repairs replacements or adjustments to the Equipment or any costs of labor performed by the Purchaser or othe...

Страница 5: ...ll main electrical disconnect switch and disconnect any separate control lines if used before attempting to work or perform maintenance on the unit 4 Do not attempt to service any part while machine is in an operational mode 5 Do not attempt to remove any parts without first relieving the entire air system of pressure 6 Do not operate the dryer at pressures in excess of its rating 7 Do not operate...

Страница 6: ... heater and blower operate for 2 hours and 57 minutes The blower continues to operate for an additional ten minutes to cool the heater The Repressurization Valve is then opened allowing dry compressed air to pass through the regenerating tower for 48 minutes 7 0 PRINCIPLES OF OPERATION 7 3 3 HEATLESS PRESSURE SWING REGENERATION In the heatless mode following depressurization regeneration uses appr...

Страница 7: ...corresponding values When power is supplied to the dryer the Microprocessor Control will illuminate and default to the Standby mode displaying the Press ON prompt The following illustration summarizes the keypad functions Figure 1 Microprocessor Controller BUTTONS ON Initiates PLC program Begins system monitoring and valve switching functions OFF Stops PLC program Stops valve switching functions I...

Страница 8: ...E Indicates whether unit is currently consuming purging air Requires EMS Heater Status BLOWER PURGE MODE ONLY On Off Indicates that the heater is being given a signal to heat the purge air Blower Status BLOWER PURGE MODE ONLY On Off Indicates that the blower is being given a signal to supply the purge air Heater Temperature BLOWER PURGE MODE ONLY HEATER TEMP XX Indicates the heater temperature set...

Страница 9: ...gram Should however power be cut to the dryer before the Shutdown Sequence has been initiated the dryer can be configured to restart in one of two restart modes 7 8 1 MANUAL MODE ZERO Ingersoll Rand dryers are shipped from the factory in the Manual Mode After power is re supplied to the dryer the user will be presented with the PRESS ON display The valve switching and timing operations will only s...

Страница 10: ... point The EMS dew point sensor communicates the pressure dew point reading to the Microprocessor Controller Should the pressure dew point rise above the alarm set point the Microprocessor Controller will display the alarm condition on the controller screen 8 6 ENERGY MANAGEMENT SYSTEM EMS OPTIONAL EMS is an energy savings feature that matches moisture loading and regeneration energy usage Drying ...

Страница 11: ...ollowing Depressing the button returns the controller to the top of the ALARM LIST BEGIN ALARMS Depressing the button again returns the controller to the CUSTOMER MODE ALARM LIST PRESS ENTER Depressing the SELECT DISPLAY list displays the most recent of the alarms stored by the Microprocessor Control Refer to the diagram at the end of this section for an explanation of the ALARM LIST Display FAIL ...

Страница 12: ...COOL SWEEP COOL SWEEP OFF ON HEATER TEMPERATURE SETPOINT HEATER TEMP 300 425 ENERGY MANAGEMENT SYSTEM OPTIONAL EMS OFF ON ENERGY MANAGEMENT SYSTEM SETPOINT OPTIONAL EMS SET POINT 76 68 PURGE TEMPERATURE PURGE TEMP OFF ON RESTART MODE RESTART LAST ZERO EXTENDED HEATING EXTENDED HTG OFF ON HIGH DEW POINT ALARM ACTIVATION OPTIONAL HI DEW POINT OFF ON Pressing the 2 and 3 buttons simultaneously enters...

Страница 13: ...5 ENERGY MANAGEMENT SYSTEM OPTIONAL The Energy Management System option includes a dew point sensor that transmits the outlet pressure dew point to the Microprocessor Controller The Microprocessor Controller displays the outlet pressure dew point in real time This option package also includes Energy Management System an energy savings feature that matches moisture loading and regeneration energy u...

Страница 14: ...Depress the SELECT DISPLAY button until the START MODE screen is displayed RESTART ZERO SELECT DISPLAY RESTART LAST A NOTICE The restart modes will only effect restarting should power be unexpectedly removed from the dryer After proper shut down the dryer will require the user to depress the ON button to initiate the operation of the dryer program 9 8 EXTENDED HEATING OPTIONAL BLOWER PURGE MODE On...

Страница 15: ...idered normal operation The Microprocessor Controller will only permit the jog function during specific stages of the program Should the program be at a stage where the program can not advance the following will be displayed Depress the SELECT DISPLAY button until the HIGH DEW POINT SET POINT screen is displayed HI PDP SETPOINT 10 SELECT DISPLAY SET Pressing the SET button permits the value of the...

Страница 16: ...es to the inlet and outlet connections Locate the pre filters as close as possible to the dryer Ensure the positioning allows for ease of servicing Note that the wet air inlet is located at the dryer s upper manifold and the dry outlet air is located at dryer s lower manifold In situations where air supply is required 24 hours a day it is undesirable to interrupt the airflow a three valve bypass s...

Страница 17: ...ccording to the minimum circuit ampacity shown on the dryer serial nameplate and the requirements of the NEC The power connections are marked L1 L2 and L3 A CAUTION Dryer must be grounded with the full sized ground wire connected to an earth ground 10 7 START UP With dryer de energized slowly pressurize the dryer When the dryer reaches full operating pressure check the system for air leaks Soap te...

Страница 18: ...ON Depress the ON button to initiate the dryer program The Microprocessor Controller will display the first CUSTOMER MODE screen LT DRY RT REGEN ON The sequence will initiate proper Inlet and Purge Valve positioning and tower depressurization If the dryer has been in storage or off for an extended period of time the Blue Moisture Indicator may be gray the High Dew Point Alarm if equipped may be ac...

Страница 19: ...s often as required to prevent contamination of the regenerative dryer s desiccant bed Pre filter drains must be checked daily Failure to drain condensed liquid from the sump of the filter housing will result in carry over and damage to the desiccant material HB post filters are used to prevent desiccant dust particulate contamination from migrating downstream into plant processes Elements should ...

Страница 20: ...GEOUT PROCEDURE A WARNING To avoid injury depressurize dryer before performing any service A CAUTION Be sure to wear respiratory protection during the draining and filling process to minimize inhalation of desiccant as desiccant will produce dust during this procedure A NOTICE Each dryer is shipped with a desiccant sample kit to allow the desiccant to be sent for analysis This kit can be used to h...

Страница 21: ... 4 8 mm ACTIVATED ALUMINA 1 8 2 5 mm HB 3 16 4MM 8MM 1 8 2MM 5MM MODEL ACTIVATED ALUMINA LB ACTIVATED ALUMINA LB 150 52 184 200 78 266 250 100 298 300 111 359 400 160 444 500 178 570 600 86 922 800 86 1184 1000 142 1258 1200 142 1464 1500 266 1934 1800 266 2334 2100 266 2662 3000 572 3654 4000 720 4418 5000 896 6304 6000 1100 7540 8000 1400 10120 NOTE Qty is per dryer DESCRIPTION PART ACTIVATED AL...

Страница 22: ...nt to heater and blower Correct problem and reset blower motor starter Remove and clean or replace blower filter Reset blower motor starter Replace control solenoid valve Reset blower motor starter Repair or replace valve Reset blower motor starter Replace check valve Reset blower motor starter Verify and correct sizing of exhaust piping Reset blower motor starter Insufficient purge rate I Inlet a...

Страница 23: ... CONTROLLER DISPLAY PANEL SEE DETAIL 34 00 C OF AIR OUTLET 66 09 1 4 MPT AUTOMATIC DRAIN CONNECTION 1 4 MPT AUTOMATIC DRAIN CONNECTION 20 81 TOWER TEMPERATURE GAUGE REACTIVATION BLOWER OPTIONAL TOWER INSULATION SHOWN THIS VIEW ONLY PILOT AIR SHUT OFF VALVE 17 50 17 50 PREFILTER PURGE ADJUSTMENT PRESSURE GAUGE OUTLET FLOW CHECK VALVE PURGE FLOW CHECK VALVE BLOWER INTAKE FILTER HEATER REPRESSURIZATI...

Страница 24: ... 36 50 1 23 HEATER ON LIGHT BLOWER ON LIGHT 1 DRYER ON OFF CONTROL 2 DRYER ALARM 3 HEATER OPERATION TEMP CONTROL 4 HIGH HEATER TEMP ALARM 5 HEATER FAILURE ALARM 6 LEFT RIGHT TOWER DRYING 7 LEFT RIGHT TOWER REGEN 8 FAILURE TO SHIFT ALARM 9 REGEN SEQUENCE STATUS 10 BLOWER OPERATION CONTROL 11 HIGH HUMIDITY ALARM OPTIONAL 12 ENERGY MANAGEMENT SYSTEM EMS OPTIONAL TOWER TEMPERATURE GAUGE OPTIONAL TOWER...

Страница 25: ...RESET 4 TEST 5 SET 6 SELECT DISPLAY 7 ENTER 8 LCD DISPLAY 1 4 MPT AUTOMATIC DRAIN CONNECTION 1 DRYER ON OFF CONTROL 2 DRYER ALARM 3 HEATER OPERATION TEMP CONTROL 4 HIGH HEATER TEMP ALARM 5 HEATER FAILURE ALARM 6 LEFT RIGHT TOWER DRYING 7 LEFT RIGHT TOWER REGEN 8 FAILURE TO SHIFT ALARM 9 REGEN SEQUENCE STATUS 10 BLOWER OPERATION CONTROL 11 HIGH HUMIDITY ALARM OPTIONAL 12 ENERGY MANAGEMENT SYSTEM EM...

Страница 26: ...TOWER DRYING LIGHT 1 DRYER ON OFF CONTROL 2 DRYER ALARM 3 HEATER OPERATION TEMP CONTROL 4 HIGH HEATER TEMP ALARM 5 HEATER FAILURE ALARM 6 LEFT RIGHT TOWER DRYING 7 LEFT RIGHT TOWER REGEN 8 FAILURE TO SHIFT ALARM 9 REGEN SEQUENCE STATUS 10 BLOWER OPERATION CONTROL 11 HIGH HUMIDITY ALARM OPTIONAL 12 ENERGY MANAGEMENT SYSTEM EMS OPTIONAL 56 50 82 41 C OF MOUNTING HOLE C OF MOUNTING HOLE L L 40 50 2 0...

Страница 27: ...F VALVE 3 NPT AIR INLET CONNECTION 3 NPT AIR INLET CONNECTION C OF AIR INLET L TOWER TEMPERATURE GAUGE 39 75 FACE OF AIR OUTLET HEATER ON LIGHT BLOWER ON LIGHT 1 DRYER ON OFF CONTROL 2 DRYER ALARM 3 HEATER OPERATION TEMP CONTROL 4 HIGH HEATER TEMP ALARM 5 HEATER FAILURE ALARM 6 LEFT RIGHT TOWER DRYING 7 LEFT RIGHT TOWER REGEN 8 FAILURE TO SHIFT ALARM 9 REGEN SEQUENCE STATUS 10 BLOWER OPERATION CON...

Страница 28: ...F AIR OUTLET L RELIEF VALVE 3 NPT AIR INLET CONNECTION 3 NPT AIR INLET CONNECTION C OF AIR INLET L TOWER TEMPERATURE GAUGE 39 75 FACE OF AIR OUTLET HEATER ON LIGHT BLOWER ON LIGHT 1 DRYER ON OFF CONTROL 2 DRYER ALARM 3 HEATER OPERATION TEMP CONTROL 4 HIGH HEATER TEMP ALARM 5 HEATER FAILURE ALARM 6 LEFT RIGHT TOWER DRYING 7 LEFT RIGHT TOWER REGEN 8 FAILURE TO SHIFT ALARM 9 REGEN SEQUENCE STATUS 10 ...

Страница 29: ...E L L L L AFTERFILTER FACE OF AIR INLET OUTLET OPTIONAL 3 VALVE BYPASS BLOWER BLOWER INTAKE FILTER 79 50 PREFILTER BLOWER PRESSURE GAUGE NEMA 4 ELECTRICAL ENCLOSURE CONTROL BOX NEMA 4 ELECTRICAL ENCLOSURE POWER BOX CONTROLLER AND DISPLAY PANEL SEE DETAIL POWER ON LIGHT ALARM LIGHT CONTROLLER LCD DISPLAY CONTROLLER PUSH BUTTONS CONTROLLER AND DISPLAY PANEL DETAIL 1 ON 2 OFF 3 RESET 4 TEST 5 SET 6 S...

Страница 30: ...NTAKE FILTER PREFILTER BLOWER PRESSURE GAUGE NEMA 4 ELECTRICAL ENCLOSURE CONTROL BOX NEMA 4 ELECTRICAL ENCLOSURE POWER BOX CONTROLLER AND DISPLAY PANEL SEE DETAIL POWER ON LIGHT ALARM LIGHT CONTROLLER LCD DISPLAY CONTROLLER PUSH BUTTONS CONTROLLER AND DISPLAY PANEL DETAIL 1 ON 2 OFF 3 RESET 4 TEST 5 SET 6 SELECT DISPLAY 7 ENTER 8 LEFT TOWER REGEN LIGHT BLOWER ON LIGHT HEATER ON LIGHT RIGHT TOWER R...

Страница 31: ...NCLOSURE POWER BOX CONTROLLER AND DISPLAY PANEL SEE DETAIL POWER ON LIGHT ALARM LIGHT CONTROLLER LCD DISPLAY CONTROLLER PUSH BUTTONS CONTROLLER AND DISPLAY PANEL DETAIL 1 ON 2 OFF 3 RESET 4 TEST 5 SET 6 SELECT DISPLAY 7 ENTER 8 LEFT TOWER REGEN LIGHT BLOWER ON LIGHT HEATER ON LIGHT RIGHT TOWER REGEN LIGHT RIGHT TOWER DRYING LIGHT LEFT TOWER DRYING LIGHT 1 DRYER ON OFF CONTROL 2 DRYER ALARM 3 HEATE...

Страница 32: ...KE FILTER BLOWER PRESSURE GAUGE NEMA 4 ELECTRICAL ENCLOSURE CONTROL BOX NEMA 4 ELECTRICAL ENCLOSURE POWER BOX CONTROLLER AND DISPLAY PANEL SEE DETAIL POWER ON LIGHT ALARM LIGHT CONTROLLER LCD DISPLAY CONTROLLER PUSH BUTTONS CONTROLLER AND DISPLAY PANEL DETAIL 1 ON 2 OFF 3 RESET 4 TEST 5 SET 6 SELECT DISPLAY 7 ENTER 8 LEFT TOWER REGEN LIGHT BLOWER ON LIGHT HEATER ON LIGHT RIGHT TOWER REGEN LIGHT RI...

Страница 33: ... OUTLET REPRESSURIZATION VALVE BLOWER PRESSURE GAUGE 77 56 INLET FLOW VALVE TYP L L 68 13 C OF AIR INLET L BLOWER 6 00 TYP 48 00 60 00 4 50 24 50 35 50 48 62 FACE OF AIR INLET 90 00 PILOT AIR SHUT OFF VALVE NEMA 4 ELECTRICAL ENCLOSURE CONTROL BOX NEMA 4 ELECTRICAL ENCLOSURE POWER BOX RELIEF VALVE CONTROLLER AND DISPLAY PANEL SEE DETAIL POWER ON LIGHT ALARM LIGHT CONTROLLER LCD DISPLAY CONTROLLER P...

Страница 34: ... INLET FLOW VALVE L L C OF AIR INLET L 31 50 32 62 84 00 38 81 60 00 OUTLET PURGE VALVE POWER ON LIGHT ALARM LIGHT CONTROLLER LCD DISPLAY CONTROLLER PUSH BUTTONS CONTROLLER AND DISPLAY PANEL DETAIL 1 ON 2 OFF 3 RESET 4 TEST 5 SET 6 SELECT DISPLAY 7 ENTER 8 LEFT TOWER REGEN LIGHT BLOWER ON LIGHT HEATER ON LIGHT RIGHT TOWER REGEN LIGHT RIGHT TOWER DRYING LIGHT LEFT TOWER DRYING LIGHT 1 DRYER ON OFF ...

Страница 35: ...96 00 1 50 TYP 86 25 DEPRESSURIZATION MUFFLER DEPRESSURIZATION VALVE PURGE PRESSURE GAUGE PURGE ADJUSTMENT VALVE BLOWER PRESSURE GAUGE BLOWER REPRESSURIZATION VALVE 49 50 30 50 NEMA 4 ELECTRICAL ENCLOSURE CONTROLS BOX NEMA 4 ELECTRICAL ENCLOSURE POWER BOX OUTLET PURGE VALVE CONTROLLER AND DISPLAY PANEL SEE DETAIL POWER ON LIGHT ALARM LIGHT CONTROLLER LCD DISPLAY CONTROLLER PUSH BUTTONS CONTROLLER ...

Страница 36: ...N LIGHT HEATER ON LIGHT RIGHT TOWER REGEN LIGHT RIGHT TOWER DRYING LIGHT LEFT TOWER DRYING LIGHT 1 DRYER ON OFF CONTROL 2 DRYER ALARM 3 HEATER OPERATION TEMP CONTROL 4 HIGH HEATER TEMP ALARM 5 HEATER FAILURE ALARM 6 LEFT RIGHT TOWER DRYING 7 LEFT RIGHT TOWER REGEN 8 FAILURE TO SHIFT ALARM 9 REGEN SEQUENCE STATUS 10 BLOWER OPERATION CONTROL 11 HIGH HUMIDITY ALARM OPTIONAL 12 ENERGY MANAGEMENT SYSTE...

Страница 37: ...ADJUSTMENT VALVE REPRESSURIZATION VALVE INLET FLOW VALVE TYP RELIEF VALVE CONTROLLER AND DISPLAY PANEL SEE DETAIL POWER ON LIGHT ALARM LIGHT CONTROLLER LCD DISPLAY CONTROLLER PUSH BUTTONS CONTROLLER AND DISPLAY PANEL DETAIL 1 ON 2 OFF 3 RESET 4 TEST 5 SET 6 SELECT DISPLAY 7 ENTER 8 LEFT TOWER REGEN LIGHT BLOWER ON LIGHT HEATER ON LIGHT RIGHT TOWER REGEN LIGHT RIGHT TOWER DRYING LIGHT LEFT TOWER DR...

Страница 38: ... DEPRESSURIZATION VALVE FV 4F 1002 1051 FV 4G BLOWER 1051 1051 FV 4E 13 1191 12 11 1181 1171 1153 10 1161 1151 STR1 2 8 1154 SSR 2 TS 1 4 1 9 SSR 3 1152 2 34 1152 SSR 1 LEFT TOWER PURGE VALVE RIGHT TOWER INLET VALVE LEFT TOWER INLET VALVE RIGHT TOWER PURGE VALVE 1051 FV 4C FV 4A 1051 1051 FV 4D FV 4B HEATER SOLID STATE RELAY 1 HEATER SOLID STATE RELAY 2 OVERTEMP THERMOSTAT HEATER SOLID STATE RELAY...

Страница 39: ...37 HB Series Desiccant Dryer Models 150 8000 ingersollrandproducts com 14 0 WIRING DIAGRAM WIRING DIAGRAM HB800 HB1800 TM 580095 C 120 26 Dryer Operation Installation Maintenance Manual and Parts ...

Страница 40: ...I2 34 0 5 A 0 5 A 2 A 30 1051 1051 8 7 1122 EXPANSION ADAPTER LEFT TOWER DEPRESSURIZATION VALVE REPRESSURIZATION VALVE 1 EXPANSION MODULE 127 126 125 123 124 122 POWER V CABLE 0V 121 120 CABLE P 0V N OV V 1271 1251 AO0 O0 O1 A01 O2 O3 EM 1241 1051 BLOWER STR 1002 15 14 1051 I1 I0 I2 13 I5 I4 I6 I7 EA CABLE 1261 16 RIGHT TOWER DEPRESSURIZATION VALVE 1051 18 1241 1251 1261 1241 1251 1261 34 SSR 2 10...

Страница 41: ... O3 EM 1241 1051 BLOWER STR 1002 15 14 1051 I1 I0 I2 13 I5 I4 I6 I7 EA CABLE 1261 16 RIGHT TOWER DEPRESSURIZATION VALVE 1051 18 1241 1251 1261 1241 1251 1261 HEATER SOLID STATE RELAY 2 HEATER SOLID STATE RELAY 1 1002 1051 1122 1122 GND DP 5 1042 1051 1051 1042 1051 1001 22 1 2 3 4 5 6 7 8 9 1 2 3 22 12 11 9 37 7 10 13 30 58 59 60 DISPLAY PANEL 1151 1151 BLOWER AUXILIARY CONTACT STR1 1 DP R1 R1 10K...

Страница 42: ...SSR 5 1051 4 SSR 1051 HEATER SOLID STATE RELAY 5 HEATER SOLID STATE RELAY 4 1155 1002 1051 1042 1051 1051 1042 1051 1001 1153 22 FV 4B FV 4D FV 4A FV 4C FV 4E FV 4F FV 4G 1041 5V 0V 5V GND 1042 24V DCPS 24V 5V POWER SUPPLY L N 21 GROUND F6 1L1 F5 1L2 1L3 F7 MOTOR STARTER STR1 MOTOR 1M1 1M2 1M3 MOTOR BLOWER 6T3 6T2 6T1 CONTACTOR CTR2 L1 SSR4 SOLID STATE RELAYS L2 SSR5 SSR3 SSR6 L3 TAN HEATER TAN TA...

Страница 43: ...R T 1 SP 1282 1271 1241 1261 1251 1181 1191 1171 1051 1151 1152 1122 1051 GND 1002 1001 1001 1161 10 BLK 3 1 3 1 32 33 35 34 31 30 29 2 WHT 1 26 25 28 27 21 23 24 22 R1 R2 DCPS 24V 1042 DC I2 DC I1 DC I0 DCPS 5V 1041 DCPS 0V 1051 DC AN0 18 19 20 TB 2 SP 1282 1271 14 16 15 17 11 12 13 1241 1261 1251 1181 1191 1171 6 8 9 7 4 5 3 1051 1151 1152 1122 DCPS 0V 1051 1002 GND TB 1 2 1 1001 1001 1152 1152 ...

Страница 44: ...42 HB Series Desiccant Dryer Models 150 8000 ingersollrandproducts com 15 0 FLOW DIAGRAM FLOW DIAGRAM HB150 HB400 580477 B 120 26 Dryer Operation Installation Maintenance Manual and Parts ...

Страница 45: ...43 HB Series Desiccant Dryer Models 150 8000 ingersollrandproducts com 15 0 FLOW DIAGRAM FLOW DIAGRAM HB500 HB800 580309 C 120 26 Dryer Operation Installation Maintenance Manual and Parts ...

Страница 46: ...44 HB Series Desiccant Dryer Models 150 8000 ingersollrandproducts com 15 0 FLOW DIAGRAM FLOW DIAGRAM HB1000 HB1200 580043 D 120 26 Dryer Operation Installation Maintenance Manual and Parts ...

Страница 47: ...45 HB Series Desiccant Dryer Models 150 8000 ingersollrandproducts com 15 0 FLOW DIAGRAM FLOW DIAGRAM HB1500 HB8000 580051 E 120 26 Dryer Operation Installation Maintenance Manual and Parts ...

Страница 48: ... 631853 631853 631853 2 GAUGE PRESSURE PURGE 0 300 PSI 634278 634278 634278 634278 634278 634278 1 GAUGE PRESSURE TOWER 0 300 PSI 631789 631789 631789 631789 631789 631789 2 GAUGE TOWER TEMPERATURE 631787 631787 631787 631787 631787 631787 2 HEATER 632560 632037 632356 632356 633692 632044 1 MODULE CONTROLLER EXPANSION 633602 633602 633602 633602 633602 633602 1 1 1 1 MODULE CONTROLLER EXPANSION A...

Страница 49: ... 300 PSI 634278 634278 634278 634278 634278 634278 1 GAUGE PRESSURE TOWER 0 300 PSI 631789 631789 631789 631789 631789 631789 2 GAUGE TOWER TEMPERATURE 631787 631787 631787 631787 631787 631787 2 HEATER 632044 633792 633725 633725 633741 633741 1 MODULE CONTROLLER EXPANSION 633602 633602 633602 633602 633602 633602 1 1 1 1 MODULE CONTROLLER EXPANSION ADAPTER 683953 683953 683953 683953 683953 6839...

Страница 50: ...ONTROL AIR 630524 630524 630524 630524 630524 630524 1 1 1 1 MUFFLER PURGE 680455 680455 633766 633766 633766 633766 OVERLAY CONTROLLER 634088 634088 634088 634088 634088 634088 1 OVERLOAD MOTOR STARTER 633726 683880 683880 683880 684022 684022 1 POWER SUPPLY 5V 24V DC 633665 SP 633665 SP 633665 SP 633665 SP 633665 SP 633665 SP 1 1 1 1 PROBE TEMPERATURE 633609 633609 633609 633609 633609 633609 1 ...

Страница 51: ...r HP MCA MOP Width in cm Depth in w o Bypass cm Depth in w Bypass cm Height in cm Air In out Connection Shipping Weight lbs kg Desiccant Weight lbs kg HB150 150 3 1 6 8 45 144 33 84 39 99 66 168 1 1050 476 236 107 HB200 200 4 5 1 7 8 49 124 37 94 45 114 67 170 1 1 2 1150 522 344 156 HB250 250 6 1 5 11 12 53 135 38 97 46 117 68 173 1 1 2 1400 635 398 181 HB300 300 6 1 5 11 12 53 135 38 97 46 117 68...

Отзывы: