PYRAMID-PLUS UPS’s can be provided with boards that are designed as communication interface
with computer systems or remote monitoring panels.
- The dry contacts interface
- The serial link interface
- The remote signalling/control panel and its connection interface
7.1 Serial Link Interface
Using serial link interface which is installed in your system, user can get all information about UPS .
All measured parameters, alarms can be monitored. This port is interactive and you may use the
following commands:
•
Switch to BYPASS
•
Switch to INVERTER
•
SOUND on/off
•
Adjust UPS time and date
•
Start SIMULATION mode
•
Short BATTERY TEST
•
BATTERY TEST until battery low alarm
•
CANCEL battery test
•
Turn off UPS output voltage immediately (SHUTDOWN)
•
Turn off UPS output voltage after delay (WAITING SHUTDOWN)
•
Turn off UPS output voltage (SHUTDOWN) and turn on UPS output voltage (WAITING
RESTART)
•
CANCEL SHUTDOWN
•
RENAME UPS
UPS will give response to these commands if the
REMOTE: ENABLE
opsion is selected from
SETTINGS MENU .
7.2 Serial Link Interface Cable
The maximum length for RS232 communication cable is 25 meters, cable connector pins are as
follows :
UPS side
PC side
9 Tx
2 Rx
7 Gnd
5 Gnd
6 Rx
3 Tx
For remote panel – UPS connection cable is okay.
SERIAL LINK SETUP
BAUD RATE
2400 baud
STOP BIT
1
DATABITS 8
BIT
PARITY None