Non-compliance with the installation guidelines contained in the present manual could adversely
effect the working and/or reliability of the UPS.
3.1 Introduction
WARNING!!!
•
Do not apply electrical power to the UPS equipment before the arrival of authorized service
personnel.
•
Installation and maintenance has to be done by authorized service person only.
3.2
Unpacking
The UPS is packed and enclosed in a structural cardboard carton to protect it from damage.
1.
Inspect for damage that may have occurred during the transport, if any damage is noted, please
call the forwarder or insurance company immediately and retain the shipping carton and the
UPS
.
2.
Carefully open the carton and take the UPS out.
3.
Keep the carton and packing material for future re-use.
3.3 Equipment Positioning
1.
The equipment’s installation place must be easy to service.
2.
Install the UPS in a protected area with adequate airflow and free of excessive dust.
3.
You must therefore allow for a minimum gap of 250 mm behind the unit to allow adequate air
flow (See Figure 3.1)
4.
Select a suitable place (temperature is between 0
°
C and 40
°
C) and the relative humidity (%90
max)
5.
It is recommended to use air-conditioned room (24
°
C)
6.
Temperature is a major factor in determining the battery life and capacity. Battery manufacturers
quote figures for an operating temperature of 20
°
C. On a normal installation the battery
temperature is maintained between 15
°
C and 25
°
C. Keep batteries away from main heat sources
or main air inlets etc.
7.
In case of UPS operation in a dusty environment, please clean the air with a suitable air filtration
system.
8.
Keep out of your equipment from the explosive and flammable items.
9.
Avoid direct sunlight, rain, and high humidity.
WARNING!!!
Check the capacity of the forklift if it is available for lifting.
DO NOT MOVE THE BATTERY CABINET WHILE THE BATTERIES ARE INSTALLED.
Содержание Pyramid Plus
Страница 1: ...288713405 Operating and Installation manual for PYRAMID PLUS 10 200kVA Uninterruptible Power Systems...
Страница 2: ...288713405...
Страница 38: ...288713405 35 Figure 6 3 a POWER CONNECTIONS OF TWO UPS s FOR PARALLEL OPERATION 10 15 20 kVA...
Страница 39: ...288713405 36 Figure 6 3 a POWER CONNECTIONS OF TWO UPS s FOR PARALLEL OPERATION 30 kVA...