5 - 14
XTC/3 Operating Manual
5.2.2.3.5 Standard Query Input Definition (XTC/3M Only)
Command:
QI <Input Number>
Input Number = <Byte> 1-9, 255 (255=All 9 inputs)
Response:
If Input Number was 1 – 9:
<Input Definition>
If Input Number was 255:
<Input 1 Definition> <Input 2 Definition> … <Input 9 Definition>
Input Definition = < Byte > As decoded below
0 Blank (Input not used)
1 Start
2 Stop
3 End Deposit
4 Rate Watcher Hold Initiate
5 Rate Watcher Hold Inhibit
6 Crystal Fail Inhibit
7 Zero Thickness
8 Soak 2 Hold
9 Crucible 1 Valid
10 Crucible 2 Valid
11 Reset
12 Select Process 1-4, 2 bits*
13 (Select Process 1-4, 2 bits, bit 2)
14 Select Process 1-16, 4 bits*
15 (Select Process 1-16, 4 bits, bit 2)
16 (Select Process 1-16, 4 bits, bit 3)
17 (Select Process 1-16, 4 bits, bit 4)
18 Select Process 1-64, 6 bits*
19 (Select Process 1-64, 6 bits, bit 2)
20 (Select Process 1-64, 6 bits, bit 3)
21 (Select Process 1-64, 6 bits, bit 4)