SE5M24

2

Off:  The valve is closed when the stem is in its highest position.

SW2 Control signal

On:  2...10 V DC
Off:  0...10 V DC
 

The actuator can also be connected to a 4...20 mA control signal.  

 

In this case, a 500 Ohm resistor should be installed between the  

 

control signal input (terminal 3) and system neutral (terminal 2)   

 

and SW2 should be set to position On (2...10 V DC).  

 

The control signal will then be converted to 2...10 V DC.

SW3 Reverse/Direct operation

On:  Reverse operation. The actuator closes the valve on increasing   
 

control signal.

Off:  Direct operation. The actuator opens the valve on increasing    
 

control signal.

SW4 Split function

On:  Split function. Two actuators can share a control signal and work  
 

in sequence.

Off:  No split function.

SW5 Working range when using split function

On:  5…10 V= 0…100 % (6…10 V when SW2=On)
Off:  0…5 V= 0…100 % (2…6 V when SW2=On)

LEDs

The actuator has two LEDs with indications according to the table 

below.

Indication

Green steady light

Actuator working properly

Green light quick flashing

Test run in progress

Green light slow flashing

The setting was changed during the 
operation. The new setting will be 
valid after the next power on.

Red and green steady light

Endpoint reached

Red light slow flashing

Override operating mode

Red steady light

Operation faulty, either the improper 
installation or the valve stroke lost

 

Endpoint markers

There is a red and a blue plastic endpoint marker on the actuator 
linkage. The markers can easily be moved in order to show when the 
actuator is closed/open for heating/cooling. 
For heating valves, the red marker should be in the completely open 
valve position and the blue marker in the completely closed valve 
position. 
For cooling valves, the blue marker should be in the completely open 

valve position and the red marker in the completely closed valve position.

 

EMC emissions & immunity standards

This product conforms to the requirements of the EMC Directive  
2004/108/EC through product standards EN 60730-1:2000 and 
EN 60730-2-14:1997.

RoHS

This product conforms with the Directive 2011/65/EU of the European 
Parliament and of the Council.

Contact

AB Industrietechnik Srl

Via Julius Durst, 70 - 39042 Bressanone (BZ) - Italy
Tel.  +39 0472/830626 - Fax +39 0472/831840
www.industrietechnik.it - [email protected]

i

ISTRUZIONI

 

SE5M24

IT

Prima dell‘installazione e del cablaggio del prodotto, 

leggere le presenti istruzioni.

Attuatore per valvola con comando 0(2)...10 V

Il modello SE5M24 è un attuatore valvola adatto al controllo di valvole 
AB Industrietechnik 

VFG2, VFG3, VFD2, VFD3, VFDH fino a DN80.

 

È dotato della funzione di regolazione automatica della corsa e può 
essere azionato manualmente.

Caratteristiche tecniche

Tensione di alimentazione   

24 V CA ±15%, 50/60 Hz

 

 

 

o 24 V CC ±15% 

Segnale di comando 

 

0(2)...10 V CC 

Potenza assorbita   

 

Max. 4,5 W 

Corsa 

 

 

10...30 mm 

Tempo di corsa 

 

 

1,5 s/mm 

Forza 

 

 

500 N 

Temperatura ambiente 

 

0...50°C 

Temperatura di stoccaggio  -40...80°C 
Umidità ambiente   

 

10...90 % UR 

Dimensioni 

 

 

150 x 253 x 85 mm 

Classe di protezione 

 

IP54

Installazione

Montare sulla valvola l’adattatore per lo stelo e l’adattatore per il 

fissaggio valvola, se non sono già montati. Estrarre lo stelo della 

valvola il più possibile. 

Rimuovere i dadi di fissaggio e il bullone a U dalla staffa 

dell’attuatore. Se necessario, muovere manualmente (vedi 
azionamento manuale) il perno dell’attuatore in modo che i fori di 
montaggio del bullone a U, siano allineati alla scanalatura presente 
sull’adattatore valvola. Premere, quindi, la linguetta a molla sul 
dispositivo a ghigliottina e inserire lo stelo della valvola. Rilasciare la 
linguetta per assicurare l’aggancio.
Per far estendere verso l’esterno il perno dell’attuatore, premere il 
centro del pulsante manuale ruotandolo poi in senso orario e in senso 
antiorario per ritrarlo Quando la valvola è posizionata correttamente, 

inserire il bullone a U. Serrare i dadi fino a quando la valvola non è 
fissata saldamente. 

Per il disassemblaggio eseguire la procedura in ordine inverso.

Содержание SE5M24

Страница 1: ...V DC Measuring voltage for position indication Signal neutral Y U B M G0 G Stroke and endpoint calibration Stroke and endpoint calibration is not necessary due to a construction utilizing endpoint stops When the valve reaches the endpoint a force is generated Once the force of the actuator reaches a predefined level the limit switch automatically halts the drive motor Override Activation of the ov...

Страница 2: ...o the requirements of the EMC Directive 2004 108 EC through product standards EN 60730 1 2000 and EN 60730 2 14 1997 RoHS This product conforms with the Directive 2011 65 EU of the European Parliament and of the Council Contact AB Industrietechnik Srl Via Julius Durst 70 39042 Bressanone BZ Italy Tel 39 0472 830626 Fax 39 0472 831840 www industrietechnik it info industrietechnik it i ISTRUZIONI SE...

Страница 3: ...ove impostazioni saranno valide a partire dalla successiva accen sione dell attuatore 1 On 0 Off SW1 Perno in basso con valvola chiusa Perno in alto con valvola chiusa FS impostazione di fabbrica SW2 Y 2 10 V CC Y 0 10 V CC FS SW3 Funzionamento inverso Funzionamento diretto FS SW4 Segnale Y suddiviso secon do impostazione di SW5 Nessuna funzione di suddivisione FS SW5 5 6 10 V 0 100 0 2 5 6 V 0 10...

Страница 4: ...e consommée 4 5 W max Course 10 30 mm Temps de course 1 5 s mm Force 500 N Température ambiante 0 50 C Température de stockage 40 80 C Humidité ambiante 10 90 HR Dimensions LxHxP 150 x 253 x 85 mm Indice de protection IP54 Installation Si ce n est pas déjà fait montez la tige et l adaptateur sur la vanne Tirez la tige au maximum Retirez l attache en U de l actionneur Insérez la tige de la vanne da...

Страница 5: ... actionneur ferme la vanne quand le signal de commande augmente Off Fonctionnement direct L actionneur ouvre la vanne quand le signal de commande augmente SW4 Fonction split On Fonction split active Deux actionneurs peuvent partager un même signal de commande et travailler en séquence Off Fonction split inactive SW5 Plage de fonctionnement avec la fonction split On 5 10 V 0 100 6 10 V quand SW2 On...

Страница 6: ...ler U 0 10 V DC Measuring voltage for position indication Signal neutral Y U B M G0 G Hubweg und Enpunktkalibrierung Eine Hubweg und Endlagenkalibrierung wird nicht benötigt da bei Erreichen der Endlage eine Stellkraft generiert wird Erreicht diese ein vorbestimmtes Niveau stoppt ein Endlagenschalter automatisch den Antriebsmotor Übersteuerung Bei Aktivierung des Übersteuerungseingangs wird das Ve...

Страница 7: ...nstellungen während des Testlaufs geändert Die neuen Einstellungen sind ab dem nächsten Einschalten gültig Stetiges rotes und grünes Licht Endlage erreicht Rotes langsam blinkendes Licht Betriebsmodus Übersteuerung Stetiges rotes Licht Fehlfunktion entweder inkorrekte Installation oder fehlender Hubweg Endlagenanzeige An der Konsole des Stellantriebs befinden sich eine rote und eine blaue Endlagen...

Отзывы: