Ref.
013001000100
Rev.1: 18-01-2021
32
13.
Installation and Maintenance
Notes for installation:
-
The installation position should be free from the following: dust or oil smoke,
conductive dust, corrosive or flammable gas, high temperature, condensation, and
rain.
-
Besides, vibration and impact also affect the PLC normal operation and shorten its
lifespan; electric shock, fire or misact also damages the product. During drilling or
wiring, prevent the metal particles or wire segments from falling into the PLC casing,
which may cause fire, fault or misact.
-
After the PLC installation, clean the ventilation duct to prevent blocking, which may
cause bad ventilation, or even fire, faults or misact.
-
Do not online connect, plug or unplug cables, which is apt to cause electric shock or
damage the circuit. Installation and wire connection must be firm and reliable. Poor
connection could cause misact.
-
Use shielded twisted pair for the I/O of high frequency signal and analog signal to
improve system IMS.
The installation environment should be free from dust, oil smoke, conductive particle,
corrosive or flammable gases, high temperature, condensation, and rain.
Besides, vibration and impact also affect the PLC normal operation and shorten its lifespan.
It is recommended to install the PLC, together with the matching switches and contactors,
in a dedicated electric cabinet and keep the cabinet ventilated. If the location has high
ambient temperature or heat generating equipment nearby, install forced convection
devices on top or sides of the cabinet to avoid over-temperature. During drilling or wiring,
prevent the metal particles or wire segments from falling into the PLC casing, which may
cause fire, fault or misact. After the PLC installation, clean the ventilation duct to prevent
blocking, which may cause bad ventilation, or even fire, faults or misact.
The only way to disconnect the equipment from the electrical network is by removing the
connectors that feed the equipment. Once installed in the electrical cabinet it is very
important to ensure the power connectors for proper operation.
Separate the 10 I/Os DIGITAL MODULE from heat, high voltage and electrical noise:
Always separate the devices that generate high voltage and high electrical noise from the
10 I/Os Digital Module. When configuring the layout of the 10 I/Os Digital Module inside
your panel, consider the heat-generating devices and locate the electronic-type devices in
the cooler areas of your cabinet. Reducing the exposure to a high-temperature
environment will extend the operating life of any electronic device. Also consider the
routing of the wiring for the devices in the electric cabinet. Avoid placing low-voltage
signal wires and communications cables in the same tray with AC power wiring and high
energy, rapidly switched DC wiring.
Provide adequate clearance for cooling and wiring 10 I/Os Digital Module. Is designed for
natural convection cooling. For proper cooling, you must provide a clearance of at least 25 cm
Содержание PLC 10
Страница 1: ...PLC 10 I Os DIGITAL MODULE CPU ARDUINO NANO PLC 10 I Os DIGITAL MODULE CPU ARDUINO NANO...
Страница 2: ...Ref 013001000100 Rev 1 18 01 2021 1...
Страница 25: ...Ref 013001000100 Rev 1 18 01 2021 24...
Страница 30: ...Ref 013001000100 Rev 1 18 01 2021 29 10 Typical Connections 3 3 24v...
Страница 32: ...Ref 013001000100 Rev 1 18 01 2021 31 12 10 I Os Family Dimensions 45mm width DIN rail mounting...