background image

WARNINGS AND LIMITATIONS

 

Our devices use high quality electronic components and plastic materials that are 
highly resistant to environmental deterioration. However, after 10 years of continu-
ous operation, it is advisable to replace the devices in order to minimize the risk of 
reduced  performance  caused  by  external  factors.  Ensure  that  this  device is  only 
used  with  compatible  control  panels.  Detection  systems  must  be  checked,  ser-
viced and maintained on a regular basis to confirm correct operation.

 

Smoke detectors may respond differently to various kinds of smoke particles, thus 
application  advice  should  be  sought  for  special  risks.  Detectors  cannot  respond 
correctly if barriers exist between them and the fire location and may be affected 
by special environmental conditions.

 

Refer to and follow national codes of practice and other internationally recognized 
fire engineering standards.

 

Appropriate  risk  assessment  should  be  carried  out  initially  to  determine  correct 
design criteria and updated periodically.

 

WARRANTY

 

All  devices  are  supplied  with  the benefit of  a  limited  3  years  warranty  relating  to 
faulty  materials  or  manufacturing  defects,  effective  from  the  production  date 
indicated on each product.

 

This warranty is invalidated by mechanical or electrical damage caused in the field 
by incorrect handling or usage.

 

Product  must  be  returned  via  your  authorized  supplier  for  repair  or  replacement 
together  with full information on any problem identified.

 

Full  details  on  our  warranty  and  product’s  returns  policy  can  be  obtained  upon 
request.

 

ARGUS SECURITY S.R.L.

 

Via del Canneto, 14

 

34015 Muggia (TS)

 

Italy

 

16

 

HFW

-

SIM

-

01

-

AS + HFC

-

WSR

-

03

 

HFW

-

SIM

-

01

-

AS + HFC

-

SBR

-

23

-

03

 

HFW

-

SIM

-

01

-

AS + HFC

-

WSR

-

03

 

HFW

-

SIM

-

01

-

AS + HFC

-

SBR

-

23

-

03

 

For use in compatible fire detection and alarm system.

 

Category rating: W 

-

 2.5 

-

 7

 

Duration of operation: Pass

 

Provision for external conductors: Pass

 

Flammability of materials: Pass

 

Enclosure protection: Pass

 

Access: Pass

 

Manufacturer's adjustments: Pass

 

On

-

site adjustment of behaviour: Pass

 

Requirements for software controlled devices: Pass

 

Coverage volume: Pass

 

Variation of light output: Pass

 

Minimum and maximum light intensity: Pass

 

Light colour: White

 

Light temporal pattern / frequency of flashing: N/A / 0.5 Hz

 

Marking and data: Pass

 

Synchronization: Pass

 

Durability: Pass

 

Temperature resistance: Pass

 

Humidity resistance: Pass

 

Shock and vibration resistance: Pass

 

Corrosion resistance: Pass

 

Electrical stability: Pass

 

ABN 67 153 750 648

 

SAI Global

 

Lic SMK40120

 

AS ISO 7240.25 

-

 2015

 

AS ISO 7240.23 

-

 2014

 

Содержание HFC-SBR-23-03

Страница 1: ...ION 3 Set the HFW SIM 01 AS s link switch to ON 4 Extract the HFW SIM 01 AS s battery covers 5 Insert both batteries into their HFW SIM 01 AS holders oriented as per polarity marks 6 Link the HFW SIM 01 AS device to the Hyfire system LINKING 7 Reinstall the battery covers 8 Check the wireless link quality of the HFW SIM 01 AS positioned in the final installation location WIRELESS LINK QUALITY CHEC...

Страница 2: ... in picture 1 when in the open position flush 4 Detach the sounder body from the base by pulling gently to separate picture 2 MODULE S EXTRACTION 1 Gently release the locking catch allowing the module to lift and rotate to release from the side wall 2 Remove the module Picture 2 Picture 3 Picture 1 When assembling or removing the front operating section of the sounder to from the back box be caref...

Страница 3: ... will start blinking according to the following table 3 Move the link switch to position BLANK again device will NOT WORK if the link switch is on position ON LINK SWITCH LED INDICATOR Picture 4 During all the duration of the linking phase the module must be only a few inches away from the transla tor expander module you are linking to LINK QUALITY EVALUATION DEVICE S INDICATION No connection Fail...

Страница 4: ...TION Fix the sounder base to the wall the prepared location options for the fixing screws are highlighted in picture 6 MODULE S INSTALLATION 1 Insert the terminal edge of the module between the securing points on the wall of the back box 2 Gently push down the module body so that the locking catch engages fully to hold the PCB in place Check that it feels secure Picture 5 Picture 6 LOCKING CATCH P...

Страница 5: ... select the five switch selection settings OUTPUT VOLUME SETTING Use the DIP switch at the back of the sounder body to select the output volume in particular switches 6 and 7 highlighted in picture 9 are used The switches positioned upwards acquire value 1 on the other hand if positioned downwards acquire value 0 1 Select the alarm volume required when the sounder is activated table 3 2 Refer to t...

Страница 6: ... for 150ms 11001 HF Back up interrupted tone fast 15 2800Hz continuous 01001 HF Continuous 16 800Hz for 500ms then OFF for 500ms 01111 Interrupted tone 17 1000Hz for 250ms then OFF for 250ms 01101 Interrupted tone medium 18 970Hz for 500ms then OFF for 500ms 01110 ISO 8201 LF BS5839 Pt 1 1988 19 2850Hz for 500ms then OFF for 500ms 01100 ISO 8201 HF 20 800Hz for 150ms then OFF for 150ms 11010 LF Ba...

Страница 7: ...ep for the second side locking mechanism starting from point 2 the locking mechanism appears as in picture 11 once closed recessed 5 To secure use the retaining screws using the location holes on both sides of the base picture 12 Picture 10 Picture 12 Picture 11 When assembling or removing the front operating section of the sounder to from the back box be careful to ensure the interconnection bloc...

Страница 8: ...T When the translator module indicates a low battery condition on a child device batteries must be replaced When a low battery condition is indicated both batteries must be changed altogether During this procedure the linking switch must NOT be touched at all 1 Detach the front operating section from the sounder back box 2 Extract the HFW SIM 01 AS from the sounder s back box 3 Extract the HFW SIM...

Страница 9: ...Picture 13 ...

Страница 10: ...m Device VAD frequency 0 5 Hz VAD flash coverage W 2 5 7 122 5 m3 Tolerated temperature range 25 C 55 C Maximum tolerated humidity 85 RH without condensation Height base included 192 mm Diameter 130 mm Weight 380 g IP rating EN 54 3 certified 33C Type B IP rating not certified 65 TECHNICAL SPECIFICATIONS HFW SIM 01 AS Communication range with the translator expander 200 m in open space Operating f...

Страница 11: ...ctive from the production date indicated on each product This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect handling or usage Product must be returned via your authorized supplier for repair or replacement together with full information on any problem identified Full details on our warranty and product s returns policy can be obtained upon request ARGU...

Отзывы: