FIREscape System Installation Manual
Page 9 of 56
3.2
Installation Environment
The operating environment of the system and its connected components must be considered at the design
stage prior to installation
4
Panel Housing
4.1
Installation
The weight of the control panel is approximately 8 kg, including 1 x 7 Ah battery. The weight of the control panel
must be considered when for wall mounting. The cable between the control panel and the transformer must not
exceed 1 m. The cable is provided with the control panel.
Figure 2 - An example installation
Drill 4 x 6mm holes for the mounting plugs. The hole depth must be 20
–25 mm. Refer to
Figure 3 on page 8 for the location of the holes. Once drilled, insert appropriate fixing plugs.