![Incite Fire FIREscape Скачать руководство пользователя страница 25](http://html.mh-extra.com/html/incite-fire/firescape/firescape_installation-manual_2051134025.webp)
FIREscape System Installation Manual
Page 27 of 56
12 Emergency Luminaires
The majority of the FIREscape light units can be fitted directly to the standard mounting base (EL-TSB).
12.1 EL-DL2-AS Escape Corridor Down Light
The EL-DL2-AS corridor down light is an LED
based, addressable corridor down light
featuring one high- powered LED with a
specially engineered dual surface free-form
optic.
The unit’s body contains the electronics and the
stand-by battery and features a bicolored status
LED indicating charge/fault status (green for
charging, red for fault).
12.1.1 EL-DL2-AS Technical Specifications
Classification
C0: C2 C90: E25
Ordering code
EL-DL2-AS
Operating Voltage
24v
– 40v
Minimum Standby Operating time
+ 3 Hours
Power consumption from line (W)*
0.1 Watt
Battery
7.4v /450mAh / 3.33Wh
Dimensions (mm)
100 (diameter) x 48 (height) (inc 8mm for EL-
TSB base)
Weight including battery (g)
100g
Temp Range
40°C
Fire class
UL94 V-O
Case material
Fire resistant PC + ABS plastic (FR3010)
Case color
White (RAL 9003 “Signal White”)
Compliance
AS2293, AS/NZS 60598.2.22, EN55015
IP Rating
IP 20 (IP67 available with EL-DE)
Base Compatibility
EL-TSB
12.1.2 EL-DL2-AS Classifications & Mounting Heights
Mtr
2.1 2.4 2.7
3
3.3
3.6
4
4.5
5
6
7
8
9
10
15
C0
C2
4.1 4.1 4.1
3.9
3.7
3.3
2.6
C90
E25
9
10 10.8 11.4 12.2 12.8 13.6 14.4 15.2 16.6 17.
4
18.2 18.6 18.6 17.4
Содержание FIREscape
Страница 1: ...Emergency Lighting System INSTALLATION MANUAL ...
Страница 22: ...FIREscape System Installation Manual Page 24 of 56 Figure 6 An example of a spur arrangement ...
Страница 37: ...FIREscape System Installation Manual Page 39 of 56 Figure 20 EL EXP Connection ...
Страница 47: ...FIREscape System Installation Manual Page 49 of 56 Minimum Operating Voltage 7 5 V Figure 28 ...
Страница 48: ...Page 50 of 56 FIREscape System Installation Manual Minimum Operating Voltage 8 5 V Figure 29 ...
Страница 50: ...Page 52 of 56 FIREscape System Installation Manual Minimum Operating Voltage 7 5 V Figure 31 ...
Страница 51: ...FIREscape System Installation Manual Page 53 of 56 Minimum Operating Voltage 8 5 V Figure 32 ...