Document No. BExDS120D and BExDS110D (Gas-Dust) English Issue E (Four Sheets) 19-02-10 (5
)
INSTRUCTION MANUAL (ATEX / IECEx) (GBR)
BExDS120D and BExDS110D
Flameproof Sounders
For use in Flammable Gas and Dust Atmospheres
2) Marking
All units have a rating label, which carries the following
important information:-
Unit Type No.
BExDS120D or BExDS110D
Input Voltage: DC Units 12V or 24V or 48V
AC Units 230V or 110V or 115V
Codes:
Ex d IIC T4 for Ta –50ºC to +55ºC
Ex d IIB T4 for Ta –50ºC to +70ºC
Ex tD A21 IP67 T115ºC based on max Ta of +70ºC
Certificate No’s
KEMA 99ATEX6312
IECEx KEM 10.0003
“Warnings
”
DO NOT OPEN WHEN AN EXPLOSIVE
GAS OR DUST ATMOSPHERE IS PRESENT
COVER BOLTS CLASS A4-80
USE HEAT RESISTING CABLES AND CABLE GLANDS
(Rated 110ºC) AT AMB. TEMPERATURES OVER 40ºC
4) Installation Requirements
Sounders must be installed in accordance with the following
or equivalent standards.
EN60079-14:2008
Electrical Installations in Hazardous
IEC60079-14:2007 (Ed4)
Areas (other than mines)
EN60079-10:2003
Classification of Hazardous Areas
IEC60079-10:2008 (Ed1)
Installation should only be carried by competent personnel
and any local codes of practice applied.
5) Zones, Gas Group, Category and Temperature
Classification
The units can be installed in locations with the following
conditions:-
Area Classification Gas:
Zone 1
Explosive gas air mixture likely to occur in
normal operation.
Zone 2
Explosive gas air mixture not likely to occur,
and if it does, it will only exist for a short time.
Gas Groupings:
Group IIA
Propane
Group IIB
Ethylene
Group IIC < +55ºC
Hydrogen and Acetylene
Temperature Classification:
T1
400
o
C
T2
300
o
C
T3
200
o
C
T4
135
o
C
Area Classification Dust:
Zone 21
Explosive dust air mixture likely to occur in
normal operation.
Zone 22
Explosive dust air mixture not likely to occur,
and if it does, it will only exist for a short time.
IP Rating:
IP67
T100ºC Ta < +55ºC
T115ºC Ta < +70ºC
Equipment Category:
2G/D
Ambient Temperature Range:
-50
°
C to +55
°
C
Gas Groups IIA, IIB and IIC
-50
°
C to +70
°
C Gas Group IIA and IIB
6) Sounder Location and Mounting
See drawing A
7) Access to the Flameproof Enclosure
See drawing B
Note the four
M6 screws are Class A4-80 stainless steel
and only screws of this category can be used on these
sounders.
It is therefore important that these screws and
their spring washers are kept in a safe place during
installation.
8) Power Supply Selection
The system power supply must have the necessary capacity
to provide the input current to all of the sounders connected
to the system.
The following table shows the input current taken by the
various sounder units:-
Unit Type
Input
Input
Max.
Voltage
Current I/P Volts
BExDS120D
24V DC
800mA
30V
BExDS120D
12V DC
850mA
15V
BExDS120D
48V DC
420mA
58V
BExDS120D
230V AC
90mA
264V
0518
II 2G/D
Epsilon x:
Equipment Group and
Category:
CE Marking:
Notified Body No.