Incremental Mode

In Incremental Mode, alarms and warnings occur when the difference between two consecutive measurement values is less than
the minimum threshold value or greater than the maximum threshold value. This difference means the alarm threshold is a slope
instead of a fixed value.

Minimum

Threshold

Value

Maximum

Threshold

Value

Current

Measurement Value

Previous

Measurement

Value

Measurement

Delta

Result

10

60

200

150

50

OK

10

60

199

200

-1

ALARM

-50

50

300

260

40

OK

-50

50

300

200

100

ALARM

-50

50

200

240

-40

OK

-50

50

400

500

-100

ALARM

-6000

200

0

1000

-1000

OK

-6000

10

130

110

20

ALARM

-6000

10

130

125

5

OK

-10

8000

150

165

-15

ALARM

-10

8000

1200

0

1200

OK

Tips:

l

Minimum Threshold values should be negative, otherwise a decreasing parameter will always generate an alarm.

l

Maximum Threshold values should be positive, otherwise an increasing parameter will always generate an alarm.

l

Set Minimum Threshold values to large negative numbers to disable alarms for decreasing values (see the green values
above).

Probe Out of Range SMS Alarms in Absolute Mode

The Cube can send SMS (text) messages when alarms are triggered. SMS alarms are enabled in the General Information,
Parameters, and Functional Options section on the Alarms tab.

Below is an example situation showing when SMS messages would be sent for the "Reading from Probe Out of Range" alarm with
the following settings.

Содержание 0034390

Страница 1: ...change without notice In Situ In Situ logo Baro Merge BaroTROLL HERMIT HydroVu iSitu Pocket Situ RDO RuggedCable RuggedReader SmarTROLL TROLL VuSitu and Win Situ are trademarks or registered trademark...

Страница 2: ...arks of In Situ Inc Microsoft and Windows are registered trademarks of Microsoft Corporation Pentium is a registered trademark of Intel Tefzel and Delrin are registered trademarks of E I DuPont de Nem...

Страница 3: ...be to the Computer 10 Select Connected Probes 10 Select Probe Parameters for Alarming 10 Set Level Reference 11 Set the Site Name and Clock 11 Configure Options 12 Modem Parameters 12 Activate Alarms...

Страница 4: ...rd 19 SD Card 19 Warranty 19 Obtaining Repair Service 20 8 Appendix Alarms 20 Alarms Overview 20 Absolute Mode 21 Incremental Mode 22 Probe Out of Range SMS Alarms in Absolute Mode 22 Probe Out of Ran...

Страница 5: ...itu instruments Software can be installed from www in situ com software If you did not purchase a SIM card and data plan from In Situ you will need these additional items l SIM subscriber identity mod...

Страница 6: ...tion Therefore the example model number means the following C3S 3G B 5T Cube 300S solar 3G non vented 5 Twist lock connections Serial Number The unit serial number is printed on the product label affi...

Страница 7: ...ata Loggers RDO PRO X Probe Rugged BaroTROLL Data Logger Rugged TROLL 200 Data Logger TROLL 9500 Multiparameter Instrument Communication Antenna GSM quad band 850 900 1800 1900 MHz GPRS SMS email FTP...

Страница 8: ...s or No to save these settings as the default for Win Situ 5 You must change Win Situ Software communication settings to match the device address and instrument communication settings next time you co...

Страница 9: ...figuration software If you are using a 3rd party data plan you will need to install the SIM card prior to setting up the Cube with the configuration software See SIM Card on page 19 Opening the Unit 1...

Страница 10: ...to the Cube 2 Click Probe and set point configuration 3 Click the Connected probes tab 4 Select the appropriate probe names from the drop down menus and enter the correct device addresses as set in W...

Страница 11: ...l information on alarms See Alarms Overview on page 20 6 Click Write probes and set points 7 Close the window Set Level Reference 1 Click Functional mode and test 2 Click Probes real time reading 3 Cl...

Страница 12: ...r EMnify SIM cards em If you are using a third party cellular service provider you must contact them for your APN 4 If your cellular service provider requires a user name and password enter those in t...

Страница 13: ...SMS message is generated every time 6 Enter the number of consecutive times a parameter in Incremental alarm mode can exceed its threshold before an SMS message is generated A value of 1 means an SMS...

Страница 14: ...e Immediate reading probes button Ensure all values are appropriate for the current conditions of the instruments If the readings are all zeros there is a connection issue with your instruments See Ch...

Страница 15: ...ion parameters and options 2 Click the Options tab l For a digital or pulse input enter a Parameter name value of a parameter and parameter units under Input 1 l For an analog input enter a Parameter...

Страница 16: ...ou are deploying the Cube using the Wall Mounting Adapter PN 0062330 use appropriate hardware to attach the Cube to the adapter using the pre drilled holes If you are deploying the Cube using a differ...

Страница 17: ...7 Conduct an FTP or email test See Restart Device and Test Communications on page 14 8 Check probe readings 1 Click Functional mode and test 2 Click Probes real time reading 3 Click theImmediate read...

Страница 18: ...the APN Verify that the SIM has been enabled Error 813 817 Verify the username and password for the APN Error 831 Verify the directory exists that you have permission to access Error 832 Verify the P...

Страница 19: ...ider if your application requires a static IP address when purchasing the SIM card Once a SIM card is obtained install it in the Cube as shown below The SIM card slot is located between the two circui...

Страница 20: ...Support states otherwise 6 Carefully pack your product in its original shipping box if possible 7 Mark the RMA number clearly on the outside of the box 8 Send the package shipping prepaid to In Situ...

Страница 21: ...a measurement value is less than the minimum threshold value or greater than the maximum threshold value Minimum Level Value Maximum Level Value Measurement Value Result 1 15 16 ALARM 1 15 1 OK 1 15...

Страница 22: ...00 10 130 110 20 ALARM 6000 10 130 125 5 OK 10 8000 150 165 15 ALARM 10 8000 1200 0 1200 OK Tips l Minimum Threshold values should be negative otherwise a decreasing parameter will always generate an...

Страница 23: ...ding the alarm threshold reading no 8 9 10 A second SMS alarm is sent after the sixth consecutive measurement reading no 11 12 13 While another three consecutive measurements are above the alarm thres...

Страница 24: ...nt A An SMS alarm is sent on the third consecutive set of measurements where the delta exceeds the alarm threshold reading no 6 7 7 8 8 9 Incident B No SMS alarm is sent Only one consecutive set of me...

Отзывы: