I-Control manual
page 9
Flush time
(00:10 to 15:00 minutes:seconds)
This is the activated flushing time of each group.
Note:
The installer can adjust the flushing time for each flushing variable (time, temperature, pollution). For
example, the flushing time for pollution can be longer than another flushing variable.
New round
(off, on)
Switch this function ON when starting a new round in the house. The I-Control will reset all registrations and reset
the day counter to 1. In this way the curves restart from day one. When this is done by the I-Control, this function
will automatically go to OFF.
Wait time
(00:00 to 23:59 hours)
The I-Control indicates the waiting time before it is possible to flush again. See next function for additional
information.
Delay flush
(00:01 to 23:59 hours)
When a flush has taken place, even if there are flushes programmed, during a set time there will be no flushing.
This prevents unnecessary flushing, such as flushing on a basis of temperature followed by flushing on a time basis.
Time control
Select this menu by pressing the
key in the main screen. Select “Time control” and press the
key.
This menu displays the flush settings on a time basis. The I-Control will automatically start flushing at the set times.
Note:
This menu can also be reached directly from the main screen by pressing the shortcut ‘9/TIME’ .
Start time 1
(00:00 to 23:59 hours)
At a set time the I-Control starts flushing. If you do not wish to make use of a set start time, set the timer to 00:00
hours. The start time will then be ignored.
Note:
When the I-Control is still in the waiting time after the last
flushing, a start time will be skipped over.
Rep. day st.1
(1 to 14 days)
If you do not wish the flushing cycle to be carried out at a set time every day, the number of days the flushing will
be done is set here. With function 1, the flushing cycle will be carried out at a set time every day. With function 2,
the start time is every 2 days, etc. The start settings 2 to 4 can be set the same way.
Temperature control
Select this menu by pressing the
key in the main screen. Select “Temperature control” and press the
key. The functions in this menu concern temperature regulated flushing.
Note:
If the temperature control has been switched off by the installer, this menu will not be displayed.
Note:
This menu can also be reached directly from the main summary screen by pressing the shortcut ‘7/TEMP’ .
Water temp.
(-70 to +130
˚
C)
This is the actual temperature measured by the sensor located in the drinking water circuit. If this temperature
becomes too high, temperature controlled flushing will take place.
Supply temp.
(-70 to +130
˚
C)
The I-Control displays the current temperature of the supply circuit. If so desired, automatic temperature
controlled flushing can start when the difference between the temperature in the drinking water circuit and the
supply circuit is too high.
Note:
If
no temperature sensor has been installed in the supply circuit, this function will
not be displayed.
Max.water T.
(0 to 50
˚
C)
If the temperature in the drinking water circuit rises above the set temperature, flushing will start automatically.