Chapter 4 Software index
4-35
Parameter b90 timing and operation diagram
Note: If b91 = 001, reverse command is disabled.
b91 Reverse run
000: Reverse enable
001: Reverse disable
A00 = 000 and b91 = 001, b88 (motor direction) disabled, the
iDrive
is set to forward operation.
A00 = 001 or 002, and b91 = 001, reverse command is disable.
b92 Stopping method
000: Decelerate to stop
001: Free run (Coast) to stop
1.) b92 = 000: after receiving stop command, the motor will decelerate (ramp) to stop according
to setting of A05.
2.) b92 = 001: after receiving stop command, the motor will free-run (coast) to stop.
b93 Status monitoring display
000: Disable
001: Enable.
b93 = 001 display shows Output Frequency, Motor Current, Output Voltage, DC Link Voltage,
or PID feedback.
b94 Copy module
000: Copy module Disabled
001: Copy to module from
iDrive
(Read)
002: Copy to
iDrive
from module (Write)
003: Read / write check (Compare parameters).
Note: Parameter copy facility is applicable only to
iDrives
with the same voltage and kW capacity.
b90 =2
Three wire
control
b90 =0
Run/Stop
/Reverse
b90 =1
Run/Reverse
/Stop
ON
ON
ON