STZSkW ed 12/07
ZEUS Superior kW
Technical Documentation
Technical Documentation
ERROR 31
Loss of Remote Control communication
31
The Remote Control is connected correctly.
N.B.: only remote controls supplied by Immergas can be used (CAR
or SuperCAR).
No
Check the connection between the circuit board (clamps 42-43) and
remote control (IN+ e IN-) performed respecting polarity and using a
dedicated line in order to prevent interference;
Yes
Replace the remote control. If the anomaly should persist, replace the control board.
ERROR 37
Low power supply voltage
37
The power supply voltage of the boiler exceeds 190 VAC.
No
Restore the correct electric power supply of the appliance (230 VAC
±10%).
Yes
The electric power supply connection cables and relative external
fuses are integral.
No
Restore the electric connection/replace the cables/external fuses.
Yes
Replace the circuit board.