1.1 INSTALLATION 

RECOMMENDATIONS.

Only professionally qualified heating/plumbing 

technicians are authorised to install Immergas 

gas appliances.
Individual and cascade installation Victrix Pro 1I 

boilers can be installed outdoors or in a suitable 

plant room.

The installation must comply with all laws and 

standards in force.
The place of installation of the appliance and 

relative Immergas accessories must have suitable 

features (technical and structural) such to allow 

(always in safety, efficiency and comfortable 

conditions):

-  installation (according to the provisions of the 

technical legislation and technical regulations);

-  maintenance operations (including scheduled, 

periodic, routine and special maintenance);

- removal (to outdoors in the place for 

loading and transporting the appliances 

and components) as well as their eventual 

replacement with appliances and/or equivalent 

components.

Attention:

 these boilers must be used to heat 

rooms and the like; they are for heating water 

to a temperature lower that boiling point at 

atmospheric pressure. Therefore, they must be 

connected to a heating system that is suitable for 

their performance and their power.
Before installing the appliance, ensure that it is 

delivered in perfect condition; if in doubt, contact 

the supplier immediately.

Packaging materials (staples, nails, plastic bags, 

polystyrene foam, etc.) constitute a potential 

hazard and must be kept out of the reach of 

children.

Keep all flammable objects away from the 

appliance (paper, rags, plastic, polystyrene, etc.).

In the event of malfunctions, faults or incorrect 

operation, turn the appliance off and contact a 

qualified company (e.g. the Immergas Technical 

After-Sales Centre, which has specifically trained 

staff and original spare parts)

Do not attempt to modify or repair the appliance 

alone.

Failure to comply with the above implies personal 

responsibility and invalidates the warranty.

• Installation regulations: these boilers are not 

in any way designed for installation on bases 

or floors (Fig. 1-1), but exclusively for wall 

installation. The wall surface must be smooth, 

without any protrusions or recesses enabling 

access to the rear part. Wall mounting of the 

boiler must guarantee stable and efficient 

support for the boiler. 

The plugs (standard 

supply) are to be used only in conjunction 

with the mounting brackets or fixing template 

to fix the appliance to the wall;

 they only 

ensure adequate support if inserted correctly 

(according to technical standards) in walls 

made of solid or semi-hollow brick or block. 

In the case of walls made from hollow brick or 

block, partitions with limited static properties, 

or in any case walls other than those indicated, 

a static test must be carried out to ensure 

adequate support. The boilers must be installed 

in a way to prevent collisions and tampering.

N.B.: the hex head screws supplied in the 

blister pack are to be used exclusively to fix the 

mounting bracket to the wall.

1.2  POSITION OF THE APPLIANCES.

The boilers can be installed:

- outdoors;
- in outdoor environments, also adjoining the 

building served, located in uncovered space, as 

long as structurally separated and without walls 

in common, or situated on the flat covering of 

the building served, always without walls in 

common;

- in building also destined for other use or in 

places inserted in the volume of the building 

served.

These rooms must be intended exclusively to 

house CH systems and must have characteristics 

that comply with legislation in force.

Attention:

 the installation of appliances powered 

with gas with a greater density than 0.8 (L.P.G.) 

is only allowed in places out of the ground, 

also communicating with places that are on the 

ground. In both cases the walkway must not have 

hollows or depressions such to create gas pockets 

that determine dangerous conditions.

Height of the installation room.

Installation of individual appliance

: the room 

must have a minimum ceiling height of 2 m.

Installation of multiple appliances in cascade (2 

÷ 5 Victrix Pro 1I):

 considering the size of the 

boiler, the flue manifold (which must be installed 

on a 3% gradient) and the hydraulic manifolds, 

the room must have a minimum ceiling height 

of 2.3 m.
The aforementioned heights allow for correct 

installation of the appliances and observe the 

technical regulations in force.

Position of the appliances in the room.

Individual appliance

: the distances between 

any external point of the boiler and the vertical 

and horizontal walls of the room must allow 

accessibility to the regulation, safety and control 

elements for routine maintenance.

Multiple appliances, not interconnected, but 

installed in the same room

: the minimum distance 

to maintain between several boilers installed 

on the same wall must be 200 mm, in order to 

allow accessibility to the regulation, safety and 

control elements and routine maintenance of all 

appliances installed.

Cascade installation (2 ÷ 5 Victrix Pro 1I)

: The 

instructions for correct cascade installation are 

provided in the respective documents or on the 

www.immergas.com website in the high power 

section.

YES

NO

Содержание Victrix Pro 100 1 I

Страница 1: ...VICTRIX PRO 80 100 120 1 I 1 036116ENG IE Instruction and warning book...

Страница 2: ......

Страница 3: ...ransfer or succession of ownership It must be stored with care and consulted carefully as all of the warnings provide important safety indications for installation use and maintenance stages This inst...

Страница 4: ...DEX 2 Use and maintenance instructions 22 2 1 Cleaning and maintenance 22 2 2 Aeration and Ventilation of the installation rooms 22 2 3 General warnings 22 2 4 Control panel 23 2 5 Using the boiler 23...

Страница 5: ...adequate support if inserted correctly according to technical standards in walls made of solid or semi hollow brick or block In the case of walls made from hollow brick or block partitions with limite...

Страница 6: ...tion rating and can also be installed outdoors without additional protections Attention all optional kits that can be potentially connected to the boiler must be protected on the basis of their electr...

Страница 7: ...f the fuel Storage tanks in case of supply from LPG depot New LPG storage tanks may contain residual inert gases nitrogen that degrade the mixture delivered to the appliance causing problems with boil...

Страница 8: ...on Immergas S p A declines any respon sibility for damage or physical injury caused by failure to connect the boiler to an efficient earth system or failure to comply with the reference standards Also...

Страница 9: ...if external probe is present The zone manager is powered directly by the cascade heat adjuster via 2 wires Cascadeandzoneregulatorelectricconnection or On off chrono thermostat Optional Any thermosta...

Страница 10: ...sealed chamber and fan assisted The boiler leaves the factory with B23 configuration to change the configuration of the boiler to type C sealed chamber and fan assisted disassemble the 80 adapter the...

Страница 11: ...t 1 3 m Terminal complete with vertical ex haust 80 Exhaust m 3 DUCT TYPE Equivalent length in m of concentric pipe 80 125 Concentric pipe 80 125 m 1 1 0 m Concentric bend 90 80 125 1 9 m Concentric b...

Страница 12: ...rder to ensure sufficient space to carry out the tests required by law upon commissioning External grid The intake exhaust terminal if properly installed is pleasant to look at on the outside of the b...

Страница 13: ...the lid using the previously disassembled sheet steel plate 3 Installation of the fake aluminium tile replace the tiles with the aluminium sheet 5 shaping it to ensure that rainwater runs off Position...

Страница 14: ...with this configuration can be extended up to a max measurement of 28 0 m with Victrix Pro 80 1 I 14 0 m with Victrix Pro 100 1 I and 8 5 m with Victrix Pro 120 1 I including the terminal Using the 8...

Страница 15: ...plate has been fitted This will ensure sealing and joining of the elements making up the kit Horizontal kit 80 with exhaust in flue Kit assembly Fig 1 21 install the 80 bend 1 with the male side smoo...

Страница 16: ...s in particular the declaration of conformity must be compiled at the end of work and on commissioning of the ducted system The instructions in the project or technical report must likewise be followe...

Страница 17: ...is recommended to use the pump at maximum speed The circulation pump is already fitted with a capacitor Pump release If after a prolonged period of inactivity the circulation pump is blocked unscrew t...

Страница 18: ...CHNICIAN Head available to the system Head kPa Head kPa Victrix PRO 100 1I Victrix PRO 120 1I Key A Head available to the system at maximum speed B Head available to the system at second speed Head m...

Страница 19: ...9 Condensing module air vent valve 10 Flue probe 11 Condensation module 12 Fumes hood 13 Air intake pipe 14 Igniter 15 16 Heat exchanger safety thermal fuse 17 Ignition electrode 18 Detection electro...

Страница 20: ...d block circuit breaker switches andofthethermometer notsuppliedasstandard with the boiler must be set up as described in the installation instructions in compliance with theprovisionsofthe R collecti...

Страница 21: ...tral heating circuit pump CMI 1 13 Zone 2 central heating circuit pump CMI 2 14 Zone 3 direct circuit pump CD 15 Storage tank unit feeding pump 16 Zone 1 safety thermostat CMI 1 17 Zone 2 safety therm...

Страница 22: ...down of the boiler is required proceed as follows a drain the heating system if anti freeze is not used b shut off all electrical water and gas supplies N B in the case of maintenance interventions on...

Страница 23: ...bol 23 Resettable presence of anomalies 24 Pump running 25 Summer mode 2 5 USING THE BOILER Before ignition make sure that the system is full of water checking that the manometer 5 indicates a base va...

Страница 24: ...t If a certain amount of time lapses without saving the value the boiler will exit setting mode and maintain the previous setting 2 4 2 5 Stand by mode by pressing buttons A and C at the same time it...

Страница 25: ...cts an anomalous difference between the NTC probe flow and return temperatures The error may be caused by a failure in one of the two probes Press the Reset button 1 0A16 Poor thermal flow NTC probe c...

Страница 26: ...urn NTC probe temperature detection incorrect in stand by With the boiler in stand by the board detects an anomalous difference between the NTC probe flow and return temperatures The error may be caus...

Страница 27: ...to the heating system water In systems that are drained frequently filling must be carried out with suitably treated water to eliminate hardness that can cause lime scale 2 12 CASE CLEANING Use damp...

Страница 28: ...ucts into the room even during function ing of fans check that the intake and or exhaust terminals are not blocked ensure activation of all adjustment devices seal the gas flow rate regulation devices...

Страница 29: ...not be restored in series with the electric power supply of the gas valve E4 Safety thermostat E13 Safety thermofuse G2 Igniter M1 Boiler circulator pump M20 Fan M30 Three way valve optional S1 Main s...

Страница 30: ...radiator valves are not closed and also the functionality of the pump Also check the integrity of the thermofuse and if it has been triggered it will be necessary to check the integrity of the module...

Страница 31: ...ion with a storage tank and a separate thermostat this defines the flow temperature during DHW operation 35 90 C 80 C P23 Modulazione sanitario DHW modulation Summed with the Set San P16 parameter thi...

Страница 32: ...s After Sales Assistance 3 7 HEAT OUTPUT The boiler heat output is correlated to the length of the air intake and flue exhaust pipes This de creases slightly with the increase of pipe length 3 8 ADJUS...

Страница 33: ...deposits are detected in the combustion chamber one must remove them and clean the exchanger coils using nylon or sorghum brushes it is forbidden to use brushes made of metal or other materials that...

Страница 34: ...to de tach it from the central hooks and then slide it downwards take the two clamping screws out 4 from the control panel with their rings 5 press the two side hooks 7 and tilt the control panel 6 re...

Страница 35: ...35 3 10 1 6 8 9 9 12 12 10 11 13 13 13 13 A A Rif A 7 7 INSTALLER USER MAINTENANCE TECHNICIAN Ref A...

Страница 36: ...03 5580 61 0 52460 6 63 5550 4 87 5420 59 0 50740 6 42 5390 4 71 5250 57 0 49020 6 20 5230 4 55 5090 55 0 47300 5 98 5070 4 39 4930 53 0 45580 5 76 4910 4 23 4770 51 0 43860 5 55 4750 4 07 4610 49 0 4...

Страница 37: ...40 6 68 5970 81 0 69660 8 78 5910 6 44 5760 78 0 67080 8 45 5680 6 20 5550 75 0 64500 8 12 5460 5 96 5340 72 0 61920 7 79 5240 5 72 5130 69 0 59340 7 47 5030 5 48 4930 66 0 56760 7 14 4810 5 24 4720 6...

Страница 38: ...63 0 54180 6 83 4000 5 01 3900 60 0 51600 6 51 3830 4 78 3730 57 0 49020 6 18 3660 4 54 3560 54 0 46440 5 86 3490 4 30 3390 51 0 43860 5 54 3320 4 06 3230 48 0 41280 5 21 3150 3 83 3060 45 0 38700 4 8...

Страница 39: ...mbar mm H2 O 20 204 37 377 Flue flow rate at nominal heat output kg h 146 148 Flue flow rate at min heat output kg h 16 16 CO2 at Q Nom Min 9 45 8 90 10 60 10 00 CO with 0 O2 at Nom Min Q Nom Min ppm...

Страница 40: ...7 6 107 2 107 5 Heat loss at casing with burner On Off 80 60 C 0 34 0 80 0 41 0 60 0 28 0 70 Heat loss at flue with burner On Off 80 60 C 0 01 2 2 0 01 1 9 0 01 2 0 Central heating circuit max operati...

Страница 41: ...Md Model code Sr N Serial Number CHK Check Cod PIN PIN code Type appliance configuration ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn m...

Страница 42: ......

Страница 43: ......

Страница 44: ...mmergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 036116ENG rev ST 000450 001 09...

Отзывы: