3.19 TECHNICAL DATA.
- Flue temperature values refer to an air inlet
temperature of 15°C and flow temperature of
50°C.
- The maximum sound level emitted during
boiler operation is < 55dBA. The sound level
value is referred to semianechoic chamber tests
with boiler operating at max. heat output, with
extension of flue gas exhaust system according
to product standards.
Victrix Pro 80 1 I
Victrix Pro 100 1 I Victrix Pro 120 1 I
Nominal heat input
kW (kcal/h)
75,3 (64722)
92,3 (79385)
114,1 (98109)
Minimum heat input
kW (kcal/h)
7,6 (6532)
9,8 (8401)
11,4 (9813)
Nominal heat output (useful)
kW (kcal/h)
73,0 (62780)
90,0 (77400)
111,0 ( 95460)
Minimum heat output (useful)
kW (kcal/h)
7,2 (6192)
9,4 (8084)
11,0 (9460)
Effective thermal efficiency 80/60 Nom./Min.
%
97,0 / 94,8
97,5 / 96,2
97,3 / 96,4
Effective thermal efficiency 50/30 Nom./Min.
%
106,6 / 106,9
107,0 / 107,4
106,7 / 107,2
Effective thermal efficiency 40/30 Nom./Min.
%
107,3 / 107,2
107,4 / 107,6
107,2 / 107,5
Heat loss at casing with burner On/Off (80-60°C)
%
0,34 / 0,80
0,41 / 0,60
0,28 / 0,70
Heat loss at flue with burner On/Off (80-60°C)
%
0,01 / 2,2
0,01 / 1,9
0,01 / 2,0
Central heating circuit max. operating pressure
bar
4,4
4,4
4,4
Central heating circuit max. operating temperature
°C
90
90
90
Adjustable central heating temperature
°C
20 - 85
20 - 85
20 - 85
Head available with 1000 l/h flow rate
kPa (m H
2
O)
69,70 (7,11)
90,7 (9,24)
91,2 (9,30)
Weight of full boiler
kg
85,0
106,0
114,2
Weight of empty boiler
kg
81,0
95,9
102,5
Boiler water content
l
4,0
10,1
11,7
Electrical connection
V/Hz
230/50
230/50
230/50
Nominal absorption
A
1,4
1,7
2,1
Installed electric output
W
290
370
440
Pump consumption
W
168
236
236
Fan power consumption
W
100
102
160
Equipment electrical system protection
-
IPX5D
IPX5D
IPX5D
Max. operating room temperature
°C
+50
+50
+50
Min. operating room temperature
°C
-5
-5
-5
Min. operating room temperature with anti-freeze kit
(Optional)
°C
-15
-15
-15
Flue gas max. temperature
°C
75
75
75
NO
X
class
-
5
5
5
Weighted NO
X
mg/kWh
25,0
20,0
33,0
Weighted CO
mg/kWh
16,0
12,0
18,0
Type of appliance
C13 / C33 / C63 / B23p / B33 / B53p
Category
II2H3 P