Programming menu

Menu item

Description

Adjustment range

Default value

P08 Pot risc max disponibile 

(Available max heat out) This defines the maximum power percentage to be used during the set CH phase 

P09 ÷ 100%

100%

P09 Pot risc min disponibile 

(Available max heat out) This defines the minimum power percentage to be used during the set CH phase 

0 ÷ P08%

0%

P10 -

Not used

14 l / minutes

P11

Anti umidità elettrodi 

(Electrodes anti-

humidity)

This defines fan speed and operating mode, to avoid humidity inside the condensing module, which 

could otherwise cause the electrodes to malfunction (0 = disabled function, recommended value = 

40)

P26 

÷

120 RPM x 50

0

P12 -

Not used

20

P13 Boiler power

This defines the boiler power (this parameter has no effect on boiler operation)

÷

 255 kW

80 kW = 75

100 kW = 90

120 kW = 115

P14 External probe curve

This is used to select the external probe operating curve (optional) (0 = disabled probe)

÷

 10

0

P15 External probe offset

This defines the CH offset in relation to the selected external probe curve

20 

÷

 70 °C

30 °C

P16 Set San (DHW set)

This defines the DHW temperature

20 ÷ 65 °C

65 °C

P17 -

Not used

P18 Isteresi sanitario (DHW 

hysteresis)

This defines the DHW power-on hysteresis during CH

2 ÷ 10 °C

5 °C

P19

Post circolazione  

sanitario (DHW post-

circulation)

This is the post circulation time during DHW, once DHW production is finished

÷

 180 seconds

60 seconds

P20

Pot san max disponibile 

(Available max DHW 

pow)

This defines the maximum power percentage to be used during the set DHW phase 

P21 

÷

 100 %

50 %

P21

Pot san min disponibile 

(Available max DHW 

pow)

This defines the minimum power percentage to be used during the set DHW phase 

÷

 P20 %

0 %

P22 DHW flow temperature 

with thermostat

In combination with a storage tank and a separate thermostat, this defines the flow temperature 

during DHW operation

35 

÷

 90 °C

80 °C

P23 Modulazione sanitario 

(DHW modulation)

Summed with the “Set San” (P16) parameter, this defines the flow temperature set that the boiler has 

to modulate the power on during DHW

÷

 30 °C

15 °C

P24 Incremento off sanitario 

(DHW off increment)

This defines the time that the boiler allows the burner to switch off during DHW, by an increment of 

5 °C on top of the flow temperature

÷

 255 seconds

60 seconds

P25

Velocità Max 

ventilatore (Max fan 

Speed)

This defines the max fan speed and therefore the maximum relative boiler operating power

P26 

÷

 255 RPM x 50

80 kW Met. 130

80 kW LPG 128

100 kW Met. 137

100 kW LPG 128

120 kW Met. 140

120 kW LPG 138

P26

Velocità Min 

ventilatore (Min fan 

Speed)

This defines the min fan speed and therefore the minimum relative boiler operating power

÷

 P25 RPM x 50

80 kW Met. 24

80 kW LPG 22

100 kW Met. 24

100 kW LPG 23

120 kW Met. 24

120 kW LPG 23

P27 Velocità min circolatore 

(Min pump speed)

Not used on this boiler model

- - -

30 %

P28

Velocità circolatore in 

accensione bruciatore 

(Pump speed during 

burner ignition)

Not used on this boiler model

- - -

40 %

P29 Configurazione sanitario 

(DHW configuration)

This is used to select the DHW operating mode, choosing between NTC probe or on/off thermostat

1 = NTC probe

17 = on/off thermostat

1

P30

Velocità in accensione 

ventilatore (Speed 

during fan power-on)

 This defines the fan speed during burner ignition

Attention:

 do not change this parameter

÷

 114 RPM x 50

(range limited by parameters 

P25 and P26)

46

P31 Unit of measurement

This defines the unit of measure on the display, whether metric or Imperial

0 ÷ 127 = °C - kW

128 ÷ 256 = °F - kBTu/h

0

P32 -

Not used

0

P33 -

Not used

5

P34 -

Not used

15

P35 -

Not used

60

P36 Temperature adjustment 

calculation time

This defines the time required to calculate the boiler temperature

Attention:

 do not change this parameter

÷

 10 seconds

3 seconds

Содержание Victrix Pro 100 1 I

Страница 1: ...VICTRIX PRO 80 100 120 1 I 1 036116ENG IE Instruction and warning book...

Страница 2: ......

Страница 3: ...ransfer or succession of ownership It must be stored with care and consulted carefully as all of the warnings provide important safety indications for installation use and maintenance stages This inst...

Страница 4: ...DEX 2 Use and maintenance instructions 22 2 1 Cleaning and maintenance 22 2 2 Aeration and Ventilation of the installation rooms 22 2 3 General warnings 22 2 4 Control panel 23 2 5 Using the boiler 23...

Страница 5: ...adequate support if inserted correctly according to technical standards in walls made of solid or semi hollow brick or block In the case of walls made from hollow brick or block partitions with limite...

Страница 6: ...tion rating and can also be installed outdoors without additional protections Attention all optional kits that can be potentially connected to the boiler must be protected on the basis of their electr...

Страница 7: ...f the fuel Storage tanks in case of supply from LPG depot New LPG storage tanks may contain residual inert gases nitrogen that degrade the mixture delivered to the appliance causing problems with boil...

Страница 8: ...on Immergas S p A declines any respon sibility for damage or physical injury caused by failure to connect the boiler to an efficient earth system or failure to comply with the reference standards Also...

Страница 9: ...if external probe is present The zone manager is powered directly by the cascade heat adjuster via 2 wires Cascadeandzoneregulatorelectricconnection or On off chrono thermostat Optional Any thermosta...

Страница 10: ...sealed chamber and fan assisted The boiler leaves the factory with B23 configuration to change the configuration of the boiler to type C sealed chamber and fan assisted disassemble the 80 adapter the...

Страница 11: ...t 1 3 m Terminal complete with vertical ex haust 80 Exhaust m 3 DUCT TYPE Equivalent length in m of concentric pipe 80 125 Concentric pipe 80 125 m 1 1 0 m Concentric bend 90 80 125 1 9 m Concentric b...

Страница 12: ...rder to ensure sufficient space to carry out the tests required by law upon commissioning External grid The intake exhaust terminal if properly installed is pleasant to look at on the outside of the b...

Страница 13: ...the lid using the previously disassembled sheet steel plate 3 Installation of the fake aluminium tile replace the tiles with the aluminium sheet 5 shaping it to ensure that rainwater runs off Position...

Страница 14: ...with this configuration can be extended up to a max measurement of 28 0 m with Victrix Pro 80 1 I 14 0 m with Victrix Pro 100 1 I and 8 5 m with Victrix Pro 120 1 I including the terminal Using the 8...

Страница 15: ...plate has been fitted This will ensure sealing and joining of the elements making up the kit Horizontal kit 80 with exhaust in flue Kit assembly Fig 1 21 install the 80 bend 1 with the male side smoo...

Страница 16: ...s in particular the declaration of conformity must be compiled at the end of work and on commissioning of the ducted system The instructions in the project or technical report must likewise be followe...

Страница 17: ...is recommended to use the pump at maximum speed The circulation pump is already fitted with a capacitor Pump release If after a prolonged period of inactivity the circulation pump is blocked unscrew t...

Страница 18: ...CHNICIAN Head available to the system Head kPa Head kPa Victrix PRO 100 1I Victrix PRO 120 1I Key A Head available to the system at maximum speed B Head available to the system at second speed Head m...

Страница 19: ...9 Condensing module air vent valve 10 Flue probe 11 Condensation module 12 Fumes hood 13 Air intake pipe 14 Igniter 15 16 Heat exchanger safety thermal fuse 17 Ignition electrode 18 Detection electro...

Страница 20: ...d block circuit breaker switches andofthethermometer notsuppliedasstandard with the boiler must be set up as described in the installation instructions in compliance with theprovisionsofthe R collecti...

Страница 21: ...tral heating circuit pump CMI 1 13 Zone 2 central heating circuit pump CMI 2 14 Zone 3 direct circuit pump CD 15 Storage tank unit feeding pump 16 Zone 1 safety thermostat CMI 1 17 Zone 2 safety therm...

Страница 22: ...down of the boiler is required proceed as follows a drain the heating system if anti freeze is not used b shut off all electrical water and gas supplies N B in the case of maintenance interventions on...

Страница 23: ...bol 23 Resettable presence of anomalies 24 Pump running 25 Summer mode 2 5 USING THE BOILER Before ignition make sure that the system is full of water checking that the manometer 5 indicates a base va...

Страница 24: ...t If a certain amount of time lapses without saving the value the boiler will exit setting mode and maintain the previous setting 2 4 2 5 Stand by mode by pressing buttons A and C at the same time it...

Страница 25: ...cts an anomalous difference between the NTC probe flow and return temperatures The error may be caused by a failure in one of the two probes Press the Reset button 1 0A16 Poor thermal flow NTC probe c...

Страница 26: ...urn NTC probe temperature detection incorrect in stand by With the boiler in stand by the board detects an anomalous difference between the NTC probe flow and return temperatures The error may be caus...

Страница 27: ...to the heating system water In systems that are drained frequently filling must be carried out with suitably treated water to eliminate hardness that can cause lime scale 2 12 CASE CLEANING Use damp...

Страница 28: ...ucts into the room even during function ing of fans check that the intake and or exhaust terminals are not blocked ensure activation of all adjustment devices seal the gas flow rate regulation devices...

Страница 29: ...not be restored in series with the electric power supply of the gas valve E4 Safety thermostat E13 Safety thermofuse G2 Igniter M1 Boiler circulator pump M20 Fan M30 Three way valve optional S1 Main s...

Страница 30: ...radiator valves are not closed and also the functionality of the pump Also check the integrity of the thermofuse and if it has been triggered it will be necessary to check the integrity of the module...

Страница 31: ...ion with a storage tank and a separate thermostat this defines the flow temperature during DHW operation 35 90 C 80 C P23 Modulazione sanitario DHW modulation Summed with the Set San P16 parameter thi...

Страница 32: ...s After Sales Assistance 3 7 HEAT OUTPUT The boiler heat output is correlated to the length of the air intake and flue exhaust pipes This de creases slightly with the increase of pipe length 3 8 ADJUS...

Страница 33: ...deposits are detected in the combustion chamber one must remove them and clean the exchanger coils using nylon or sorghum brushes it is forbidden to use brushes made of metal or other materials that...

Страница 34: ...to de tach it from the central hooks and then slide it downwards take the two clamping screws out 4 from the control panel with their rings 5 press the two side hooks 7 and tilt the control panel 6 re...

Страница 35: ...35 3 10 1 6 8 9 9 12 12 10 11 13 13 13 13 A A Rif A 7 7 INSTALLER USER MAINTENANCE TECHNICIAN Ref A...

Страница 36: ...03 5580 61 0 52460 6 63 5550 4 87 5420 59 0 50740 6 42 5390 4 71 5250 57 0 49020 6 20 5230 4 55 5090 55 0 47300 5 98 5070 4 39 4930 53 0 45580 5 76 4910 4 23 4770 51 0 43860 5 55 4750 4 07 4610 49 0 4...

Страница 37: ...40 6 68 5970 81 0 69660 8 78 5910 6 44 5760 78 0 67080 8 45 5680 6 20 5550 75 0 64500 8 12 5460 5 96 5340 72 0 61920 7 79 5240 5 72 5130 69 0 59340 7 47 5030 5 48 4930 66 0 56760 7 14 4810 5 24 4720 6...

Страница 38: ...63 0 54180 6 83 4000 5 01 3900 60 0 51600 6 51 3830 4 78 3730 57 0 49020 6 18 3660 4 54 3560 54 0 46440 5 86 3490 4 30 3390 51 0 43860 5 54 3320 4 06 3230 48 0 41280 5 21 3150 3 83 3060 45 0 38700 4 8...

Страница 39: ...mbar mm H2 O 20 204 37 377 Flue flow rate at nominal heat output kg h 146 148 Flue flow rate at min heat output kg h 16 16 CO2 at Q Nom Min 9 45 8 90 10 60 10 00 CO with 0 O2 at Nom Min Q Nom Min ppm...

Страница 40: ...7 6 107 2 107 5 Heat loss at casing with burner On Off 80 60 C 0 34 0 80 0 41 0 60 0 28 0 70 Heat loss at flue with burner On Off 80 60 C 0 01 2 2 0 01 1 9 0 01 2 0 Central heating circuit max operati...

Страница 41: ...Md Model code Sr N Serial Number CHK Check Cod PIN PIN code Type appliance configuration ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn m...

Страница 42: ......

Страница 43: ......

Страница 44: ...mmergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 036116ENG rev ST 000450 001 09...

Отзывы: