44
STMaE4E and 07/11
MAIOR EOLO 4 E
Technical Documentation
Technical Documentation
The burner ignites.
No
The error 01 appears on the display
(wait for the P.C.B. to make 2 ignition cycles).
See error section 01 - b
No
The error 04 appears on the display
(wait for the P.C.B. to run 5 ignition cycle attempts).
See error section 04.
Yes
The burner stays on after the first
10 seconds.
No
The error 01 appears on the display
(wait for the P.C.B. to run 2 ignition cycles).
See error section 01 -c
Yes
The error 27 appears on the display Yes
See error section 27
The error 02 appears on the display Yes
See error section 02 - b
No
The boiler reaches
and maintains the
set central heating
temperature.
No
Check the Maximum
heating output and
adjust it to maximum
if necessary.
See section D
Yes
The central heating request is satisfied.
The boiler reaches and
maintains the set DHW
temperature.
No
See section D
No
Check that,
- the flow rate of domestic hot water is
not greater than the amount the boiler
is able to supply (see technical data,
output, flow rate, ∆T);
- the plate heat exchanger is clean and
replace it, if necessary.
Yes
The domestic hot water request is satisfied.