2.5 TROUBLESHOOTING.

The hydronic module signals any anomalies by 

flashing a code on the display (14) according to 

the following table.
Hydronic module error codes are preceded by 

the letter "E", while error codes referring to 

the condensing unit are preceded by the letter 

"A". For the latter, refer to the condensing unit 

booklet for the complete list of all the anomalies.
The CAR

V2

 displays error codes with only the 

last two digits (e.g. E184 = ERR 84).

Error 

Code

Anomaly signalled

Cause

Hydronic module status / Solution

E 2

Safety thermostat 

block (over-temper-

ature)

During normal operation, if a fault causes excessive overheating 

internally, the boiler goes into overheating block.

Press the Reset button (1)

E 5

Flow probe anomaly

The board detects an anomaly on the flow NTC probe.

The system does not start (1).

E 12

Storage tank probe 

anomaly

The board detects an anomaly on the storage tank probe

The hydronic module is unable to pro-

duce domestic hot water (1).

E 23

Return probe anomaly

The board detects an anomaly on the return NTC probe

The system does not start (1).

E 24

Push button control 

panel anomaly

The board detects an anomaly on the pushbutton panel.

If normal conditions are restored, the 

system restarts without having to be reset 

(1).

E 26

System flowmeter 

anomaly

The board detects an anomaly on the system flowmeter.
Return pump (optional) always working.

The system does not start (1).
Make sure the return pump (optional) only 

activates when requested.

E 27

Insufficient circulation

This happens when the hydronic module overheats due to poor water 

circulation in the primary circuit. The causes can be: 
-  low system circulation; check that no shut-off devices are closed on 

the central heating circuit and that the system is free of air (deaer-

ated);

- pump blocked; free the pump.

Press the Reset button (1).

E 31

Loss of communica-

tion with the CAR

V2

 

(zone 1)

This happens when an incompatible remote control is connected or 

when communication between the hydronic module and CAR

V2

 is lost.

Cut power to the hydronic module then 

power it back on. If the Remote Control is 

still not detected at restart, the system will 

switch to local operating mode, i.e. using 

the controls on the control panel. In this 

case the “Central Heating” (1) mode cannot 

be activated.

E 32

Low temperature zone 2 

probe anomaly

If the board detects an anomaly on the low temperature zone 2 probe, 

the system cannot work in the affected area.

(1)

E 37

Low power supply 

voltage

This occurs when the power supply voltage is lower than the allowed 

limits for correct system operation. 

If normal conditions are restored, the sys-

tem restarts without having to be reset (1)

46

Low temperature safety 

thermostat (optional)

During normal operation, if an anomaly causes excessive overheating 

of the flow temperature in the low temperature zone, the unit indicates 

the malfunction.

The unit does not meet the zone central 

heating requirement. (1)

E 50

External probe missing 

or faulty

In the event the external probe is not connected or is faulty, the 

anomaly is indicated. 

Check the external probe connection.
The system continues to operate with the 

external probe integrated in the condensing 

unit (1).

E 54

Central heating storage 

tank probe anomaly 

(optional)

The central heating storage tank has an out of range resistive value

Puffer mode is disabled. (1)

E 129

Zone 1 humidity probe 

anomaly

Anomaly on the zone 1 humidity probe (optional). Zone humidity 

cannot be checked.

In addition to the humidity, the dew point 

is not calculated for the zone (1) either

E 130

Zone 2 humidity probe 

anomaly

Anomaly on the zone 2 humidity probe (optional). Zone humidity 

cannot be checked.

In addition to the humidity, the dew point 

is not calculated for the zone (1) either

E177

DHW maximum time 

alarm

Domestic hot water production is not met within the pre-estab-

lished time

The system continues to operate with 

non-optimal performance (1)

E178

Anti-Legionella cycle 

not successful

The anti-Legionella cycle is run without success within the pre-es-

tablished time

(1)

E179

Liquid phase probe 

anomaly

The board detects an anomaly on the liquid phase NTC probe.

The system does not start (1).

(1) If the block or anomaly persists, contact an authorised company (e.g. Immergas Technical After-Sales Service).

Содержание MAGIS PRO ERP

Страница 1: ...MAGIS PRO ERP Mono phase hydronic module to pair with an outdoor condensing unit Instruction and recommendation booklet IE 1 039356ENG...

Страница 2: ......

Страница 3: ...be designed by qualified professionals within the dimensional limits established by the Law Installation and maintenance must be performed in compliance with the regulations in force according to the...

Страница 4: ...l 14 2 4 System use 15 2 5 Troubleshooting 16 2 6 Parameters and information menu 18 2 7 Switching off the hydronic module 19 2 8 Restoring central heating system pressure 19 2 9 System draining 19 2...

Страница 5: ...l spare parts Do not attempt to modify or repair the appliance alone Failuretocomplywiththeaboveimpliespersonal responsibility and invalidates the warranty Installation regulations this hydronic modul...

Страница 6: ...this liquid must be followed scrupulously regarding the percentage necessary with respect to the minimum temperature at which the system must be kept An aqueous solution must be made with potential po...

Страница 7: ...not to void the product war ranty before making unit connections carefully clean the heating system pipes radiators etc with special pickling or de scaling products to remove any deposits that could j...

Страница 8: ...tionscompart ment Fig 1 5 To carry out electrical connections all you have to do is open the connections compartment as follows Remove the front panel Fig 3 5b Remove the cover b fig 1 4 1 Loosen the...

Страница 9: ...s Comando Amico Remoto Remote Control V2 or On Off chrono thermostat electrical con nections Optional The operations described below must be performed after having removed the voltage from the applian...

Страница 10: ...in central heating mode with external probe Zone 2 mixed flow temperature in cooling mode with external probe Key Rxx Heat regulation menu parameter TE Outdoor temperature TM Flow temperature U01 Zon...

Страница 11: ...t the dehumidifier line has a minimum of 3 l kW dehumidifier hydraulic circuit connection 1 12 OPERATING LIMITS The system was designed to work in a specific range of temperatures and at a specific ma...

Страница 12: ...motor shaft using a screwdriver Take great care during this operation to avoid damage to the motor Total head available to the system Head kPa A B Head available with by pass closed B Head available w...

Страница 13: ...t Should it be necessary you can install an electrical resistance to supplement the central heating system this resistance can be installed directly inside the hydronic module 2 zone kit 1 direct and...

Страница 14: ...light etc the appliance power cable must not be re placed by the user in the event of damage to the cable switch off the appliance and contact exclusively qualified staff for replacement if the applia...

Страница 15: ...be considered as the hydronic module mount panel Attention if the hydronic module is switched off the CARV2 will display the connection error symbol ERR CM The CARV2 is still powered constantly so as...

Страница 16: ...power to the hydronic module then power it back on If the Remote Control is still not detected at restart the system will switch to local operating mode i e using the controls on the control panel In...

Страница 17: ...ing unit and its instructions booklet 1 E183 Condensing unit in test mode A signal notifies that the condensing unit is in test mode During this time room heating air condi tioning and domestic hot wa...

Страница 18: ...humidity 0 99 D 42 Zone 2 relative humidity 0 99 D 43 Zone 1 humidistat OFF ON D 44 Zone 2 humidistat OFF ON D 45 Dehumidifier zone 1 OFF ON D 46 Dehumidifier zone 2 OFF ON D 47 Zone 1 circulator pump...

Страница 19: ...the electric power supply completely empty the central heating circuit and the hydronic module domestic hot water circuit In systems that are drained frequently filling must be carried out with suitab...

Страница 20: ...l adjustment devices check the production of domestic hot water check sealing efficiency of water circuits Even if just one single safety check provides a negative result do not commission the system...

Страница 21: ...d M1 2 System circulator pump M10 1 Zone 1 circulator optional M10 2 Zone 2 circulator optional M31 2 Zone 2 mixing valve optional M52 Hot cold three way optional T1 Transformer Colour code key BK Bla...

Страница 22: ...8 Storage tank function unabling resistance R14 Configuration resistance S20 1 Zone 1 room thermostat optional S20 2 Zone 2 room thermostat optional S36 1 Zone 1 humidistat optional S36 2 Zone 2 humid...

Страница 23: ...in tap 4 Open the cap 1 and clean the filter 2 3 4 TROUBLESHOOTING N B maintenance interventions must be carried out by an authorised company e g Immergas After Sales Technical Assistance Service Nois...

Страница 24: ...until the Password menu appears Enter the password modify the numer ical values using the DHW regulation buttons 5 and confirm with the OK button 1 Once you have accessed programming you can scroll th...

Страница 25: ...nditioning For special systems e g zone systems with motorised valves etc it may be necessary to delay ignition 0 240 seconds step 10 sec 0 T 08 Display lighting Establishes the display lighting mode...

Страница 26: ...ines the maximum flow temperature in room central heating mode in the low temperature zone 35 55 35 R 09 Low temperature zone minimum central heating Defines the minimum flow temperature in room centr...

Страница 27: ...stem The function lasts for 18 hours and can be interrupted by pressing the ESC button and setting the function to OFF Activation of the function is signalled by the countdown shown on the indicator 1...

Страница 28: ...function is activated in two different ways each time the hydronic module is re powered by pressing the buttons at the same time 3 and 5 Fig 2 1 for 5 seconds with the hydronic module in stand by N B...

Страница 29: ...two screws a 2 Press the hooks inwards which block the lower grid b 3 remove the grid b Front panel Fig 3 5b 4 Open the protection door e1 pulling it towards you 5 Remove the cover caps c and loosen...

Страница 30: ...e control panel i 10 Tilt the control panel i towards you The control panel i can rotate until the support cord j is completely extended 11 If the left side needs to be removed unhook the support cord...

Страница 31: ...changer water inlet remains at 23 C 18 C outdoor air temperature 35 C Performance in compliance with EN 14511 Central heating mode status heat exchanger water inlet remains at 40 C 45 C outdoor air te...

Страница 32: ...154 201 Nominal heat output kW 7 80 5 50 6 00 Average temperature 47 55 Parameter Value Colder zones Average zones Hotter zones Annual energy con sumption for the central heating function QHE kWh year...

Страница 33: ...ure operating limit Pdh 4 2 kW Tj temperature operating limit COPd 2 03 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tbiv...

Страница 34: ...ture operating limit Pdh 5 5 kW Tj temperature operating limit COPd 2 36 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tbiv...

Страница 35: ...operating limit Pdh 4 6 kW Tj temperature operating limit COPd 3 31 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tbiv 4 C...

Страница 36: ...ture operating limit Pdh 4 6 kW Tj temperature operating limit COPd 1 73 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tbiv...

Страница 37: ...ature operating limit Pdh 4 3 kW Tj temperature operating limit COPd 1 49 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tbi...

Страница 38: ...operating limit Pdh 4 2 kW Tj temperature operating limit COPd 2 09 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tbiv 7 C...

Страница 39: ...5 10 5 70 5 50 Average temperature 47 55 Parameter Value Colder zones Average zones Hotter zones Annual energy con sumption for the central heating function QHE kWh year 11475 5469 2882 Room central...

Страница 40: ...re operating limit Pdh 5 5 kW Tj temperature operating limit COPd 1 93 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tbiv 2...

Страница 41: ...ture operating limit Pdh 5 9 kW Tj temperature operating limit COPd 1 97 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tbiv...

Страница 42: ...operating limit Pdh 6 5 kW Tj temperature operating limit COPd 3 20 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tbiv 1 C...

Страница 43: ...ure operating limit Pdh 6 0 kW Tj temperature operating limit COPd 1 75 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tbiv...

Страница 44: ...ature operating limit Pdh 4 0 kW Tj temperature operating limit COPd 0 98 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tbi...

Страница 45: ...operating limit Pdh 4 9 kW Tj temperature operating limit COPd 1 54 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tbiv 4 C...

Страница 46: ...W 9 00 10 00 8 80 Average temperature 47 55 Parameter Value Colder zones Average zones Hotter zones Annual energy con sumption for the heating function QHE kWh year 13274 7214 3765 Room central heatin...

Страница 47: ...ure operating limit Pdh 6 6 kW Tj temperature operating limit COPd 1 93 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tbiv...

Страница 48: ...rature operating limit Pdh 8 1 kW Tj temperature operating limit COPd 2 59 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tb...

Страница 49: ...e operating limit Pdh 8 4 kW Tj temperature operating limit COPd 3 01 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tbiv 7...

Страница 50: ...ature operating limit Pdh 6 9 kW Tj temperature operating limit COPd 1 75 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tbi...

Страница 51: ...rature operating limit Pdh 4 5 kW Tj temperature operating limit COPd 0 98 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tb...

Страница 52: ...e operating limit Pdh 6 6 kW Tj temperature operating limit COPd 1 54 for air water heat pumps Tj 15 C if TOL 20 C Pdh kW for air water heat pumps Tj 15 C if TOL 20 C COPd Bivalent temperature Tbiv 4...

Страница 53: ...pplementary boiler From boiler board Room central heating seasonal energy efficiency in colder and hotter climate conditions The energy efficiency of the set of products indicated in this sheet may no...

Страница 54: ...11 2013 in case of an assembly including a boiler to integrate with the heat pump In this case the heat pump must be considered as the main appliance of the assembly Fig 3 9 Parameter Magis Pro 5 ErP...

Страница 55: ...e of the products compared to the size and features of the building Room central heating seasonal energy efficiency of the assemble in av erage climate conditions Room central heating seasonal energy...

Страница 56: ...d 1 039356ENG rev ST 002317 000 01 16 Inglese per IRLANDA IE Followus Immergas Italia immergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 12...

Отзывы: