3.16 VARIABLE HEAT OUTPUT.
- Check the function of the electrode.
- Check the condition and integrity of the elec-
trical system and in particular:
- electrical power cables must be inside the
fairleads;
- there must be no traces of blackening or
burning.
Note:
in addition to yearly maintenance, one
must also check the thermal system, with
frequency and procedures that comply with the
indications of the technical regulations in force.
- Check sealing efficiency of gas circuit and the
internal system.
- Check the intervention of the device against no
gas ionisation flame control. Intervention time
must be less than 10 seconds.
- Visually check for water leaks or oxidation
from/on connections.
- Visually check that the water safety drain valve
is not blocked.
- Check that, after discharging system pressure
and bringing it to zero (read on boiler pressure
gauge), the expansion vessel load is at 1.0 bar.
- Check that the system static pressure (with
system cold and after refilling the system by
means of the filling valve) is between 1 and 1.2
bar.
- Check visually that the safety and control
devices have not been tampered with and/or
shorted, in particular:
- temperature safety thermostat;
- water pressure switch;
3.15 YEARLY APPLIANCE CHECK AND
MAINTENANCE.
The following checks and maintenance should
be performed at least once a year.
- Check that the system's water PH is between 7
and 8.5.
- Clean the flue side of the heat exchanger.
- Clean the main burner.
- Visually check the flue hood for deterioration
or corrosion.
- Check correct lighting and operation.
- Ensure correct calibration of the burner in
domestic water and heating phases.
- Check correct operation of control and
adjustment devices and in particular:
- intervention of main electrical switch positi-
oned outside of the boiler;
- system control thermostat intervention;
- domestic hot water control thermostat inter-
vention.
METHANE (G20)
BUTANE (G30)
PROPANE (G31)
HEAT
OUTPUT
HEAT
OUTPUT
D.H.W.
BURNER GAS
FLOW RATE
BURNER NOZZLES
PRESS.
BURNER GAS
FLOW RATE
BURNER NOZZLES
PRESS.
BURNER GAS
FLOW RATE
BURNER NOZZLES
PRESS.
(kW)
(kcal/h)
(m
3
/h)
(mbar)
(mm H
2
O)
(kg/h)
(mbar)
(mm H
2
O)
(kg/h)
(mbar)
(mm H
2
O)
23.0
19780
2.67
13.00
132.6
2.00
28.20
287.6
1.96
36.40
371.2
22.0
18920
2.56
11.84
120.8
1.91
25.89
264.0
1.88
33.23
338.9
21.0
18060
2.44
10.76
109.7
1.82
23.71
241.8
1.79
30.27
308.7
20.0
17200
2.33
9.75
99.4
1.74
21.66
220.9
1.71
27.50
280.4
19.0
16340
2.22
8.81
89.8
1.65
19.72
201.1
1.63
24.90
254.0
18.0
15480
2.11
7.93
80.9
1.57
17.88
182.3
1.55
22.47
229.2
17.0
14620
2.00
7.11
72.5
1.49
16.14
164.6
1.46
20.19
205.9
16.0
13760
1.89
6.34
64.7
1.41
14.50
147.8
1.39
18.06
184.2
15.0
12900
1.78
5.63
57.4
1.33
12.93
131.9
1.31
16.06
163.8
14.0
12040
1.67
4.97
50.6
1.25
11.45
116.8
1.23
14.20
144.8
13.0
11180
1.56
4.35
44.4
1.17
10.05
102.5
1.15
12.45
127.0
12.0
10320
1.45
3.78
38.6
1.09
8.72
88.9
1.07
10.83
110.5
11.0
9460
1.35
3.26
33.3
1.00
7.46
76.1
0.99
9.33
95.2
10.0
8600
HEAT.
+
D.H.W.
1.24
2.79
28.4
0.92
6.27
63.9
0.91
7.95
81.1
9.0
7740
1.12
2.36
24.0
0.84
5.15
52.5
0.83
6.68
68.1
8.0
6880
D.H.W.
1.01
1.97
20.1
0.76
4.09
41.8
0.74
5.53
56.4
7.2
6192
0.92
1.70
17.3
0.69
3.30
33.7
0.68
4.70
47.9