MAGIS HERCULES PRO 4-6-9
62
THE REPORTED DATA REFERS TO THE FOLLOWING CONDITIONS (in compliance with EN 14511):
ROOM
HEATING PHASE (°C)
COOLING PHASE (°C)
Water TEMP. (F/R)
(1)
- AIR (db/wb)
35/30 - 7/6
18/23 - 35 (bs)
Water TEMP. (F/R)
(2)
- AIR (db/wb)
45/40 - 7/6
7/12 - 35 (bs)
Water TEMP. (F/R)
(3)
- AIR (db/wb)
55/47 - 7/6
29
TECHNICAL DATA MAGIS HERCULES PRO 4 - 6 - 9
MHP
4 6 9
Central heating circuit
Power in CH mode with water set at 35 °C
(1)
kW 4.40 6.00 9.00
Power in CH mode with water set at 45 °C
(2)
kW 4.20 5.40 8.60
Power in CH mode with water set at 55 °C
(3)
kW 3.90 4.80 8.00
CH mode COP with water set at 35 °C
(1)
5.20 4.92 4.81
CH mode COP with water set at 45 °C
(2)
3.85 3.58 3.69
CH mode COP with water set at 55 °C
(3)
2.95 2.65 2.93
Flow temperature range
°C
20 - 65
20 - 65
20 - 65
Outdoor temp. limits for Heating mode operation
°C
- 25 / 35
- 25 / 35
- 25 / 35
System integrative resistance absorption (optional)
kW
3 (each kit)
3 (each kit)
3 (each kit)
Cooling circuit
Power in cooling mode with water set at 18 °C
(1)
kW 5.00 6.50 8.70
Power in cooling mode with water set at 7 °C
(2)
kW 3.60 4.70 6.50
Cooling mode EER with water set at 18 °C
(1)
4.59 4.42 4.12
Cooling mode EER with water set at 7 °C
(2)
3.24 3.26 3.33
Flow temperature range
°C
5 - 25
5 - 25
5 - 25
Outdoor temp. limits for Cooling mode operation
°C
10 / 46
10 / 46
10 / 46
DHW circuit
V40 - Water mixed at 40°C
l
245
244
304
Domestic hot water adjustable temperature
°C
10 - 55
10 - 55
10 - 55
Domestic hot water adjustable temperature with
DHW (Domestic hot water) integration resistance
°C
10 - 65
10 - 65
10 - 65
DHW (Domestic hot water) integrative resistance absorption (standard)
kW
2.3 2.3 2.3
DHW (Domestic hot water) integrative resistance absorption (optional) kW
2.3 (each kit) 2.3 (each kit) 2.3 (each kit)
General data
Max hydraulic system operating
bar
3
3
3
System expansion vessel nominal / (real) capacity
litres
24 / (19.70)
24 / (19.70)
24 / (19.70)
Max operating pressure on the DHW (Domestic hot water) system
bar
8 8 8
Rated DHW expansion vessel capacity
litres
16
16
16
C.H. sound power level
dB(A)
58
60
64
Electric protection rating
IP
X5D
X5D
X5D
Power supply (indoor unit)
V - Hz
230-50
230-50
230-50
Permitted voltage range
V
198-264
198-264
198-264
Maximum absorbed power (indoor unit)
W
135
135
135
Absorbed power by the zone 2 or 3 pump (optional)
W
50 (each kit)
50 (each kit)
50 (each kit)
Maximum absorbed power (outdoor condensing unit)
W
2100
2900
4300
Refrigerant fluid load (R32)
g
1200
1200
1400
Water content (in the storage tank)
litres
56 (235)
56 (235)
56 (235)
Condensing outdoor unit empty weight
kg
46.5
46.5
73.0
Indoor unit empty weight
kg
211
211
211