MAGIS HERCULES PRO 12-14-16
40
17.1
ELECTRIC CONNECTION CABLES FEATURES
Features of the indoor unit connection.
The outdoor unit
power cable (not standard supplied) must be suitable for outdoor
installation and must have at least a flexible polychloroprene
sheath (code IEC:60245 IEC 57 / CENELEC:H05RN-F or FG
16). Indicatively, the appropriate cable section can be 6 ~ 10 mm
2
for UE AUDAX PRO 12-14-16 V2, to be checked depending
on the specific installation conditions.
Outdoor Unit
Nominal Values
Field of Tolerable
Voltage
Maximum absorbed
current (MAC) in
normal operation
MAC
✴
1.25 +
Additional Load
Flow rate of the
protective device
required for the
device
Hz
V
V
V
A
A
A
UE AUDAX PRO 12 V2
50
220 - 240
198
264
28
35
35
UE AUDAX PRO 14 V2
50
220 - 240
198
264
30
37.5
40
UE AUDAX PRO 16 V2
50
220 - 240
198
264
32
40
40
Features of the connection between outdoor and indoor units.
Use H07RN-F or H05RN-F class cables to power the indoor
unit.
If the indoor unit is installed in a room with a computer or in-
ternet server, you must use a double shielded FROHH2R class
cable (Aluminium tape/Pol Copper braid).
MAGIS HERCULES PRO Power supply (indoor unit)
BUS communication cable
between outdoor units and
indoor units
Power supply
Max./Min.(V)
Main Power supply
Cable
Power supply Cable
System resistances
Power supply Cable
DHW (Domestic hot
water) resistances
Mono-phase,
220-240V, 50Hz
±10%
2.5 mm², 3 wires
6 mm², 3 wires
4 mm², 3 wires
0,75 ~ 1.5 mm², 2 wires
Single-phase with 2 wires
230 Vac
OUTDOOR UNIT
SUPPLY VOLTAGE
PROTECTION
SWITCHES
UNIT SUPPLY
VOLTAGE
SYSTEM INTEGRATING
RESISTANCE SUPPLY VOLTAGE
COMMUNICATION
CABLE
INDOOR
UNIT
Mono-phase
2 conductors
to 230 Vac
Mono-phase
2 conductors
to 230 Vac
OUTDOOR
UNIT