56
de
fr
en
nl
:
page 64
:
page 69
manual switching
manual switching
activate | deactivate | test
:
page 55
last 20 messages
standard: de, en, fr, nl
:
page 57
423
Main menu
MSBX
Start-up
Check
Parameter
Info
Start-up
MSBX
Check
MSBX
Tightness
Check pumps/valves
Check outputs
Water make-up
View check
Info
MSBX
Type
Pleno PI
Version
V2.10
MinPressure P0
1.8 bar
Initial pres. Pa
2.1 bar
Final pres. Pe
2.5 bar
NS sender BrainCube
1
View messages
View start-up
Parameter
MSBX
Language selection
Date
12.05.2009
Time
15:38
Stat. height HST
15 mWs
T limiter TAZ
<100°C
Safe. valve PSV
3.0 bar
Contact wat.meter
þ
Primary vessel
200 l
Water make-up quant.
Output 1
Contrast
120
1)
Standard: output 1 = alarms
2)
Triggering of an external water make-up
device.
3)
:
Terminal plan page 63,
if
þ
selected, Invers output is switched
(NO
→
NC).
4)
Relevant only if «water make-up active».
5)
For messages M27, M28, M30, ..., please
contact the IMI Hydronic Engineering’s
customer service. The equipment may have
a fault in the electronics and may not work
correctly.
If message M29 appears when the equip-
ment is first switched on or during entering of
the parameters and subsequent power loss
then the unit does not have a fault and M29
can be cancelled.
However if M29 appears during normal
operation it may mean a fault with the elec-
tronics and the unit may not work correctly.
Please contact the IMI Hydronic Engineer-
ing’s customer service.
6)
Set the nominal volume VN if Statico. If
more than one vessel: Set number * VN of
vessels.
7)
The max. make-up quantity calculated by
the BrainCube has been exceeded. There is
a risk of corrosion in the installation. Repair
any leakages in the installation.
8)
Display:
- Total make-up quantity.
- Admissible make-up quantity during
the monitoring period (factory setting: 12
months). If exceeded, message M14 is sent.
- Make-up quantity during monitoring period
in previous months up to current date.
Note: The admissible make-up quantity
during the monitoring period can be changed
manually. If set to 0 litres, the BrainCube
calculates and sets the optimal value.
Important! If higher values are set, there is a
risk of corrosion in the installation.
9)
Not if key lock is activated
:
page 54.
10)
Display for pressure-dependent water make-
up only
:
page 65.
11)
Check the date and time and adjust if neces-
sary.
12)
Only relevant if receiving external make-up
signals through RS 485-1 interface. Display
BrainCube No. from which make-up signals
are received. Factory setting: BrainCube 1 (can
be changed by IMI Hydronic Engineering’s
Customer Service to BrainCube 2, 3 or 4).
13)
Connection information MSBX
:
page 57
1)
8)
6)
12)
10)
10)
9)
9)
9)
9)
To prevent unauthorised
access, the «Start-up» menu
item can be permanently
hidden. It is displayed again
in the same way:
1. press
menu
,
2. press
esc
and hold until
000 appears (at top left
on message line 1),
3. keep holding
esc
and use
scroll
to enter the number
423 (4x right, 2x left,
3x right),
4. release
esc
.
13)
13)
13)
13)
13)
Operation - BrainCube control
menu
– Selected applications
Содержание IMI PNEUMATEX Pleno PI